48
CET Electric Technology
Figure 3-5 Mobile Device Web Interfaces
3.2.4 Accessing PMC-592’s Web Interface
1)
Enter the IP Address of the PMC-592 in the Address area of your Internet Explorer and then press
<Enter>
.
2)
The PMC-592’s Web Interface appears. There are six
Main Menu
items on the left-hand pane –
Global
Status, Metering, Alarm Status, Event Log, Setup
and
Diagnostics
.
3)
The user is not required to login to the Web interface to view data. Login is only required if the
user intends to make changes to the setup parameters.
Figure 3-6 PMC-592’s Web Interface
3.2.4.1 Global Status
The
Global Status
page includes following information:
Parameter
Description
Global/Mains-I/Mains-II
Displays the Global, Mains-I or Mains-II Alarms.
Run Time
Displays Main Unit’s run time since the last power on. Click the
Refresh
icon at the upper right-
hand corner and below the Logout button to enable/disable the
Auto Refresh
function.
Latest Alarm Channel
Displays the latest alarm location.
Total SOE Logs
Displays the current value of the SOE Log Pointer.
Total Energy Log
Displays the current value of the Energy Log Pointer.
Total Waveform Logs
Displays the current value of the Waveform Log Pointer.
DI1/DI2/DI3/DI4 Status
Displays the DI1 to DI4 status.
DI3 and DI4 only appear if the PMC-592 Is equipped with the 4xDIs option.
DO1/DO2 Status
Displays the DO1 and DO2 status.
WFR Manual Trigger
Click
Record
to trigger WFR manually. If
Auto Refresh
is turned on, the
Total Waveform Logs
number
should be incremented.
Table 3-2 Global Status Description