![Casals CTRL-DPH Скачать руководство пользователя страница 18](http://html1.mh-extra.com/html/casals/ctrl-dph/ctrl-dph_user-manual-and-instructions_2566782018.webp)
18
CV072018-1
PARAMETERS AVAILABLE IN THE INSTALLER MENU
Language
With this parameter you can select the language in which all the menus will be displayed (with the exception of the Factory menu, which will
always be displayed in English).
GB
English display (default value)
FR
Display in French
ES
Display
in
Spanish
IT
Display in italian
NL
Display
in Dutch
DE
Display in German
HU
Display in Hungarian
DK
Display in Danish
PT
Display in Portuguese
SI
Display in Slovenian
Auto
With this parameter you can configure a device to regulate the fan speed automatically. For the connection of the device see the electrical
diagram.
ex signal The speed of the fans will be regulated by an external 0-10V analog signal (default value); if the external signal assumes a value equal
to 0V; the control will signal a problem of the external signal source. For units equipped with variable speed fans:
AutoMin%
corresponds to the percentage of the input signal by which the fans must operate at the minimum speed.
AutoMax%
corresponds to the percentage of the input signal by which the fans must operate at maximum speed.
For units equipped with three-speed fans:
SP. 1,2% = Automax% - A AutoMin%
SP. 2,3% = 7 x (AutoMax% - AutoMin%) + AutoMin%
∆
= Automax% - AutoMin%
12
10
5
The values of SP.1.2% SP.2.3% and A depend on the values of the two parameters AutoMin% and AutoMax% according to the following: