PREHEATING MANAGEMENT
In addition to the post-heating, the CTRL-DPH control is able to manage an electric preheating system (operated by a PWM signal or on-off)
to prevent the formation of ice inside the heat exchanger. The control automatically activates the anti-frost procedure when the temperature
measured by the expulsion probe (Tx) drops below the value of 3 °C. Here the heater is powered at the minimum power. If the temperature Tx
continues to decrease and falls below 1 °C, the feed of the preheater is progressively increased until it reaches 100%. When Tx returns above
3 °C the procedure is interrupted. The temperature values 3C° and 1C° are set at the factory and can be modified on request. The preheating
status is shown in the main window.
MENU SELECTION
From the main window you access the menu window by touching the corresponding icon (window change icon). You have to scroll with the
up arrow key and then press OK on the desired item. When selecting, you access the diverse detailed information about the installation. When
the last menu item is reached, the arrow below disappears.
On the other hand, when you go beyond the first one, the window change icon appears with the arrow to the left. To return to the previous
menu, click on the latter.
In the menu window you can access the following functions:
- Status
- Program
- Clock
- Alarms
- Installer
- Factory (protected by password, accessible only by factory).
From the Menu window, you access the main window by pressing the up arrow button until the window change icon appears and pressing OK.
Menu selection window
Active post-heating
Postheating off
Central window change icon