92
Triple Evacuation Method
The triple evacuation method should only be used when vacuum
pump is capable of pumping down to 28--in. of mercury and
system does not contain any liquid water. Proceed as follows:
1. Pump system down to 28--in. of mercury and allow pump
to continue operating for an additional 15 minutes.
2. Close service valves and shut off vacuum pump.
3. Connect a nitrogen cylinder and regulator to system and
open until system pressure is 2 psig.
4. Close service valve and allow system to stand for 1 hr.
During this time, dry nitrogen will be able to diffuse
throughout the system, absorbing moisture.
5. Repeat this procedure. System will then contain minimal
amounts of contaminants and water vapor.
Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate. Refer to
Carrier GTAC II; Module 5; Charging, Recovery, Recycling, and
Reclamation section for charging methods and procedures. Unit
panels must be in place when unit is operating during charging
procedure.
Puron
®
(R-410A) refrigerant systems should be charged with
liquid refrigerant. Use a commercial type metering device in the
manifold hose.
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
Puron (R--410A) refrigerant systems operate at higher
pressures than standard R--22 systems. Do not use R--22
service equipment or components on Puron refrigerant
equipment. Gauge set, hoses, and recovery system must
be designed to handle Puron refrigerant. If unsure
about equipment, consult the equipment manufacturer.
!
WARNING
NOTE
:
Do not use recycled refrigerant as it may contain
contaminants.
No Charge
Use standard evacuating techniques. After evacuating system,
weigh in the specified amount of refrigerant (refer to unit
nameplate).
NOTE
: System charge for units with Humidi-MiZer
™
system is
greater than the system charge of the standard unit.
Low Charge Cooling
Using cooling charging chart (see Fig. 64--79), add or remove
refrigerant until conditions of the chart are met. An accurate
pressure gauge and temperature-sensing device is required.
Charging is accomplished by ensuring the proper amount of liquid
subcooling. Connect pressure gauge to the compressor discharge
service valve. Connect temperature sensing device to the liquid
line between the condenser and the TXV (thermostatic expansion
valve), and insulate it so that ambient temperature does not affect
reading.
To Use the Cooling Charging Chart, Standard Unit
NOTE
: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
Override function to start all outdoor fans.
R410A
R410A REFRIGERA
REFRIGERANT
NT
OUTDOOR
OUTDOOR FAN
FAN MUST
MUST BE
BE OPERATING
OPERATING ON
ON HIGH
HIGH SPEED
SPEED
20
20
40
40
60
60
80
80
100
100
120
120
140
140
160
160
150
150
200
200
250
250
300
300
350
350
400
400
450
450
500
500
550
550
600
600
Comp
Compressor
ressor Disch
Discharge
arge Pressu
Pressure,
re, [p
[psig
sig]
OutdoorO
u
td
o
o
r
CoilC
o
il
L
eavine
a
v
in
g
Te
m
p
Te
m
p
eratue
ra
tu
re,re
,
[Deg[D
e
g
reesre
e
s
F]F
]
Add
dd Charge
Charge if
if Above
bove the
the Curve
Curve
Remo
Remove
ve Charge
Charge if
if Below
Below the
the Curve
Curve
C07038
Fig. 64 -- Charging Chart — 48/50PG03
R4
R410A RE
REFRI
RIGERANT
RANT
OUTDOOR F
R FAN M
N M UST BE OPERATING ON H
N HIGH S
H SPEED
20
20
40
40
60
60
80
80
10
100
12
120
14
140
16
160
150
150
200
200
250
250
300
300
350
350
400
400
450
450
500
500
550
550
600
600
Co mp re ss
ssor Disc
isc h a rg e P re ss
ssu re , [p sig
sig]
Add Cha
harge
ge if Abov
bove the
the Cur
urve
Re
Rem ove Charge if Be
Below the Curve
OutdoorO
u
td
o
o
r
CoilC
o
il
L
eavine
a
v
in
g
TempTe
m
p
eratue
ra
tu
re,re
,
[Deg[D
e
g
reesre
e
s
F]F
]
C07039
Fig. 65 -- Charging Chart — 48/50PG04
Use the temperature and pressure readings, and find the
intersection point on the cooling charging chart. If intersection
point on chart is above line, add refrigerant. If intersection point on
chart is below line, carefully recover some of the charge. Recheck
suction pressure as charge is adjusted.
The TXV is set to maintain between 10 and 15 degrees of
superheat at the compressors. The valves are factory set and cannot
be adjusted. Do not use A TXV designed for use with R-22.
To Use the Cooling Charging Charts, Units With
Humidi--Mizer
t
Adaptive Dehumidification System
NOTE
: All circuits must be running in normal cooling mode.
Indoor airflow must be within specified air quantity limits for
cooling. (See Appendix D.) All outdoor fans must be on and
running at high speed. Use the Cooling Service Test Outdoor Fan
function (
Service Test
→
COOL
→
OF.OV
) to start all outdoor fans.
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...