Fig. 14 -- Hot Gas Reheat Mode (Reheat2) — Humidi--MiZer
t
System
48/50PG20--28 and 48/50PM16--28
Reheat Control
The cooling staging and compressor control routines are
responsible for controlling each circuit in one of the three
sub--modes (Cool, Reheat1, or Reheat2). When there is only a
cooling demand, one or more circuits will operate in normal
cooling mode. When there is only dehumidification demand, all
circuits will operate in Reheat2 mode. When there is both cooling
demand and dehumidification demand, all circuits will operate in
either Reheat1 or Reheat2 mode, with the portion of Reheat1
circuits determined from the cooling demand. The Requested
Reheat2 Stages (
Operating Modes
→
COOL
→
HMZR
→
REQ.R
)
shows the control’s request for reheat circuits if cooling is not
already requesting all stages. Available Reheat2 Stages (
Operating
Modes
→
COOL
→
HMZR
→
AVL.R
) displays circuits that are
available for reheat use.
Actual Reheat2 Stages (
Operating
Modes
→
COOL
→
HMZR
→
ACT.R
) displays the current number
of circuits running in Reheat2 mode. These three status points
should only be monitored when there is only a dehumidification
demand, because their values can be forfeited to cooling stages
when cooling demand is present.
Reheat2 Stage Incr. Time
(
Configuration
→
HMZR
→
R.INC
) and Reheat2 Stage Decr. Time
(
Configuration
→
HMZR
→
R.DEC
) set the time delay when
adding or subtracting a compressor for a reheat function. These
only apply when using adaptive thermostat or space sensor control.
There are three relay outputs that show reheat status. Cool -- >
Reheat1 Control (
Outputs
→
COOL
→
CRC
) show when the unit
has switch from pure cooling to reheat ready (based on a
dehumidification
demand).
Reheat2
Valve
A
(
Outputs
→
COOL
→
RH2.A
)
and
Reheat2
Valve
B,C
(
Outputs
→
COOL
→
RH2.B
) display when the respective circuit’s
Reheat2 valve is energized.
A circuit can be restricted from Reheat2 operation by the outside
temperature and saturated suction temperature. Reheat2 OAT
Limit A (
Configuration
→
HMZR
→
RA.LO
) and Reheat2 OAT
Limit B,C (
Configuration
→
HMZR
→
RB.LO
) set the lowest
outside temperature the respected circuit is allowed to run in
reheat2 mode. The lockout on/off status is shown as Reheat2 OAT
Lockout A (
Operating Modes
→
COOL
→
HMZR
→
R.LO.A
) and
Reheat2 OAT Lockout B,C (
Operating Modes
→
COOL
→
HMZR
→
R.LO.B
) for their respective circuit. If a circuit’s saturated
suction pressure falls below the low limit configuration during
Reheat2 operation, the circuit will switch to reheat1 (the circuits
Reheat2 valve will be turned off) for at least 2 minutes and until its
suction rises back above the high limit. Reheat2 SSP Lo Limit A
(
Configuration
→
HMZR
→
RA.LP
) and Reheat2 SSP Lo Limit
B,C (
Configuration
→
HMZR
→
RB.LP
) set the low pressure limit
for Reheat2 mode for individual circuits. Reheat2 SSP Hi Limit A
(
Configuration
→
HMZR
→
RA.HP
) and Reheat2 SSP Hi Limit B,
C (
Configuration
→
HMZR
→
RB.HP
) set the high pressure limit
for Reheat2 mode for each circuit.
Reheat Mode Diagnostic Help
The status of reheat mode sensor inputs may be viewed within the
display Inputs menu. The status of reheat mode outputs may be
viewed within the display Outputs or
Run Status
→
COOL
menus.
Additional diagnostic help, including status of circuit reheat
temperature limit lockouts may be viewed within the
Humidi-MiZer
™
sub-menu of the cooling mode diagnostic table at
Operating Modes
→
COOL
→
HMZR
.
The Service Test mode may be used to force the system to operate
in various stages of Reheat1 or Reheat2 mode, or to independently
operate the reheat valve control outputs. Fig. 15--19 show the
valve locations of Humidi--MiZer equipped units.
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...