background image

4

CV072018-1

MANAGEMENT OF FAN SPEED, FLOW OR CONSTANT PRESSURE

To modify this parameter, the icon at the top right of the synoptic table must be selected by clicking on it (it will turn green and the direction 
buttons will appear). Then press the icon of the address button up to increase or down direction to decrease the value located next to it; Once 
the desired one is located, press the OK button to confirm the selection. At first it is possible to turn off the machine directly by pressing the 
central button, it disappears automatically by pressing the direction buttons. The variation can be expressed as a percentage for variable spe-
ed machines, with a simple 1-2-3 for machines with 3 speeds, in flow (m³ \ h) for machines with constant flow or pressure (Pa) for machines with 
constant expression (equipped with the corresponding supplementary kit, see page 29). For these last two models, once the desired value has 
been selected, the speed of the fans will automatically vary to keep the flow or the set pressure constant. For machines with a sensor mounted 
different from the cop / cav kit, but always with constant pressure or flow rate, enter the percentage value of the pressure or flow scale of the 
unit. The regulation it will be carried out in the same way. This also applies to the settings of the weekly programming menu (Program). In 
addition to the scale value, the timer element will appear and, if selected, will start the default weekly time program (see Program menu). If an 
air quality, relative humidity sensor is present in the unit or if the analog input (0-10V) is activated, we will also have the automatic selection 
that allows the automatic regulation of the fan speed in function of CO2, Humidity measured or by an external signal.

In detail the possible selections are:

- off: 

with this selection, the fans are stopped. Be careful because in any case the unit is electrically powered; this value is obtained by descen-

ding below the minimum adjustable speed.

-xxx%:

 if the unit has modulating fans it is possible to adjust a percentage value of the speed, flow rate or full-scale pressure (for units not 

equipped with the corresponding kit but always in a cop / cav version with a different sensor), starting from a minimum (factory adjusted) to 
100% with steps of 5% (1% on request).

-1,

 

2

 

or

 

3

: if the unit is equipped with 3-speed fans, it is possible to select one of the available ones: speed 1, speed 2 or speed 3.

-watch:

 with this selection the speed of the fans is controlled according to what is established by the weekly chronoprogram (see Program 

menu), this indication is obtained by selecting a value higher than the maximum speed (100% or 3).

-

 

auto:

 this mode is available only if a sensor (CO2, CO2-COV, relative humidity HR) or an external signal (0-10V) is present. It is obtained by 

selecting a value higher than clock.

-

 

xxx

 

 

\

 

h:

 if the unit is a constant flow (CAV) version with a kit, the desired value can be set in m3 \ h of flow. The fans will be regulated au-

tomatically to keep it constant depending on the changes in the load.

Speed fan controller (%)

Airflow control

Pressure control

Direction buttons

Direction buttons

on/off

Содержание CTRL-DPH

Страница 1: ...www casals com CV072018 1 CTRL DPH USER MANUAL AND SET INSTRUCTIONS...

Страница 2: ...T PROG PREDEF TIMETABLE ADJUSTMENT OF SPEED LEVELS CLOCK MEN CLOCK SETTINGS ALARMS MEN VISUALIZATION OF THE STATUS OF THE ALARMS INSTALLER MEN CONFIGURATION OF THE INSTALLATION PARAMETERS WINTER SUMME...

Страница 3: ...es to green and modifications can be made with the direction buttons The main window is a detailed graphic representation of the state of the machine from which all available functions can be activate...

Страница 4: ...ee Program menu If an air quality relative humidity sensor is present in the unit or if the analog input 0 10V is activated we will also have the automatic selection that allows the automatic regulati...

Страница 5: ...d an icon thermometer with a temperature value appears in the lower right corner On its side and on the flow of the driving air a picture of post heating cooling appears Selecting the icon in the bott...

Страница 6: ...ating status is shown in the main window MENU SELECTION From the main window you access the menu window by touching the corresponding icon window change icon You have to scroll with the up arrow key a...

Страница 7: ...elative to the coil is activated when the temperature measured by the Tw probe falls below 3 C and then deactivates when it returns above 5 C 3 2 When a temperature below 3 is detected the control val...

Страница 8: ...the fans operate at the speed set on the remote panel Off if DI open fans stopped Boost It is active if a digital input DI is configured as a booster parameter adjustable in the factory end DI open an...

Страница 9: ...n system Air temperature after the cold coil in C The digital inputs outputs can be programmed from the factory menu by asking the manufacturer for passwords and instructions on the available function...

Страница 10: ...8 00 21 59 high ON C7 22 00 00 00 medium OFF C8 not used SPEED LEVELS Low Medium sp OFF Medium sp 030 if the unit is equipped with adjustable speed fans 1 if the unit is equipped with three speed fans...

Страница 11: ...using the arrows increases arrow up or decreases arrow down the schedule in 30 minute sections Once you have located the desired value press OK This parameter can take a value between the beginning o...

Страница 12: ...or the weekly programming it is necessary to access the main page of the Program menu with the arrows indicate the level to be modified for example Low speed and press the OK button Using the arrows y...

Страница 13: ...he OK button to confirm the selection the day will change from green to blue Settingthetime Select the hours hour line and press the OK button the current time set will turn green Scroll with the dire...

Страница 14: ...eplace the temperature probe 3 If the problem persists replace the electronic card Tr return ok Return air temperature sensor works correctly ko Problem in the return air temperature sensor 1 checkthe...

Страница 15: ...y ko External signal not present voltage at terminals equal to 0V 1 checktheelectricalconnectionsoftheexternalsource seeelectricaldiagrams 2 if the problem persists check the presence of the external...

Страница 16: ...ed only when the control detects that the conditions exist for which the current station should be selected It may be due to the winter summer settings in the installer menu see or the presence of a c...

Страница 17: ...n arrows and press the OK button The currently established value is shown in green at this point it is possible to modify it using the arrows and pressing OK to confirm the selection The parameters re...

Страница 18: ...ction of the device see the electrical diagram ex signalThe speed of the fans will be regulated by an external 0 10V analog signal default value if the external signal assumes a value equal to 0V the...

Страница 19: ...2 VOC The speed of the fans will be regulated by a CO2 sensor or CO2 VOC with 0 10V output and linear characteristic between 0 and 2000 ppm 0V correspond to 0 ppm and 10V correspond to 2000 ppm if the...

Страница 20: ...priate value to assign to the parameter AutoMax ppm This parameter is available only if the auto parameter is set to CO2 VOC It can take values between 20 ppm and 2000 ppm steps of 20 ppm with the lim...

Страница 21: ...than adjusted the digital output changes state AutoOff ppm 0000 2000 This parameter is only available if the auto parameter is set to CO2VOC and the digital output is set to auto cmp Default value 05...

Страница 22: ...nu 1000Pa DpEstr XXX DpIng 067 150 This parameter is available only for constant pressure units with control over the two flows Default value 100 expresses in percentage the desired ratio between the...

Страница 23: ...elative to the return flow default 0 40 Tau Caud E s This parameter is available only for constant flow units with control over the two flows Factory menu It is the integral time value relative to the...

Страница 24: ...his value it will be closed if it is modulating only free cooling or free cooling it will be regulated in it It is also used as a minimum reference for aftercare Ti Entr Max 28 40 This parameter is av...

Страница 25: ...assign to serial communication default 9600 Stop bits It can be configured only for the RS485 protocol Represents the value of the stop bit that you want to assign to serial communication default 1 Co...

Страница 26: ...ver after connecting the network machine open your browser and type in the address bar http 192 168 1 243 The main screen will appear as in the figure On the screen we find a reproduction of the typic...

Страница 27: ...0 AND AF TER IT IS IN 1 IT MEANS THAT THERE HAS BEEN A RESET OF THE CARD B01 R TERMINAL_ACTIVE 1 ACTIVE TERMINAL CONNECTION B02 R TERM_RS485_ACTIVE 1 ACTIVE TERMINAL CONNECTION RS485 B04 R W CONNECTIO...

Страница 28: ...TIMER 0 14400 sec R W MAXIMUM SPEED TIMER FANS 54 SPEEDS REMOTE CONTROL B00 06 REMOTE_SUPPLY_SPEED 0 100 B07 SUPPLY_SPEED_REMOTE_CONTROL 0 OFF 1 ON B08 14 REMOTE_ EXHAUST_SPEED 0 100 B15 EXHAUST_SPEED...

Страница 29: ...E IF FANS_FAIL_TACH REG 7 B08 IS SET TO 1 RPM OTHERWISE R SPEED FAN IN RETURNS OR PERCENTAGE SEE REGISTER 7 B08 88 SPEED_D_VALUE IF FANS_FAIL_TACH REG 7 B08 IS SET TO 1 RPM OTHERWISE R SPEED FAN RETUR...

Страница 30: ...EED_0 TIME_TABLE_SPEED_1 TIME_TABLE_SPEED_2 IF CONFIG_FLAGS_1 MODULE_FLAG 0 0 1 2 3 OR AUTO 5 IF CONFIG_FLAGS_1 MODULE_FLAG 1 and PRESS_FLOW_REG_PRESENT 0 0 100 OR AUTO 102 IF CONFIG_FLAGS_1 MODULE_FL...

Страница 31: ...OL FEATURES Power supply 9 30 VDC 250mW working temperature between 0 and 50 C storage temperature between 20 C and 70 C WARRANTY CONDITIONS The warranty period of 2 years 24 months begins with the re...

Страница 32: ...32 CV072018 1 DIMENSIONS mm...

Страница 33: ...CV072018 1 ASSEMBLY mm Insert two supports to the right and left of the panel Push the support upwards and the panel down until the panel is completely fixed in the support Place the panel on the sta...