57 |
P a g e
Compressor Minimum Off Time
After a cycle has ended, the compressor must be off for this time before starting
up again. This setting is used to allow the refrigerant pressures to equalize in the
system so the compressor is not started up under load, which can cause thermal
limit trips.
Default:
5 minutes
Options:
Between 5 and 15 minutes
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Thresholds >
Compressor Configurations > Compressor Minimum Off Time
Содержание TP-WEM01
Страница 38: ...38 P a g e ...
Страница 50: ...50 P a g e ...