129
APPENDIX C — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
*Always CCN for the slave chiller.
†Slave chiller chillstat value
**This decision is consistent for master chiller only. It shall be set by default to 0 for the slave chiller.
††This item is true when chiller has loaded its total available capacity tonnage.
NOTE: Table for display only. Used for Cooling and Heat Pump Compressor Envelope.
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
MSTSLAVE
MASTER/SLAVE CONTROL
Unit is Master or Slave
Disable/Master/Slave
mstslv
Master Control Type*
Local/Remote/CCN
ms_ctrl
Master/Slave Ctrl Active
True/False
ms_activ
Lead Unit is the:
Master/Slave
lead_sel
Slave Chiller State†
0=Chiller is off
1=Valid Run State in
CCN Mode
2=Unused for this control
3=Chiller is in local mode
4=Power fail restart in
progress
5=Shudown due to fault
6=Communication failure
slv_stat
Slave Chiller Total Cap
0-100
%
slv_capt
Lag Start Delay**
1-30
minutes
l_strt_d
Lead/Lag Hours Delta*
±nnnnn
hours
ll_hr_d
Lead/Lag Changeover?**
Yes/No
ll_chang
Lead Pulldown?
Yes/No
ll_pull
Master/Slave Error
nn
ms_error
Max Available Capacity?††
True/False
cap_max
Slave Lagstat
0=Unit not configured
as a slave chiller
1=Slave pump
configuration error
(ms_error=1)
2=Unit configured as
slave chiller with
lwt_opt=no (entering
water control) with
pump control
(lag_pump=0)
3=Unit configured as slave
chiller with lwt_opt=yes
(leaving water control)
with pump control
(lag_pump=0)
4=Unit Configured as slave
chiller with lwt_opt=no
(entering water control)
with no pump control
(lag_pump=1)
5=Unit configured as slave
chiller with lwt_opt=yes
(leaving water control)
with no pump control
(lag_pump=1)
lagstat
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
OCCMAINT
Current Mode (1=occup.)
0/1
MODE
Current Occp Period #
1 to 8
PER_NO
Timed-Override in Effect
Yes/No
OVERLAST
Timed-Override Duration
0-4
hours
OVR_HRS
Current Occupied Time
00:00-23:59
STRTTIME
Current Unoccupied Time
00:00-23:59
ENDTIME
Next Occupied Day
Mon-Sun
NXTOCDAY
Next Occupied Time
00:00-23:59
NXTOCTIM
Next Unoccupied Day
Mon-Sun
NXTUNDAY
Next Unoccupied Time
00:00-23:59
NXTUNTIM
Prev Unoccupied Day
Mon-Sun
PRVUNDAY
Prev Unoccupied Time
00:00-23:59
PRVUNTIM
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
PR_LIMIT
Discharge A Temp Average
±nnn.n
°F
sdt_m_a
Discharge A Temp Rate
±nnn.n
^F
sdt_mr_a
Discharge A Gas Limit
±nnn.n
°F
sdtlim_a
Suction A Temp Average
±nnn.n
°F
sst_m_a
Discharge B Temp Average
±nnn.n
°F
sdt_m_b
Discharge B Temp Rate
±nnn.n
^F
sdt_mr_b
Discharge B Gas Limit
±nnn.n
°F
sdtlim_b
Suction B Temp Average
±nnn.n
°F
sst_m_b
Discharge C Temp Average
±nnn.n
°F
sdt_m_c
Discharge C Temp Rate
±nnn.n
^F
sdt_mr_c
Discharge C Gas Limit
±nnn.n
°F
sdtlim_c
Suction C Temp Average
±nnn.n
°F
sst_m_c
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
SERMAINT
Reset Maintenance Alert
1 to 11: reset individually
12: reset all
nn
S_RESET
forcible
OPERATION WARNINGS
1 — Refrigerant Charge
Normal/Low/Disable
charge_m
2 — Water Loop Size
Normal/Low/Disable
wloop_m
GENERAL SERVICING DELAYS
3 — Cooler Pump 1 (days)
0-1000/Alert/Disable
cpump1_m
4 — Cooler Pump 2 (days)
0-1000/Alert/Disable
cpump2_m
5 — Condenser Pump 1 (days)
0-1000/Alert
hpump1_m
6 — Condenser Pump 2 (days)
0-1000/Alert
hpump2_m
7 — Water Filter (days)
0-1000/Alert/Disable
wfilte_m
8 — Cp A Oil Filter (days)
0-1000/Alert
oilfa_m
9 — Cp B Oil Filter (days)
0-1000/alert
oilfilb_m
10 — CP.C Oil Filter (days)
0-1000/Alert
oilfic_m