TC2 Resistance Value
UINT16
Table 5-9 Mains Measurements
Notes:
1)
“×100, V” indicates the value returned in the register is 100 times the actual engineering value with the unit V (voltage). For
example, if a register contains a value 22003, the actual value is 22003/100 = 220.03V.
2)
When the
Wiring Mode
is Delta, the per phase line-to-neutral voltages have no meaning, and their registers are reserved.
3)
The calculation method of Ia/Ib/Ic Loading Factor is listed below:
100%
Rating
Breaker
Ia/Ib/Ic
Factor
Loading
Ia/Ib/Ic
5.2.2 SM Measurements
Register
Property
Description
Format
Scale
Unit
0650
RO
1-Ø SM1 Current
UINT32
x1000
A
0652
RO
1-Ø SM2 Current
UINT32
….
….
0816
RO
1-Ø SM84 Current
UINT32
0818
RO
2-Ø SM1 Current Average
UINT32
0820
RO
2-Ø SM2 Current Average
UINT32
….
….
0900
RO
2-Ø SM42 Current Average
UINT32
0902
RO
3-Ø SM1 Current Average
UINT32
0904
RO
3-Ø SM2 Current Average
UINT32
….
….
0956
RO
3-Ø SM28 Current Average
UINT32
0958
RO
1-Ø SM1 kW
INT32
x1000
kW
0960
RO
1-Ø SM2 kW
INT32
….
….
1124
RO
1-Ø SM84 kW
INT32
1126
RO
2-Ø SM1 kW Total
INT32
1128
RO
2-Ø SM2 kW Total
INT32
….
….
1208
RO
2-Ø SM42 kW Total
INT32
1210
RO
3-Ø SM1 kW Total
INT32
1212
RO
3-Ø SM2 kW Total
INT32
….
….
1264
RO
3-Ø SM28 kW Total
INT32
1266
RO
1-Ø SM1 kvar
INT32
x1000
kvar
1268
RO
1-Ø SM2 kvar
INT32
….
….
1432
RO
1-Ø SM84 kvar
INT32
1434
RO
2-Ø SM1 kvar Total
INT32
1436
RO
2-Ø SM2 kvar Total
INT32
….
….
1516
RO
2-Ø SM42 kvar Total
INT32
1518
RO
3-Ø SM1 kvar Total
INT32
1520
RO
3-Ø SM2 kvar Total
INT32
….
….
1572
RO
3-Ø SM28 kvar Total
INT32
1574
RO
1-Ø SM1 kVA
INT32
x1000
kVA
1576
RO
1-Ø SM2 kVA
INT32
….
….
1740
RO
1-Ø SM84 kVA
INT32
1742
RO
2-Ø SM1 kVA Total
INT32
1744
RO
2-Ø SM2 kVA Total
INT32
….
….
1824
RO
2-Ø SM42 kVA Total
INT32
1826
RO
3-Ø SM1 kVA Total
INT32
1828
RO
3-Ø SM2 kVA Total
INT32
….
….
1880
RO
3-Ø SM28 kVA Total
INT32
1882
RO
1-Ø SM1 PF
INT32
x1000
-