START-UP CHECKLIST FOR 30XW LIQUID CHILLERS
A. PROJECT INFORMATION
Job Name ________________________________________________________________________________________
Address __________________________________________________________________________________________
City ________________________________ State ________________________ Zip ___________________________
Installing Contractor ________________________________________________________________________________
Sales Office _______________________________________________________________________________________
Start-up Performed By ______________________________________________________________________________
Design Information
Unit
Model _______________________________________ Serial ______________________________________
Compressors
Compressor A
Model _______________________________________ Serial ______________________________________
Compressor B
Model _______________________________________ Serial ______________________________________
Evaporator
Model _______________________________________ Serial ______________________________________
Condenser
Model _______________________________________ Serial ______________________________________
B. PRELIMINARY EQUIPMENT CHECK (This section to be completed by installing contractor)
1. Is there any physical damage?
Yes
No
Will this prevent start-up?
Yes
No
Description
___________________________________________________________________________________________
___________________________________________________________________________________________
2. Unit is installed level as per the installation instructions.
Yes
No
3. Power supply agrees with the unit nameplate.
Yes
No
4. Correct control voltage ________vac.
Yes
No
5. Electrical power wiring is installed properly.
Yes
No
6. Unit is properly grounded.
Yes
No
7. Electrical circuit protection has been sized and installed properly.
Yes
No
8. All terminals are tight.
Yes
No
9. All plug assemblies are tight.
Yes
No
10. All cables, thermistors and transducers have been inspected for cross wires.
Yes
No
11. All thermistors are fully inserted into wells.
Yes
No
12. Relief valve vent piping per local codes.
Yes
No
13. Mechanical room temperature maintained above 50 F (10 C).
Yes
No
Chilled Water System Check
1. All chilled water valves are open.
Yes
No
2. All piping is connected properly.
Yes
No
3. All air has been purged from the system.
Yes
No
4. Chilled water pump is operating with the correct rotation.
Yes
No
5. Chilled water pump starter interlocked with chiller.
Yes
No
6. Chilled water flow switch operational.
Yes
No
7. Inlet piping to evaporator includes a 20 mesh strainer within 10 ft.
Yes
No
8. Water loop volume greater than 3 gal/ton for air conditioning
or 6 gal/ton for process cooling and low ambient operation.
Yes
No
9. Proper loop freeze protection provided to ____
F (
C) for brine applications.
Yes
No
Antifreeze type__________________ Concentration _____%.
Yes
No
10. Outdoor piping wrapped with electric heater tape.
Yes
No
CAPACITY
EWT
LWT
FLUID TYPE
FLOW RATE
P.D.
Evaporator
Condenser