138
CET Electric Technology
6381
RW
P2 Operating Mode~
UINT16
0=Modbus RTU*
1=External DI Module
6382
RW
Number of External DI Modules~
UINT16
0* to 4
6383
RW
DI Module #1 ID~
UINT16
1 to 247, 100*
6384
RW
DI Module #2 ID~
UINT16
6385
RW
DI Module #3 ID~
UINT16
6386
RW
DI Module #4 ID~
UINT16
6387
RW
HTTP Port^
UINT16
1 to 65535, 80*
6388
RW
MODBUS TCP Port^
UINT16
1 to 65535, 502*
6389
RW
MODBUS RTU Port^
UINT16
1 to 65535, 27011*
51800-51839
RW
SMTP Sender Email Address
UINT16X40
See Note (6)
~ Available in Firmware V1.00.03 or later,
#
Available in Firmware 1.00.08 or later, ^ Available in Firmware 1.00.10 or later
Table 5-56 Communication Setup
Notes:
1)
The synchronization Interval should be set between 10 and 1440 minutes.
2)
This string register specifies the username that login the “
Sender Email
” account. This string may be up to 40 characters long.
Please add the value zero “0000” at the end of the string as the string terminator. For example, if the username is “example”,
set the registers as “00 65 00 78 00 61 00 6D 00 70 00 6C 00 65 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00”.
3)
This string register specifies the Password to login the “
Sender Email
” account. This string may be up to 40 characters long.
Please add the value zero “0000” at the end of the string as the string terminator. For example, if the password is “example”,
set the registers as “00 65 00 78 00 61 00 6D 00 70 00 6C 00 65 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00
00 00 00 00 00 00”.
4)
This string register specifies the destination email address that appears in the “To” field of the email. This string may be up
to 40 characters long. Please add the value zero “0000” at the end of the string as the string terminator. For example, if the
email address is
, so set the registers as”00 72 00 65 00 63 00 65 00 69 00 76 00 65 00 72 00 40 00 65
00 78 00 61 00 6D 00 70 00 6C 00 65 00 2E 00 63 00 6F 00 6D”.
5)
The
SNMP Event Subscription
register indicates which SOE will be send out by Trap format with a bit value of 1 meaning send
out by trap.
Bit
Bits 5 - 15
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
SOE
Reserved
Self-test Events
Operation Events
Setpoint Events
DO Events
DI Events
Table 5-57 SNMP Event Subscription
(Reg. # 6378)
6)
This string register specifies the source email address that appears in the “From” field of the email. This string may be up to
40 characters long. Please add the value zero “0000” at the end of the string as the string terminator. For example, if the
email address is
, set the registers as”00 73 00 65 00 6E 00 64 00 65 00 72 00 40 00 65 00 78 00 61 00
6D 00 70 00 6C 00 65 00 2E 00 63 00 6F 00 6D 00 00 00 00”.
5.8.3 SM Name Setup
Register
Property
Description
Format
Note
6050-6069
RW
Meter Model
1
UINT16x20
ASCII
6070-6089
RW
Mains-I Name
UINT16x20
6090-6109
RW
Mains-II Name
UINT16x20
50000-50019
RW
SM1 Name
UINT16x20
50020-50039
RW
SM2 Name
UINT16x20
….
….
51660-51679
RW
SM84 Name
UINT16x20
52000-52019
RW
VM1 Name
UINT16x20
52020-52039
RW
VM2 Name
UINT16x20
…
RW
…
52180-52199
RW
VM3 Name
UINT16x20
Table 5-58 SM Name Register
Notes:
1)
The Meter Model appears in registers 6050 to 6069 and contains the ASCII encoding of the string “PMC-592” as shown in
the following table.
Register
Value(Hex)
ANSCII
6050
0x50
P
6051
0x4D
M
6052
0x43
C
6053
0x2D
-
6054
0x35
5
6055
0x39
9
6056
0x32
2