30
CV072018-1
91
DP _SUPPLY
B15: DPEXHAUST_FAIL
FOR UNITS COP = VALUE OF
PRESSURE SIDE IMPULSION FAN
92
DP
_EXHAUST
(Pa)
FOR UNITS COP = VALUE OF
PRESSURE SIDE FAN RETURN
93
FLOW_SUPPLY
(m3/h)
FOR CAV UNITS = FLOW VALUE FLOW VALUE.
IMPULSION
94
FLOW_EXHAUST
(m3/h)
FOR CAV UNITS WITH DOUBLE PROBE = FLOW
VALUE SIDE VALUE. RETURN
95
FAN_HOURS_H
(65536 h)
OPERATING TIME FANS (FAN_HOURS_H * 65536+
FAN_HOURS_L)
96
FAN_HOURS_L
(h)
97
ALARMS 2
B00: CONFIGURATION_FAIL
B01: ANTI ICE_FAIL
CONFIGURATION ERROR ANTIFREEZE ALARM
98
PRE_HEAT
(%)
PERCENTAGE MODULATING PRE-HEATING REGULATION.
99
POST_HEAT
(%)
PERCENTAGE REGULATION POST-HEATING MODUL.
UNIT_2_DATA
101
TEMP_E
R
UNIT_4_DATA
141
TEMP_E
R
1001
1002
1003
TIME_TABLE_SPEED_0
TIME_TABLE_SPEED_1
TIME_TABLE_SPEED_2
IF CONFIG_FLAGS_1.MODULE_FLAG = 0 :
0-1-2-3) OR AUTO(5)
IF CONFIG_FLAGS_1.MODULE_FLAG = 1
and PRESS_FLOW_REG_PRESENT = 0 :
0-100% OR AUTO(102)
IF CONFIG_FLAGS_1.MODULE_FLAG = 1
AND PRESS_FLOW_REG_PRESENT = 1 :
0 - SPEED_RANGE OR
AUTO(65535)
RW
SELECTION OF SPEED A
ASSOCIATE TO THE TIME FRAME
1017
1024
MONDAY-CHANGE-0
/ 7
B00-10: TIME - MINUTES
B11-13: SPEED SELECTION :
000: TIME_TABLE_SPEED_0
001: TIME_TABLE_SPEED_1
002: TIME_TABLE_SPEED_2
B14-15: TEMPERATURE REG. ENABLE
00: OFF
01: ON
RW
ADJUST TIME IN MINUTES FROM
00.00 (EJ.:60=1.00)
SELECTION OF SPEEDS
TEMPERATURE SELECTION
1025
1032
TUESDAY-CHANGE-0
/ 7
RW
AS THE PREVIOUS
1033
1040
WEDNESDAY-CHAN-
GE-0 / 7
RW
AS THE PREVIOUS
1041
1048
THURSDAY-CHANGE-0
/ 7
RW
AS THE PREVIOUS
1049
1056
FRIDAY-CHANGE-0 / 7
RW
AS THE PREVIOUS
1057
1064
SATURDAY-CHANGE-0
/ 7
RW
AS THE PREVIOUS
1065
1072
SUNDAY-CHANGE-0
/ 7
RW
AS THE PREVIOUS