90
<2 Step Feeding, 2 Step Discharging Mode_1>
Relay Operation Graph upon Setting (F6.03-8)
1. Required set value input : Step 2(SP2) > Step 1(SP1), Step 4(SP4) – Fall(SP8) > Step 3(SP3)
2.
SP1:
Step1,
SP2:
Step2,
SP3:
Step3,
SP4:
Step4,
SP5:
Upper Limit NG,
SP6:
Lowest Limit NG,
SP7:
Final,
SP8:
Fall
3. Near zero output is according to the specified range in F1-23
4. T1 : Refer to F6.04 (Delay time of weighing Finish relay output)
T2 : Refer to F6.05 (Operation time of weighing Finish relay output)
5. Relay Output
Step 1 : OFF when ( SP1 ≤
Weight
)
Step 2 : OFF when ( SP2 ≤
Weight
)
Step 3 : ON When start input, OFF when (SP3 ≤
Discharge
Weight)
Step 4 : ON When start input, OFF when {(SP4 – SP8) ≤
Discharge
Weight}
Finish : On after T1 (set time), ON during T2 (set time)
Near Zero : F1-23 set value ≥
Weight
≥ 0 range output
6. Status lamp in the front panel is operated in the same manner as the RELAY output.