65 |
P a g e
Auxiliary Heat Stage 1 Max Runtime (Heat Pumps)
The auxiliary heat stage 1 maximum runtime setting controls the stage timer
for auxiliary heat terminals W1 and W2. The maximum amount of time to run
stage 1 before engaging stage 2. The factory default is Auto, which uses
Carrier control algorithms to decide when to engage auxiliary heat.
Default:
Auto
Options:
Between 10
– 120 minutes or Auto
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Operating
Thresholds > Auxiliary heat Configuration > Auxiliary Heat Stage 1
Max Runtime
Содержание TP-WEM01
Страница 38: ...38 P a g e ...
Страница 50: ...50 P a g e ...