Carrier Accessory Kits
There are specific accessory kits sold for various field installed
accessories.
These kits vary based on model, size, voltage,
manufacture date, and duct orientation. Some of these kits include
Economizer, Power Exhaust, and Electric Heat. Refer to the
Controls Quick Set--Up section for configuration and more
information on these accessories.
Two--Position Damper
The two-position outdoor air damper accessory usage depends on
model size and return duct orientation. This accessory wires
directly into the low voltage circuit for the indoor fan control. No
other control configuration is needed.
Indoor Air Quality
The indoor air quality (IAQ) sensor (part no. 33ZCSENCO2) is a
field-installed accessory which measures CO
2
levels in the air.
When installing this sensor, an ECB board must be installed and
the unit must be configured for IAQ use by setting
Configuration
→
AIR.Q
→
IA.CF
to a value of 1, 2, or 3. See the
Indoor Air Quality section for more information.
TB--2
4--20mA Input
. . . . . . . . . .
TB--3
Sensor Common
. . . . . . . . . .
TB--R
24vac Output
. . . . . . . . .
TB--C
Common (GND)
. . . . . . . . .
Outdoor Air Quality
The outdoor air quality (OAQ) sensor is a field-installed accessory
that measures CO
2
levels in the air. When installing this sensor, an
ECB board must be installed and the unit must be configured for
OAQ use by setting
Configuration
→
AIR.Q
→
OA.CF
to a value
of 1 or 2. See the Indoor Air Quality section for more information.
TB--2
4--20mA Input
. . . . . . . . . .
TB--3
Sensor Common
. . . . . . . . . .
TB--R
24vac Output
. . . . . . . . .
TB--C
Common (GND)
. . . . . . . . .
Smoke Detectors
The smoke detectors are field-installed accessories. These detectors
can detect smoke in either the return air (part no.
CRSMKDET003A00) or supply and return air (part no.
CRSMKSUP002A00). When installing either detector, the unit
must
be
configured
for
fire
shutdown
by
setting
Configuration
→
UNIT
→
FS.SW
to normally open (1) or normally
closed (2).
TB--Fire Shutdown--1
Dry Contact Source
. . . . . . . . . . . . .
TB--Fire Shutdown--2
Discrete Input to Board
. . . . . . . . . . .
TB--R
24vac Output
. . . . . . . . .
TB--C
Common (GND)
. . . . . . . . .
NOTE
: When a Humidi-Mizer
™
system is installed, the inputs to
the fire shutdown are moved to the control harness. See the Third
Party Control section for more information.
Filter Status
The filter status accessory (part no. CRSTATUS002B00) is a
field-installed accessory. This accessory detects plugged filters.
When installing this accessory, the unit must be configured for
filter status by setting
Configuration
→
UNIT
→
FL.SW
to
normally open (1) or normally closed (2). Normally open (1) is the
preferred configuration.
Filter status wires are pre--run in the unit harness and located near
the switch installation location. Refer to the Filter Accessory
installation instructions for more information.
Fan Status
The fan status accessory (part no. CRSTATUS003B00) is a
field-installed accessory. This accessory detects when the indoor
fan is blowing air. When installing this accessory, the unit must be
configured
for
fan
status
by
setting
Configuration
→
UNIT
→
FN.SW
to normally open (1) or
normally closed (2). Normally open (1) is the preferred
configuration.
Fan status wires are pre--run in the unit harness and located near the
switch installation location. Refer to the Fan Accessory installation
instructions for more information.
NOTE
: The fan status terminals on TB1 are NOT to be used.
Enthalpy Sensors
The enthalpy accessories (part no. CRENTSNG002A00 and
CRENTDIF002A00) are field-installed accessories. The first
accessory (outdoor air only) determines when the enthalpy is low
relative to a fixed reference. Adding the second accessory (return
air) compares the enthalpy between the outdoor and return
airstreams. In each case, the enthalpy 4 to 20 mA signals are
converted to a switch output which is read by the ECB. When
installing this accessory, the unit must be configured for
enthalpy-based
control
by
setting
Configuration
→
ECON
→
EN.SW
to normally open (1). See Fig.
29 and 30 for wiring details.
Normal status is an active switch which tells the control that
enthalpy is LOW. The actual switch terminal LOW is normally
closed. Refer to the Enthalpy Kit installation instructions for more
information on the installation.
Return/Supply Air Temperature Sensor
The temperature sensor (part no. 33ZCSENSAT) is a field-installed
accessory which may be installed on the common return air duct
and/or the common supply air duct near the unit. The duct return
air temperature (RAT) may be selected for display only if the space
temperature offset (SPTO) is not used. When installing the sensor,
the
unit
must
be
configured
by
setting
Configuration
→
UNIT
→
RAT.S
to YES. The duct supply air
temperature (SAT) may be used to replace the SAT sensor that is
internal to the unit. A supply duct SAT measurement is valid for
heating mode display while the factory-standard internal SAT is
not valid for heating due to its location upstream of the heating
section. When installing the supply duct SAT, the unit must be
configured by setting
Configuration
→
UNIT
→
SAT.H
to ENBL.
A SAT sensor in the supply duct is the preferred configuration for
systems with Carrier variable volume and temperature (VVT
®
)
accessory controls.
Space Humidistat
The Space Humidistat (part no. ----HL----38MG--029) is a wall
mounted device with an adjustable setpoint to control humidity
levels. The humidistat input is provided on the field connection
terminal board. The Space Humidity Switch configuration,
Configuration
→
UNIT
→
RH.SW
, identifies the normally open or
normally closed status of this input at LOW humidity.
TB--HUMIDISTAT1
Discrete Input to Board
. . . . . . . . . . . .
TB--HUMIDISTAT2
24 VAC Dry Contact Source
. . . . . . .
NOTE
: The humidistat terminals are only in use when the unit is
equipped with the Humidi--MiZer factory option.
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...