127
APPENDIX C — CCN TABLES (cont)
SETPOINT CONFIGURATION TABLES
*Not supported.
MAINTENANCE DISPLAY TABLES
*
Not supported.
NOTES: Tables for display only. Forcing shall not be supported on this maintenance screen.
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
SETPOINT
COOLING
Cooling Setpoint 1
–20-70
44.0
°F
csp1
Cooling Setpoint 2
–20-70
44.0
°F
csp2
Cooling Ice Setpoint
–20-70
44.0
°F
ice_sp
OAT No Reset Value
14-125
14.0
°F
oatcr_no
OAT Full Reset Value
14-125
14.0
°F
oatcr_fu
Delta T No Reset Value
0-25
0.0
^F
dt_cr_no
Delta T Full Reset Value
0-25
0.0
^F
dt_cr_fu
Current No Reset Value
0-20
0.0
ma
v_cr_no
Current Full Reset Value
0-20
0.0
ma
v_cr_fu
Space T No Reset Value
14-125
14.0
°F
spacr_no
SpaceT Full Reset Value
14-125
14.0
°F
spacr_fu
Cooling Reset Deg. Value
–30-30
0.0
^F
cr_deg
Cooling Ramp Loading
0.2-2.0
1.0
^F
cramp_sp
HEATING*
Heating Setpoint 1
80-140
100.0
°F
hsp1
Heating Setpoint 2
80-140
100.0
°F
hsp2
OAT No Reset Value
14-125
14.0
°F
oathr_no
OAT Full Reset Value
14-125
14.0
°F
oathr_fu
Delta T No Reset Value
0-25
0.0
^F
dt_hr_no
Delta T Full Reset Value
0- 25
0.0
^F
dt_hr_fu
Current No Reset Value
0-20
0.0
ma
v_hr_no
Current Full Reset Value
0-20
0.0
ma
v_hr_fu
Heating Reset Deg. Value
–30-30
0.0
^F
hr_deg
Heating Ramp Loading
0.2-2.0
1.0
^F
hramp_sp
AUTO CHANGEOVER*
Cool Changeover Setpt
39-122
75.0
°F
cauto_sp
Heat Changeover Setpt
32-115
64.0
°F
hauto_sp
MISCELLANEOUS
Switch Limit Setpoint 1
0-100
100
%
lim_sp1
Switch Limit Setpoint 2
0-100
100
%
lim_sp2
Switch Limit Setpoint 3
0-100
100
%
lim_sp3
Reclaim Setpoint*
95-140
122.0
°F
rsp
Reclaim Deadband*
5-27
9.0
°F
hr_deadb
Water Val Condensing Stp
80 to 120
86
°F
w_sct_sp
TABLE
DISPLAY NAME
RANGE
UNITS
POINT NAME
WRITE STATUS
BOARD_PN
EXV Board Circuit A
XXXXXXXX
exv_brda
EXV Board Circuit B
XXXXXXXX
exv_brdb
EXV Board Circuit C
XXXXXXXX
exv_brdc
AUX Board #1 Part Number
XXXXXXXX
aux_brd1
AUX Board #2 Part Number
XXXXXXXX
aux_brd2
AUX Board #3 Part Number
XXXXXXXX
aux_brd3
AUX Board #4 Part Number
XXXXXXXX
aux_brd4
AUX Board #5 Part Number
XXXXXXXX
aux_brd5
EMM NRCP2 Board
XXXXXXXX
emm_nrcp
Reclaim NRCP2 Board
XXXXXXXX
rec_nrcp
TCPM Board Comp A
XXXXXXXX
cpa_vers
Must Trip Amps
0-600
amps
cpa_mtam
S1 Config Switch (8 to 1)
00000000
0
cpa_s1_m
TCPM Board Comp B
nnnn
cpb_vers
Must Trip Amps
0-600
amps
cpb_mtam
S1 Config Switch (8 to 1)
00000000
0
cpb_s1_m
TCPM Board Comp C
XXXXXXXX
cpc_vers
Must Trip Amps
0-600
amps
cpc_mtam
S1 Config Switch (8 to 1)
00000000
0
cpc_s1_m
CUR_PHASE
Current Phase 1 Comp A
0-600
amps
cpa_cur1
Current Phase 2 Comp A
0-600
amps
cpa_cur2
Current Phase 3 Comp A
0-600
amps
cpa_cur3
Current Phase 1 Comp B
0-600
amps
cpb_cur1
Current Phase 2 Comp B
0-600
amps
cpb_cur2
Current Phase 3 Comp B
0-600
amps
cpb_cur3
Current Phase 1 Comp C
0-600
amps
cpc_cur1
Current Phase 2 Comp C
0-600
amps
cpc_cur2
Current Phase 3 Comp C
0-600
amps
cpc_cur3
DEFROSTM*
CIR A DEFROST CONTROL
Exchanger Frost Factor
0-100
%
frost_a
Next Sequence Allowed in
nnn
minutes
def_se_a
Defrost Active?
True/False
mode[19]
Defrost Temperature
±nnn.n
°F
DEFRT_A
Defrost Duration
nnn
minutes
defr_dua
Fan Sequence Started ?
n
def_fa_a
Override State
nn
over_d_a
Mean SST Calculation
±nnn.n
°F
sst_dm_a
Delta: OAT - Mean SST
±nnn.n
^F
delt_a
Reference Delta
±nnn.n
^F
delt_r_a
Delta - Reference Delta
±nnn.n
°F
del_v_a
Frost Integrator Gain
n.n
fr_int_a
Defrost Fan Start Cal A
0.00
psi
def_ca_a
Defrost Fan Offset Cal A
0.00
psi
def_of_a
CIR B DEFROST CONTROL
Exchanger Frost Factor
0-100
%
frost_b
Next Sequence Allowed in
nnn
minutes
def_se_b
Defrost Active?
True/False
mode[20]
Defrost Temperature
±nnn.n
°F
DEFRT_B
Defrost Duration
nnn
minutes
defr_dub
Fan Sequence Started?
n
def_fa_b
Override State
nn
over_d_b
Mean SST calculation
±nnn.n
°F
sst_dm_b
Delta: OAT - Mean SST
±nnn.n
^F
delt_b
Reference Delta
±nnn.n
^F
delt_r_b
Delta - Reference Delta
±nnn.n
^F
del_v_b
Frost Integrator Gain
n.n
fr_int_b
Defrost Fan Start Cal B
0.00
psi
def_ca_b
Defrost Fan Offset Cal B
0.00
psi
def_of_b