113
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM
EXPANSION
UNITS
RANGE
COMMENT
DEFAULT
CCN TABLE
CCN POINT
PAGE NO.
OPTN
OPTIONS CONFIGURATION
CCNA
CCN Address
XXX
1-239
1
N/A
CCNA
CCNB
CCN Bus Number
XXX
0-239
0
N/A
CCNB
BAUD
CCN Baud Rate
2400
4800
9600
19200
38400
9600
N/A
BAUD
LOAD
Loading Sequence Select
Equal
Staged
EQUAL
USER
lead_cir
29
LLCS
Lead/Lag Circuit Select
Automatic
Cir A Leads
Cir B Leads
Cir C Leads
AUTOMATIC
USER
seq_typ
29, 55
RL.S
Ramp Load Select
ENBL/DSBL
DSBL
USER
ramp_sel
35
DELY
Minutes Off Time
XX (Minutes)
1 to 15
1
USER
off_on_d
29
ICE.M
Ice Mode Enable
ENBL/DSBL
DSBL
USER
ice_cnfg
41
HPUM
Condenser Pumps Sequence
X
No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual
Not supported.
NO PUMP
hpum_seq
47
PUMP
Cooler Pumps Sequence
No Pump
1 Pump Only
2 Pumps Auto
PMP 1 Manual
PMP 2 Manual
NO PUMP
USER
pump_seq
28, 47
ROT.P
Pump Rotation Delay
XXXX (hours)
24 to 3000
Not supported.
48
USER
pump_del
28, 55
PM.PS
Periodic Pump Start
NO-YES
Not supported.
NO
USER
pump_per
28, 55
P.SBY
Stop Pump In Standby
NO-YES
Not supported.
NO
USER
pump_sby
P.LOC
Flow Checked if Pmp Off
NO-YES
Not supported.
YES
USER
pump_loc
28
LS.ST
Night Low Noise Start
XX.XX
00.00-23.59
00.00
USER
nh_start
LS.ND
Night Low Noise End
XX.XX
00-00-23.59
00.00
USER
nh_end
LS.LT
Low Noise Capacity Lim
XXX (%)
0-100
100
USER
nh_limit
55
RV.AL
Reverse Alarms Relay
NO-YES
NO
USER
al_rever
OA.TH
Heat Mode OAT Threshold
XX.X
(deg F/deg C)
Not supported.
5 F
USER
heat_th
FREE
Free Cooling OAT Limit
XX.X
(deg F/deg C)
Not supported.
32.0
USER
free_oat
CUR.S
Current Limit Select
NO/YES
NO
curr_sel
39-41
CUR.F
Current Limit at 100%
XXXX
0 to 5000
2000
curr_ful
40-41
RSET
RESET, DEMAND LIMIT, MASTER/SLAVE
CRST
Cooling Reset Type
No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
Space Temp
NO RESET
USER
cr_sel
33, 36, 55
HRST
Heating Reset Type
No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
Not supported.
NO RESET
USER
hr_sel
DMDC
Demand Limit Select
None
Switch
4-20 mA Input
NONE
USER
lim_sel
39-41, 55
DMMX
mA for 100% Demand Limit
XX.X (mA)
0.0
USER
lim_mx
40, 41
DMZE
mA for 0% Demand Limit
XX.X (mA)
0.0
USER
lim_ze
40, 41
MSSL
Master/Slave Select
Disable
Master
Slave
DISABLE
MST_SLV
ms_sel
32-35, 55
SLVA
Slave Address
XXX
1-236
2
MST_SLV
slv_addr
29, 32-35
LLBL
Lead/Lag Balance Select
Always Lead
Lag if Fail
Runtime Sel
Always
Lead
MST_SLV
ll_bal
29, 32-35,
54
LLBD
Lead/Lag Balance Delta
XXX (hours)
40-400
168
MST_SLV
ll_bal_d
29, 32-35
LLDY
Lead/Lag Delay
XX (minutes)
2-30
10
MST_SLV
lsrt_tim
30, 32-35,
54
LL.ER
Start if Error Higher
XX.X
(deg F/deg C)
3-18
4
MST_SLV
start_dt
30, 32-35
LAG.M
Lag Minimum Running Time
XXX
(min)
0-150
0
MST_SLV
lag_mini
30, 32-35
LAGP
Lag Unit Pump Select
OFF if U stp
ON if U stp
OFF if U stp
MST_SLV
lag_pump
30, 32-35,
54
LPUL
Lead Pulldown Time
XX (minutes)
0-60
0
MST_SLV
lead_pul
30, 32-35,
54
SERI
Chillers in Series
NO/YES
ll_serie
29, 32-35