8.3.x.2. TDif Tank2->Tank1 (difference)
Setting the temperature difference between second and first tank (upper
sensors) for start and stop of the mixing/heating pump.
Tdif Tank2->Tank1
4
Factory settings
min./max.
1 / 10
°C
8.3.x. Pulse start pool
This menu is shown only if pool is set in the configuration.
In this menu are additional menus for setting the pulse start of the pool
pump (kick).
If pool sensor can’t be installed into place where it can read correct
temperature, it’s recommended to enable pulse start of the pump (when
pump is still) which occasionaly starts the pump for set time, to read correct
tempearature of the pool sensor.
NOTE:
to offten and to long work of the pool pump power supply
consumption can be increrased and pool can be cooled! Work and pause
time of the pool pump depends of the location of the pool sensor.
8.3.x.1. Pulse start pool
In this menu pulse start of the pool can be enabled or disabled. All set
times and schedule are valid.
Pulse start pool
OFF
Factory settings
setting
OFF/ON
Pump working time
60
Factory settings
min./max.
0 / 3600 sec
8.3.x.3. Pump working time
Setting the working time of the pump in pulse start.
NOTE:
Time must be set according to the position of the pool sensor to
have correct pool temperature and start with the pool heating as soon as
possible.
Pump pause time
15
Factory settings
min./max.
0 / 1440 min
8.3.x.2. Pump pause time
Setting the pause time of the pool pump in pulse start.
NOTE:
Time must be set according to the position of the pool sensor to
have correct pool temperature and start with the pool heating as soon as
possible.
8.3.12.4.Schedule
In this menu are additional menus for setting the schedule for pulse start
(kick) of the pool pump.
Schedule can be switch off or one of two tables with adjusted on/off
intervals can be set.