Compressor Stage 1 Maximum Runtime
The maximum amount of time to run stage 1 before engaging stage 2. This
prevents stage 1 from running for an excessive amount of time before
compressor stage 2 is engaged. When set to Auto, the Carrier control algorithms
decide when to stage.
Default:
Auto
Options:
Between 10 and 120 minutes or Auto
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Thresholds >
Compressor Configurations > Compressor stage 1 maximum
runtime