Thresholds
This menu lets you configure the temperature and time thresholds associated with the
heating and cooling equipment
’s sequence of operation. You must configure
before setting the thresholds. Depending on your system's equipment, not all
options may be available.
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Operating
Thresholds
Auto Change Over and Deadband
Enable or disable the auto change-over between heating and cooling modes. Enabling
this option allows you to select auto change-over as a system mode. The auto
changeover feature enables the thermostat to automatically change between heating
and cooling modes as needed. This keeps the home above the
“Heat To” temperature
and below
the “Cool To” temperature you have selected.
The deadband temperature is the minimum difference allowed between the “Cool To”
and the
“Heat To” temperature setpoints when in auto mode. Adjusting the cooling
setpoint
downward will “push” the heating setpoint downward and vice versa to enforce
the deadband.
For example, if the Cool To setting 75F, the Heat To setting is 72
o
F, and
the deadband setting is 3
o
F, then decreasing the Cool To setting to 74
o
F will force the
Heat To setting to 71
o
F.
Default:
Enabled, 2
o
F
Options:
Enabled, Disabled; adjustable between 2
o
F and 6
o
F
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Thresholds > Auto
Change Over