135
CET Electric Technology
16 = DI4 Instantaneous Alarm
5
^
6020
RW
Mains-I Wiring Mode
UINT16
0 = WYE*, 1 = 1P3W
2 = Demo, 3 = Delta^
6021
RW
Self-Read Time
6
UINT16
0* to 2823, 0xFFFF
6022
RW
Date Format
UINT16
0 = YYYY/MM/DD*
1 = MM/DD/YYYY
2 = DD/MM/YYYY
6023
RW
DI Module #1 Debounce
#
UINT16
1 to 9999 (ms), 20*
6024
RW
DI Module #2 Debounce
#
UINT16
6025
RW
DI Module #3 Debounce
#
UINT16
6026
RW
DI Module #4 Debounce
#
UINT16
6027
RW
Ext. DI Module #1 Excitation Source
#
UINT16
0*=DC, 1=AC
6028
RW
Ext. DI Module #2 Excitation Source
#
UINT16
6029
RW
Ext. DI Module #3 Excitation Source
#
UINT16
6030
RW
Ext. DI Module #4 Excitation Source
#
UINT16
6031-6034
RW
Reserved
UINT16
6035
RW
Phase A Color
7#
UINT16
1-8, 2*
6036
RW
Phase B Color
7#
UINT16
1-8, 4*
6037
RW
Phase C Color
7#
UINT16
1-8, 6*
6038
RW
Phase N Color
7#
UINT16
1-8, 8*
6039
RW
DI3 Debounce
8
~
UINT16
1 to 9999 (ms), 20*
6040
RW
DI4 Debounce
8
~
UINT16
6041
RW
Mains-I PT Primary
9
^
(Should be specified as Line Voltage)
UINT32
1 to 1,000,000, 380V*
6043
RW
Mains-I PT Secondary
9
^
(should be specified as Line Voltage)
UINT16
1 to 480V, 380V*
6044
RW
Mains-II PT Primary
9
^
(Should be specified as Line Voltage)
UINT32
1 to 1,000,000, 380V*
6046
RW
Mains-II PT Secondary
9
^
(Should be specified as Line Voltage)
UINT16
1 to 480V, 380V*
6047
RW
Branch CT‘s Mains
10
^
UINT16
0 to 15, 12*
6048
RW
Tariff Switch
11
^
UINT16
0 = Disabled*
1 = DI1, 2 = DI2, 3 = DI3, 4 = DI4
#
Available in Firmware V1.00.03 or later
~ Available in Firmware V1.00.08 or later
^ Available in Firmware V1.00.10 or later
Table 5-50 Basic Setup Parameters
Notes:
1)
The
Mains CT Polarity
register indicates the various Mains current polarities with a bit value of 0 meaning normal and 1
meaning reverse. The following table illustrates the details of the
Mains CT Polarity
register.
Bit
Bit 3
Bit 2
Bit 1
Bit 0
Mains-I Current Polarity
Mains-I Ia
Mains-I Ib
Mains-I Ic
Mains-I I4
Bit
Bit 7
Bit 6
Bit 5
Bit 4
Mains-II Current Polarity
Mains-II Ia
Mains-II Ib
Mains-II Ic
Mains-II I4
Bit
Bits 8 - 15
Reserved
Table 5-51 Mains CT Polarity Register (Reg. # 6008)
2)
P.F. Convention: -IEEE is the same as IEEE but with the opposite sign.