100
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — RUN STATUS (cont)
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB---TABLE
CCN POINT
CCN WRITE
STATUS
HEAT
Heating Status
HEATDISP
DMD.H
Heating Demand
xxx.x
^F
HEAT_DMD
AVL.H
Available Heating Stages
x
AVLHSTGS
REQ.H
Requested Heating Stages
x
REQHSTGS
MAX.H
Max Allowed Heat Stages
x
MAXHSTGS
forcible
LMT.H
Max Heat Stage In Effect
x
HSTGLIMT
IDF
Indoor Fan State
On/Off
IDFSTATE
F.SPD
Commanded Fan Speed
xxx
FANSPEED
HT.1
Heat Stage 1 Relay
On/Off
HEAT_1
TG.H1
Heat Stage 1 Timeguard
xxx
sec
TIMGD_H1
HT.2
Heat Stage 2 Relay
On/Off
HEAT_2
TG.H2
Heat Stage 2 Timeguard
xxx
sec
TIMGD_H2
ECON
Economizer Status
ECONDISP
EC.CP
Econo Commanded Position
xxx
%
ECONOCMD
EC.AP
Econo Actual Position
xxx
%
ECONOPOS
EC.MP
Min Position in Effect
xxx
%
MIN_POS
forcible
IAQ.S
IAQ Level (switch)
High/Low
IAQIN
IAQ
IAQ Level (sensor)
xxxx
ppm
IAQ
OAT
Outdoor Air Temperature
xxx.x
dF
OA_TEMP
ENTH
Outdoor Enthalpy Switch
High/Low
ENTHALPY
OAQ
OAQ Level (sensor)
xxxx
ppm
OAQ
PE.1
Power Exhaust 1 Relay
On/Off
PE_1
PE.2
Power Exhaust 2 Relay
On/Off
PE_2
HRS
Component Run Hours
STRTHOUR
A1
Compressor A1 Run Hours
xxxxx.xx
hours
HR_A1
forcible
A2
Compressor A2 Run Hours
xxxxx.xx
hours
HR_A2
forcible
B1
Compressor B1 Run Hours
xxxxx.xx
hours
HR_B1
forcible
C1
Compressor C1 Run Hours
xxxxx.xx
hours
HR_C1
forcible
CCH
Crankcase Heat Run Hours
xxxxx.xx
hours
HR_CCH
forcible
IDF
Indoor Fan Run Hours
xxxxx.xx
hours
HR_IDF
forcible
OFC.1
Outdoor Fan 1 Run Hours
xxxxx.xx
hours
HR_OFC_1
forcible
OFC.2
Outdoor Fan 2 Run Hours
xxxxx.xx
hours
HR_OFC_2
forcible
OFC.3
Outdoor Fan 3 Run Hours
xxxxx.xx
hours
HR_OFC_3
forcible
HT.1
Heat Stage 1 Run Hours
xxxxx.xx
hours
HR_HTR_1
forcible
HT.2
Heat Stage 2 Run Hours
xxxxx.xx
hours
HR_HTR_2
forcible
PE.1
Power Exhaust1 Run Hours
xxxxx.xx
hours
HR_PE_1
forcible
PE.2
Power Exhaust2 Run Hours
xxxxx.xx
hours
HR_PE_2
forcible
ALRM
Alarm Relay Run Hours
xxxxx.xx
hours
HR_ALM
forcible
CRC
Reheat1 Valve Run Hours
xxxxx.xx
hours
HR_CRC
forcible
RH2.A
Reheat2 Valve A Run Hrs
xxxxx.xx
hours
HR_RH2_A
forcible
RH2.B
Reheat2 Valve BC Run Hrs
xxxxx.xx
hours
HR_RH2_B
forcible
STRT
Component Starts
A1
Compressor A1 Starts
xxxxxx
ST_A1
forcible
A2
Compressor A2 Starts
xxxxxx
ST_A2
forcible
B1
Compressor B1 Starts
xxxxxx
ST_B1
forcible
C1
Compressor C1 Starts
xxxxxx
ST_C1
forcible
CCH
Crankcase Heat Starts
xxxxxx
ST_CCH
forcible
IDF
Indoor Fan Starts
xxxxxx
ST_IDF
forcible
OFC.1
Outdoor Fan 1 Starts
xxxxxx
ST_OFC_1
forcible
OFC.2
Outdoor Fan 2 Starts
xxxxxx
ST_OFC_2
forcible
OFC.3
Outdoor Fan 3 Starts
xxxxxx
ST_OFC_3
forcible
HT.1
Heat Stage 1 Starts
xxxxxx
ST_HTR_1
forcible
HT.2
Heat Stage 2 Starts
xxxxxx
ST_HTR_2
forcible
PE.1
Power Exhaust 1 Starts
xxxxxx
ST_PE_1
forcible
PE.2
Power Exhaust 2 Starts
xxxxxx
ST_PE_2
forcible
ALRM
Alarm Relay Starts
xxxxxx
ST_ALM
forcible
CRC
Reheat1 Valve Starts
xxxxxx
ST_CRC
forcible
RH2.A
Reheat2 Valve A Starts
xxxxxx
ST_RH2_A
forcible
RH2.B
Reheat2 Valve BC Starts
xxxxxx
ST_RH2_B
forcible
(ALRMDISP) = CCN
only)
ALRMDISP
Active Alarm 1 Code
xxx
ALMCODE1
Active Alarm 2 Code
xxx
ALMCODE2
Active Alarm 3 Code
xxx
ALMCODE3
Active Alarm 4 Code
xxx
ALMCODE4
Active Alarm 5 Code
xxx
ALMCODE5
Reset All Current Alarms
Yes/No
ALRESET
forcible
Reset Alarm History
Yes/No
ALHISCLR
forcible
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...