174
CET Electric Technology
Please check via the Web Interface if the
SNTP Time Sync.
is enabled and that the SNTP function
has been properly configured.
If the SNTP Sever is working normally, please follow guidelines below to set SNTP server on
Windows OS.
1)
Set server type as NTP.
a)
Click
Start
and enter
regedit
in
Search
box, press
Enter
and open
Registry Editor
window
.
b)
Choose
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\W32Time\Parameters\Type.
c)
Right-click
Type
and select
Modify…
in the right window.
d)
Enter
NTP
in the
Editing String
box, and then click
OK.
2)
Set
AnnounceFlags
as
5
.
a)
In the
Registry Editor
window, choose
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\W32Time\Config\AnnounceFlags
b)
Right-click
AnnounceFlags
and select
Modify…
c)
Enter
5
in the
Editing String
box, and then click
OK.
3)
Enable
NTPServer.
a)
In the
Registry Editor
window, choose
HKEY_LOCAL_MACHINE\SYSTEM\CurrentControlSet\Services\W32Time\TimeProviders\NtpServer
b)
Right-click
Enabled
and select
Modify…
c)
Enter
1
in the
Editing String
box, and then click
OK.
4)
Make the configuration take effect immediately.
a)
Exit
Registry Editor
.
b)
Enter
net stop w32time && net start w32time
to restart Windows time server, and then
press
Enter
.
If the network firewall allows the NTP access.
1)
Please check the configuration of the Host Firewall to which the SNTP belongs. For example,
permission should be added to the firewall such that the NTP service is accessible from the
outside world.
Coding:
Name
Port
Protocol
Direction
SNTP Timebase
123
UDP
In
2)
If there are other gateways or firewall devices between SNTP Server and PMC-592, please
check to make sure that all these network devices allow SNTP service to pass through.