33 |
P a g e
Dehum Active
The dehumidifier active state setting determines whether the accessory terminals
should be open or closed in order to dehumidify. When set to active Open (also
referred to as active low), the thermostat will open the output contacts removing
voltage from the terminal when it calls for dehumidification. When set to active
Closed (also referred to as active high), the thermostat will close the output
contacts applying voltage to the ACC
+
terminal when it calls for dehumidification.
Default:
Open
Options:
Open, Closed
Содержание TP-WEM01
Страница 38: ...38 P a g e ...
Страница 50: ...50 P a g e ...