134
CET Electric Technology
…
RO
..
UINT32
52954
RO
VM10 T1 kWh
UINT32
x10
kWh
52956
RO
VM10 T1 kvarh
UINT32
x10
kvarh
52958
RO
VM10 T1 kVAh
UINT32
x10
kVAh
52960
RO
VM1 T2 kWh
UINT32
x10
kWh
52962
RO
VM1 T2 kvarh
UINT32
x10
kvarh
52964
RO
VM1 T2 kVAh
UINT32
x10
kVAh
52966
RO
VM2 T2 kWh
UINT32
x10
kWh
52968
RO
VM2 T2 kvarh
UINT32
x10
kvarh
52970
RO
VM2 T2 kVAh
UINT32
x10
kVAh
…
RO
…
UINT32
53014
RO
VM10 T2 kWh
UINT32
x10
kWh
53016
RO
VM10 T2 kvarh
UINT32
x10
kvarh
53018
RO
VM10 T2 kVAh
UINT32
x10
kVAh
Table 5-49 VM Tariff Energy
5.8 Setup Parameters
5.8.1 System Parameters
Register
Property
Description
Format
Range/Note/Default*
6000
RW
Panel Mode
UINT16
0 = Single Panel Mode I*
1 = Single Panel Mode II
2 = Dual Panel Mode I
3 = Dual Panel Mode II
4 = Custom^
6001
RW
Nominal Uln Voltage
UINT16
Valid for Firmware V1.00.09 or before &
obsoleted in Firmware V1.00.10 or later
and replaced by Mains-I/II PT Secondary
(Registers 6043 & 6046)
6002
RW
Nominal Frequency
UINT16
0 = 50Hz*, 1 = 60Hz
6003
RW
Mains-II Wiring Mode
UINT16
0 = WYE*, 1 = Delta, 2 = 1P3W
6004
RW
Mains-I CT Ratio.
UINT16
1A: 1* to 30000, 5A: 1* to 6000
6005
RW
Mains-I I4 CT Ratio
UINT16
1* to 10000
6006
RW
Mains-II CT Ratio
UINT16
1A: 1* to 30000, 5A: 1* to 6000
6007
RW
Mains-II I4 CT Ratio
UINT16
1* to 10000
6008
RW
Mains CT Ploarity
1
Bitmap
0* to 255
6009
RW
Power Factor Convention
2
UINT16
0 = IEC*, 1 = IEEE, 2 = -IEEE
6010
RW
kVA Calculation
3
UINT16
0 = Vector*, 1 = Scalar
6011
RW
Demand Period
UINT16
1/2/3/5/10/15*/30/60 (min)
6012
RW
Number of Sliding Windows
UINT16
1* to 15
6013
RW
SMTP Alarm Email Enable
UINT16
0 = Disabled*, 1 = Enabled
6014
RW
Time Zone
4
UINT16
0 to 32, 26*
6015
RW
System Language
UINT16
0 = Simplified Chinese, 1 = English*
2 = Traditional Chinese
6016
RW
DI1 Debounce
UINT16
1 to 9999 (ms), 20*
6017
RW
DI2 Debounce
UINT16
6018
RW
DO1 Trigger Mode
UINT16
0 = None*
1 = Mains-I Instantaneous Alarm
2 = Mains-II Instantaneous Alarm
3 = Global Total Instantaneous Alarm
4 = Mains-I Latched Alarm
5 = Mains-II Latched Alarm
6 = Global Latched Alarm
7 = Voltage-I Phase Reversal
Instantaneous Alarm^
8 = Voltage-II Phase Reversal
Instantaneous Alarm^
9 = Voltage-I Phase Loss Instantaneous
Alarm^
10 = Voltage-II Phase Loss Instantaneous
Alarm^
11 = RTD1 Instantaneous Alarm^
12 = RTD2 Instantaneous Alarm^
13 = DI1 Instantaneous Alarm^
14 = DI2 Instantaneous Alarm^
15 = DI3 Instantaneous Alarm
5
^
6019
RW
DO2 Trigger Mode
UINT16