1. TANK
User menu, tank
18
USER MENU (MAIN MENU)
THE NUMBERS OF MENU AND MENU
S
ARE CHANGING ACCORDING
TO THE SELECTED CONFIGURATION
(here are shown only fix numbers
(which are always the same), and other changeable numbers are marked
with x, menu depth where the parameter is located).
The menu 1. Tank contains menus associated with configured tanks.
Depending on the configuration, here are displayed menus for 1 to max
4 tanks.
DHW temperature
55
Factory settings
min./max.
10 / 85
°C
unit.
example: configuration 2 tanks,
function mixing-heating
1.x.
T MAX tank 1
Set
ting
maximum tank temperature 1.
Solar
c
ollectors
h
eat
t
ank 1 to
t
emp. [T MAX tank 1]
after which the heating of the tank 1 stops and the heat is transferred to
the next tank by priority (if available).
If the collector cooling function is activated, the temperature in the tank
can increase to max. 90 ° C (or 95°C if the TMAX Tank 1 is set at 90°C).
T MAX tank 1
70
Factory settings
min./max.
30 / 90
°C
unit.
1.x.
T MAX tank 2
Set maximum tank temperature 2.
Solar Collectors Heat Tank 2 to Temp. [T MAX Tank 2] after which the the
heating of the tank 2 stops and the heat transfer to the next container by
priority (if available). If the active cooling function of the collector is also
activated, the temperature in the tank can increase to max. 90°C (or
95°C if the TMAX tank is set to 90 ° C.
T MAX tank 2
T MAX tank3
T MAX tank 4
70
70
70
30 / 90
30 / 90
30 / 90
°C
°C
°C
If the
last tank in configuration is
swimming pool, the max. swimming
pool temperature can be adjusted in the following range:
T MAX tank X
28
Factory settings
min./max.
15 / 40
°C
unit.
1.x
DHW temperature
Set
ting of
d
esired DHW
(domestic hot water)
temperature.
Conventional energy sources (el. heater, boiler1 and boiler2) heat the
DHW tank to the desired DHW temperature.
NOTE
:
DHW temperature applies only to the conventional sources
.
Solar collectors heat tank up to tank temperature T
MAX
tank.
Technical instructions
Cm
-SOL
Setting of