Record Configuration Information
*Not supported.
TOUCH PILOT™
DESCRIPTION
NAVIGATOR
ITEM
NAVIGATOR™
SUBMODE
RANGE
DEFAULT
ENTRY
Cooler Heater Delta Spt
HTR
Configuration
SERV
XX.X
2.0*
Entering Fluid Control
EWTO
Configuration
SERV
NO-YES
NO
Auto Start When SM Lost
AU.SM
Configuration
SERV
NO-YES
NO
Brine Freeze Setpoint
LOSP
Configuration
SERV
XX.X
34
Brine Flow Switch SP
FL.SP
Configuration
SERV
XX.X
1*
Element
CCNA
Configuration
OPTN
XXX
1
Bus
CCNB
Configuration
OPTN
XXX
0
Baud Rate
BAUD
Configuration
OPTN
X
3/9600
Circuit Loading Sequence
LOAD
Configuration
OPTN
X
EQUAL
Staged Loading Sequence
LLCS
Configuration
OPTN
X
AUTOMATIC
Ramp Loading Select
RL.S
Configuration
OPTN
ENBL-DSBL
DSBL
Unit Off to On Delay
DELY
Configuration
OPTN
XX
1
Ice Mode Enable
ICE.M
Configuration
OPTN
ENBL-DSBL
DSBL
Condenser Pumps Sequence
HPUM
Configuration
OPTN
X
0/NO PUMP
Cooler Pumps Sequence
PUMP
Configuration
OPTN
X
0/NO PUMP
Pump Auto Rotation Delay
ROT.P
Configuration
OPTN
XX
48
Pump Sticking Protection
PM.PS
Configuration
OPTN
NO-YES
NO
Stop Pump During Standby
P.SBY
Configuration
OPTN
NO-YES
NO
Flow Checked if C Pump On
P.LOC
Configuration
OPTN
NO-YES
NO
Start Hour (Night Control)
LS.ST
Configuration
OPTN
XX.XX
00.00
End Hour (Night Control)
LS.ND
Configuration
OPTN
XX.XX
00.00
Capacity Limit (Night Control)
LS.LT
Configuration
OPTN
XXX
100
Reverse Alarms Relay
RV.AL
Configuration
OPTN
NO-YES
NO
Heating OAT Threshold
OA.TH
Configuration
OPTN
XX.X
5 F
Current Limit Select
CUR.S
Configuration
OPTN
NO-YES
NO
Current Limit at 100%
CUR.F
Configuration
OPTN
XXXX
2000
Auto Changeover Select
AUTO
Configuration
OPTN
NO-YES
NO
Cooling Reset Select
CRST
Configuration
RSET
X
0
Heating Reset Select
HRST
Configuration
RSET
X
0
Demand Limit Type Select
DMDC
Configuration
RSET
X
0
mA for 100% Demand Limit
DMMX
Configuration
RSET
XX.X
0.0
mA for 0% Demand Limit
DMZE
Configuration
RSET
XX.X
0.0
Master/Slave Select
MSSL
Configuration
RSET
X
0
Slave Address
SLVA
Configuration
RSET
XXX
2
Lead/Lag Select
LLBL
Configuration
RSET
X
DSBL
Lead/Lag Balance Delta
LLBD
Configuration
RSET
XXX
168
Lag Start Timer
LLDY
Configuration
RSET
XX
10
Start if Error Higher
LL.ER
Configuration
RSET
XX.X
4
Lag Minimum Running Time
LAG.M
Configuration
RSET
XXX
0
Lag Unit Pump Control
LAGP
Configuration
RSET
X
0
Lead Pulldown Time
LPUL
Configuration
RSET
XX
0
Chiller in Series
SERI
Configuration
RSET
NO-YES
NO