Maximum Setpoint Delta
NOTE
: This menu is not available for heat recovery (HRV) or energy recovery
ventilator (ERV) types.
When Free Cooling is enabled, the maximum setpoint delta will put an upper limit
on engaging Free Cooling based on the difference between the indoor
temperature and the cool to setpoint. If the different between the indoor
temperature and setpoint is greater than this setting then Free Cooling will not be
engaged.
Default:
Off
Options:
Off, 2, 3, 4, 5, …, 15, 16°F