21
CV072018-1
AutoMinutes
000 -> 240
This parameter is available only if the auto parameter is set to a value other than none. No (default value) there is no effect on the operation of
the system. It is a value expressed in minutes, it represents the interval of time elapsed since the signal of the external device for the auto mode
has reached, or exceeded, the value AutoMax% or Auto Max ppm, without descending below said value, above which indicates an anomaly in
the external device (CO2 probe, HR or external signal).
AutoOn %
000 ->100
This parameter is available only if the auto parameter is set to ext. or HR sensor and the digital output is set to auto cmp. Default value 050, is
expressed in%; for values of HR% measured by the relative humidity sensor (or for values of the external signal 0-10V in percentage) lower than
the set, the digital output changes state.
AutoOff%
000 ->100
This parameter is available only if the auto parameter is set to ext. or HR sensor and the digital output is set to auto cmp. Default value 050,
expressed in%; for values of HR% measured by the relative humidity sensor (or for values of the external signal 0-10V expressed in percentage)
higher than the adjusted one, the digital output returns to the normal state.
AutoOn ppm
0000 -> 2000
This parameter is available only if the auto parameter is set to CO2 VOC and the digital output is set to auto cmp. Default value 0500, expressed
in ppm; for ppm values measured by the CO2 probe lower than adjusted, the digital output changes state.
AutoOff ppm
0000 -> 2000
This parameter is only available if the auto parameter is set to CO2 VOC and the digital output is set to auto cmp. Default value 0500, expressed
in ppm; for ppm values measured by the CO2 probe above the adjusted one, the digital output returns to the normal state.
Bypass Tmin
12->18
This parameter is active only if the bypass management is set to Universal (Factory menu). Default value 15, expressed in degrees centigrade.
It is the minimum temperature value (Tmin) that the system will attend to bypass management in the case that Automatic Bypass is set in the
Parameters menu.
Bypass Tmax
20->30
This parameter is active only if the bypass management is set to Universal (Factory menu) .- Default value 22, in degrees centigrade. It is the
maximum temperature value (Tmax) that the system will attend to bypass management in case Parameter is set to Automatic bypass.
Hours filters
00000 -> 99999
This parameter is active when the jammed filters alarm is based on the hours of operation of the unit (Factory menu) Default value 02000,
in hours. Represents the number of hours of operation of the unit after which the dirty filter alarm will be triggered. To reset the alarm, the
installer must set the new limit at which the signaling of the alarm is desired (check current operating hours in the status menu, parameter
Vent hours):
Hours filters = Hours vent. + hours for new alarm
Regulation
Tr on-off
This parameter allows to modify, when there is air after treatment, the reference for the set point. Normally based on the return temperature
(on), changing the value to off becomes the intake temperature.