10
CET Electric Technology
Flexible Configuration
Programmable CT Ratio, CT Polarity, Sub-Meter (SM) Reference Voltage for each SM
Configurable CT Strip Orientation (Sequential or Crossover) and CT Strip Direction (Top or Bottom)
Configurable 2-Ø & 3-Ø SM Ordering based on out-of-sequence 1-Ø SM
Support Single, Dual and Custom Panel Modes
Programmable Label for Device, Panel, 1-Ø SMs and VMs
Metering
Mains Measurements
o
2 Mains, each supporting 3 Voltage and 4 Current Inputs
o
ULN and ULL per phase and average
o
I per phase and average, measured Neutral Current (I4)
o
kW, kvar, kVA, PF per phase and total
o
Frequency
o
Loading Factor per phase
o
kWh Import/Export, kvarh Import/Export, kVAh Total
o
Dual Tariff Energy Metering that is switchable by DI Status and provides T1/T2 kWh
Import/Export, T1/T2 kvarh Import/Export, T1/T2 kVAh Total in Firmware V1.00.10 or later
Branch Circuits Measurements
o
21, 42, 63 or 84 Branch Current Inputs
o
I, kW, kvar, kVA, PF, Loading Factor, kWh, kvarh, kVAh per 1-Ø SM
Demand Measurements
I per phase, kW Total, kvar Total, kVA Total for Mains-I and Mains-II
I, kW, kvar, kVA per 1-Ø SM and kW Total, kvar Total and kVA total per 2-Ø or 3-Ø SM
RTD 1 and RTD 2 Temperature Demand in Firmware V1.00.04 or later
Max Demands with timestamp for Historical, This Month and Last Month
Sub Meters (SM)
Support configurable 1-Ø , 2-Ø and 3-Ø Sub Meters
I Average, Loading Factor, kW/kvar/kVA/PF Total, kWh/kvarh Import and kVAh Total
Demand Values for I Average, kW, kvar and kVA
Max Demands with timestamp for Historical, This Month and Last Month
Virtual Meters (VM)
10 configurable Virtual Meters for arbitrary aggregation from Mains and any of the 84 1-Ø SMs
Support both Addition and Subtraction
kW, kWh/kvarh Import and kVAh per VM
Dual Tariff Energy Metering that is switchable by DI Status and provides T1/T2 kWh, kvarh and kVAh
for Main and GenSet Supply
Power Quality Features
Mains Inputs
o
U and I Unbalance based on Sequence Components
o
U and I THD, TOHD, TEHD and Individual harmonics to 31
st
o
Current TDD, K-Factor and Crest Factor
o
Dip/Swell and Interruption detection with Waveform Recording
Branch Inputs