107
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — SERVICE TEST
ITEM
EXPANSION
UNITS
RANGE
COMMENT
WRITE
STATUS
CCN TABLE
CCN POINT
PAGE
NO.
TEST
MANUAL TEST MODE
Remote-Off-
Enable Switch
must be set to
OFF
Position
Remote-Off-
Enable Switch
must be set to
ENABLE
Position
N/A
T.REQ
Manual Sequence
OFF/ON
forcible
N/A
service_test
61, 83
CP.A
Compressor A Output
OFF/ON
forcible
N/A
comp_serv_a
64
SLI.A
Slide Valve Capacity A
unchanged
increase
decrease
forcible
comp_ser_sid_a
CP.B
Compressor B Output
OFF/ON
forcible
N/A
comp_serv_b
64
SLI.B
Slide Valve Capacity B
unchanged
increase
decrease
forcible
comp_ser_sid_b
CP.C
Compressor C Output
OFF/ON
forcible
N/A
comp_serv_c
64
SLI.C
Slide Valve Capacity C
unchanged
increase
decrease
forcible
comp_ser_sid_c
QUIC
QUICK TEST MODE
Remote-Off-
Enable Switch
must be set to
OFF
Position
N/A
Q.REQ
OFF/ON
forcible
N/A
61
EXV.A
Circuit A EXV % Open
XXX (%)
0-100
forcible
N/A
61
EXV.B
Circuit B EXV % Open
XXX (%)
0-100
forcible
N/A
61
EXV.C
Circuit C EXV % Open
XXX (%)
0-100
forcible
N/A
ECO.A
Circ A ECO EXV %
XXX (%)
0-100
forcible
ECO.B
Circ B ECO EXV %
XXX (%)
0-100
forcible
ECO.C
Circ C ECO EXV %
XXX (%)
0-100
forcible
FAN.A
Circuit A Fan Stages
X
0-8
forcible
N/A
FAN.B
Circuit B Fan Stages
X
0-8
forcible
N/A
FAN.C
Circuit C Fan Stages
X
0-8
forcible
N/A
SPD.A
Cir A Varifan position
XXX (%)
0-100
forcible
N/A
SPD.B
Cir B Varifan position
XXX (%)
0-100
forcible
N/A
SPD.C
Cir C Varifan position
XXX (%)
0-100
forcible
N/A
HT.A
Oil Heater Circuit A
OFF/ON
forcible
SL1.A
Slide Valve 1 Cir A
OFF/ON
forcible
SL2.A
Slide Valve 2 Cir B
OFF/ON
forcible
HGP.A
Hot Gas Bypass A Output
OFF/ON
forcible
OLS.A
Oil Solenoid Cir A
OFF/ON
forcible
DGT.A
DGT Cool Solenoid A
OFF/ON
forcible
HT.B
Oil Heater Circuit B
OFF/ON
forcible
SL1.B
Slide Valve 1 Cir B
OFF/ON
forcible
SL2.B
Slide Valve 2 Cir B
OFF/ON
forcible
HGP.B
Hot Gas Bypass B Output
OFF/ON
forcible
OLS.B
Oil Solenoid Cir A
OFF/ON
forcible
DGT.B
DGT Cool Solenoid B
OFF/ON
forcible
HT.C
Oil Heater Circuit C
OFF/ON
forcible
SL1.C
Slide Valve 1 Cir C
OFF/ON
forcible
SL2.C
Slide Valve 2 Cir C
OFF/ON
forcible
HGP.C
Hot Gas Bypass C Output
OFF/ON
forcible
OLS.C
Oil Solenoid Cir A
OFF/ON
forcible
DGT.C
DGT Cool Solenoid C
OFF/ON
forcible
PMP.1
Water Exchanger Pump 1
OFF/ON
Not supported.
forcible
N/A
PMP.2
Water Exchanger Pump 2
OFF/ON
Not supported.
forcible
N/A
PMP.3
Condenser Pump 1
OFF/ON
Not supported.
forcible
CL.HT
Cooler Heater Output
OFF/ON
N/A
BVL.A
Ball Valve Position A
OPEN/CLSE
BVL.B
Ball Valve Position B
OPEN/CLSE
BVL.C
Ball Valve Position C
OPEN/CLSE
Q.RDY
Chiller Ready Status
OFF/ON
forcible
N/A
Q.RUN
Chiller Running Status
OFF/ON
forcible
N/A
SHUT
Customer Shutdown Stat
OFF/ON
forcible
N/A
CATO
Chiller Capacity in 0-10v
XX.X (vdc)
forcible
N/A
ALRM
Alarm Relay
OFF/ON
forcible
N/A
68
ALRT
Alert Relay
OFF/ON
forcible
N/A