Table 18 – IGC Board LED Alarm Codes
LED
FLASH
CODE
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET METHOD
PROBABLE CAUSE
On
Normal Operation
—
—
—
Off
Hardware Failure
No gas heating.
—
Loss of power to the IGC. Check 5 amp fuse on IGC,
power to unit, 24V circuit breaker, transformer, and
wiring to the IGC.
1 Flash
Indoor Fan On/Off Delay
Modified
5 seconds subtracted from
On delay.
5 seconds added to Off
delay (3 min max).
Power reset.
High temperature limit switch opens during heat
exchanger warm-up period before fan-on delay
expires.
High temperature limit switch opens within
10 minutes of heat call (W) Off.
See Limit Switch Fault.
2 Flashes
Limit Switch Fault
Gas valve and igniter Off.
Indoor fan and inducer On.
Limit switch closed, or
heat call (W) Off.
High temperature limit switch is open. Check the
operation of the indoor (evaporator) fan motor.
Ensure that the supply-air temperature rise is within
the range on the unit nameplate. Check wiring and
limit switch operation.
3 Flashes
Flame Sense Fault
Indoor fan and inducer On. Flame sense normal.
Power reset for LED
reset.
The IGC sensed a flame when the gas valve should
be closed. Check wiring, flame sensor, and gas valve
operation.
4 Flashes
Four Consecutive Limit
Switch Fault
No gas heating.
Heat call (W) Off.
Power reset for LED
reset.
4 consecutive limit switch faults within a single call for
heat. See Limit Switch Fault.
5 Flashes
Ignition Fault
No gas heating.
Heat call (W) Off.
Power reset for LED
reset.
Unit unsuccessfully attempted ignition for 15 minutes.
Check igniter and flame sensor electrode spacing, gaps,
etc. Check flame sense and igniter wiring. Check gas
valve operation and gas supply.
6 Flashes
Induced Draft Motor
Fault
If heat off: no gas heating.
If heat on: gas valve Off
and inducer On.
Inducer sense normal, or
heat call (W) Off.
Inducer sense On when heat call Off, or inducer
sense Off when heat call On. Check wiring, voltage,
and operation of IGC motor. Check speed sensor
wiring to IGC.
7 Flashes
Rollout Switch Lockout
Gas valve and igniter Off.
Indoor fan and inducer On.
Power reset.
Rollout switch has opened. Check gas valve
operation. Check induced-draft blower wheel is
properly secured to motor shaft.
8 Flashes
Internal Control Lockout No gas heating.
Power reset.
IGC has sensed internal hardware or software error. If
fault is not cleared by resetting 24 v power, replace
the IGC.
9 Flashes
Temporary Software
Lockout
No gas heating.
1 hour auto reset, or
power reset.
Electrical interference is disrupting the IGC software.
LEGEND
IGC
--- Integrated Gas Unit Control
LED
--- Light---Emitting Diode
NOTES
:
1. There is a 3---second pause between alarm code displays.
2. If more than one alarm code exists, all applicable alarm codes will be
displayed in numerical sequence.
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.
Table 19 – Electric Heat Service Analysis
PROBLEM
CAUSE
REMEDY
Heat Will Not Turn On.
Active alarm.
Check active alarms using
Comfort
Link
™
Scrolling
Marquee.
Unit is NOT configured for heat.
Check heating configurations using the
Comfort
Link Scrolling
Marquee
No power to unit.
Check power supply, fuses, wiring, and circuit breakers.
Unit is in minimum heat off-time, or minimum cool-heat
changeover time.
Check using
Comfort
Link Scrolling Marquee.
Thermostat or occupancy schedule setpoint not
calling for heating.
Check using
Comfort
Link Scrolling Marquee.
Heat forced off in Service Test mode.
Check using
Comfort
Link Scrolling Marquee. Turn Service
Test mode off.
No 24 vac at heater contactor.
Check transformer and circuit breaker.
Check auto-reset limit switches on heater.
Check manual-reset limit switch (LS) on indoor fan housing.
Open temperature limit switch on heater.
Check minimum airflow. Check limit switch when it is cool,
replace if open.
Inadequate Heating.
Dirty air filters.
Replace air filters.
Thermostat or occupancy schedule setpoint only
calling for W1.
Allow time for W2 to energize or adjust setpoints.
Heat undersized for load.
Decrease load or increase size of heater.
Restricted airflow
Remove restriction. Check SAT compared to the SAT
heating limits.
Too much outdoor air.
Check economizer position and configuration. Adjust
minimum position.
Limit switch cycles heaters.
Check rotation of blower and minimum airflow.
Bad heater elements.
Power off unit and remove high voltage wires. Check
resistance of element, replace if open.
Heat Will Not Turn Off.
Unit is in minimum heat on-time.
Check using
Comfort
Link Scrolling Marquee.
Thermostat or occupancy schedule setpoint still
calling for heating.
Check using
Comfort
Link Scrolling Marquee.
Heat forced on in Service Test mode.
Check using
Comfort
Link Scrolling Marquee. Turn Service
Test mode off.
Heater contactor failed.
Power off unit. Check contactor and replace if closed.
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...