Condenser Water System Check
1. All condenser water valves are open.
Yes
No
2. All piping is connected properly.
Yes
No
3. All air has been purged from the system.
Yes
No
4. Condenser water pump is operating with the correct rotation.
Yes
No
5. Condenser water pump starter interlocked with chiller.
Yes
No
6. Condenser water flow switch operational.
Yes
No
7. Inlet piping to condenser includes a 20 mesh strainer within 10 ft.
Yes
No
8. Outdoor piping wrapped with electric heater tape.
Yes
No
9. Is system equipped with head pressure control?
(Required for entering condenser water below 68 F (20 C).)
Yes
No
C. UNIT START-UP
1. All liquid line service valves are open.
Yes
No
2. All discharge service valves are open.
Yes
No
3. All suction service valves are open.
Yes
No
4. Economizer service valves open.
Yes
No
5. Oil service valves open.
Yes
No
6. Leak check unit. Locate, repair and report any refrigerant leaks.
Yes
No
7. Voltage at terminal block is within unit nameplate range.
Yes
No
Check voltage imbalance: A-B______ A-C______B-C______
Average voltage = __________ (A-B + A-C + B-C)/3
Maximum deviation from average voltage = _______
Voltage imbalance = ______% (max. deviation / average voltage) X 100
Is voltage imbalance less than 2%.
Yes
No
(DO NOT start chiller if voltage imbalance is greater than 2%.
Contact local utility for assistance.)
8. Verify evaporator flow rate
Pressure entering evaporator
_____ psig
Pressure leaving evaporator _____
psig
Evaporator pressure drop
_____ psig
psig x 2.31 ft./psi =
_____ ft of water
kpa x 0.334 m/psi =
_____ mm of water
Evaporator flow rate _____ gpm (l/s) (See Evaporator Pressure Drop Curve)
9. Verify condenser flow rate
Pressure entering condenser
_____ psig
Pressure leaving condenser
_____ psig
Condenser pressure drop
_____ psig
psig x 2.31 ft./psi =
_____ ft of water
kpa x 0.334 m/psi =
_____ mm of water
Condenser flow rate _____ gpm (l/s) (See Condenser Pressure Drop Curve)
Start and Operate Machine
1. Complete component test utilizing Quick Test Mode
2. Check refrigerant and oil charge. Record charge information.
3. Record compressor motor current.
4. Record operating data.
5. Provide operating instructions to owner’s personnel.
Circuit A
Circuit B
Refrigerant Charge
Additional charge required
__________
___________
Oil Charge
Additional charge required
__________
___________