64
Technical instructions
Cm
-SOL
8.x. DHW heating
8.x. DHW heating
In this menu are additional menus for setting the heating with the
conventional heating sources connected to tank 1.
8.x.x. Electric heater
In this menu are additional menus for setting the heating with the electric
heater.
Electric heater
OFF
Factory settings
OFF/ON
8.x.x.1. Electric heater
In this menu electric heater can be switch ON or OFF
8.x.x. Boiler 1
In this menu are addtional settings for heating with conventional source
1.
8.x.x.1. Boiler 1
In this menu for heating with conventional heating source 1 can be
enabled or disabled (ie. work of pump between conventional heat
source and tank 1).
8.x.x.2. T MAX Boiler 1
Setting of the maximum temperature of the conventional heating source
1. If the temperature in conventional heating source is higher than set,
pump to the tank will not start.
T MAX Boiler 1
90
Factory settings
min./max.
30 / 90
°C
Boiler 1
OFF
Factory settings
OFF/ON
8.4.2.3. TD boiler1-tank1 (difference)
Setting of the temperature difference between conventional heating
source 1 and first tank (upper sensor) for start and stop of the pump
between boiler 1 and tank 1. Some of the conditions:
pump start: [Tboiler1=>
TDboiler1-tank
+5]
pump stop: [Tboiler1=<
TDboiler1-tank
]
TD boiler1-tank
10
Factory settings
min./max.
3 / 20
°C
8. . .4. TH boiler1-tank1 (hysteresis)
x x
Setting the temperature hysteresis between conventional heating source 1
and fist tank (upper sensor) for start of the pump between boiler 1 and tank
1. Some of the conditions:
pump start: [Ttank1upper<TDHW-
-T
]
THboiler1-tank
lowering temperature
TH boiler1-tank
10
Factory settings
min./max.
3 / 20
°C
Installation, tank heating
example: configurated 1 electric heater and
2 conventional heating sources
selection
selection
unit.
unit.
unit.