17
CV072018-1
Humidity (%)
This parameter is available only when a dehumidification system is planned. Represents the threshold value above which dehumidification is
enabled. The default value is 50%. Dehumidification can also be forced by a digital input.
INSTALLER MENU: CONFIGURATION OF INSTALLATION PARAMETERS
To access this menu, you need to enter a password (5678) to avoid inadvertent modification by non-expert users of parameters that could
compromise the correct operation of the installation.
To enter the password, press the down arrow so that the corresponding line is indicated, press the OK button and enter the first digit. Select
the desired value using the up / down arrows and press OK when you reach it.
Repeat the operation for the three remaining figures. If the password has been entered correctly, the installer menu is displayed; otherwise,
you return to the introduction page. To modify the parameters of this menu, select the desired one (scrolling with the up/ down arrows) and
press the OK button. The currently established value is shown in green, at this point it is possible to modify it using the arrows and pressing
OK to confirm the selection. The parameters related to the coefficients and flow/ pressure values are available only for machines with kit, the
display or not of such parameters is linked to the settings in the factory menu.
Bypass configured in universal mode (Factory menu), three values can be selected for the bypass parameter:
Automatic bypass:
A temperature range, comprised between TMIN and TMAX, is considered comfortable for the user; If the internal temperature (Tr) is within this
range, the bypass will remain closed. When Tr is out of this range (Tr> TMAX or Tr <TMIN) the control will open the bypass in case the external
temperature (Te) is within the comfort range (TMIN <Te <TMAX); otherwise, the bypass will remain closed.
Not defined or automatic
This parameter is available only when a dehumidification system is planned.
Through this you can enable (Yes) or inhibit (No) the dehumidification
system. It can be used, for example, in the winter season, if you do not want
to dehumidify.
digital input
insert password
Installer menu