APPENDIX C — CCN TABLES (cont)
CONFIGURATION TABLES (cont)
TABLE
DISPLAY NAME
RANGE
DEFAULT
UNITS
POINT NAME
CFG_TABn
(n = 1 to 8)
Display x table number 1
85
tab_nb_1
Display n var number 1
4
var_nb_1
Display n table number 2
85
tab_nb_2
Display n var number 2
20
var_nb_2
Display n table number 3
85
tab_nb_3
Display n var number 3
21
var_nb_3
Display n table number 4
85
tab_nb_4
Display n var number 4
28
var_nb_4
Display n table number 5
85
tab_nb_5
Display n var number 5
29
var_nb_5
Display n table number 6
85
tab_nb_6
Display n var number 6
30
var_nb_6
Display n table number 7
92
tab_nb_7
Display n var number 7
33
var_nb_7
Display n table number 8
92
tab_nb_8
Display n var number 8
34
var_nb_8
Display n table number 9
0
tab_nb_9
Display n var number 9
0
var_nb_9
DISPCONF
Metric Display on STDU
Yes/No
No
DISPUNIT
Language Selection
0=English
1=Espanol
2=Francais
3=Portugues
4=Translated
0
LANGUAGE
MST_SLV
MASTER SLAVE CONTROL
Master/Slave Select
0=Disable
1=Master
2=Slave
0
ms_sel
Master Control Type
1=Local Control
2=Remote Control
3=CCN Control
1
ms_ctrl
Slave Address
1 to 236
2
slv_addr
Lead Lag Select
0=Always Lead
1=Lag Once
Failed Only
2=Lead/Lag
Runtime Sel
0
lead_sel
Lead/Lag Balance Delta
40 to 400
168
hours
ll_bal_d
Lag Start Timer
2 to 30
10
min
lstr_tim
Lead Pulldown Time
0 to 60
0
min
lead_pul
Start if Error Higher
4
^F
start_dt
Lag Minimum Running Time
0
min
lag_mini
Lag Unit Pump Control
0=Stop if Unit Stops
1=Run if Unit Stops
0
lag_pump
Chiller in Series
Yes/No
No
II_serie