42
Table 12 –
Comfort
Link
t
Alarm Codes
ALARM
OR
ALERT
NUMBER
DESCRIPTION
ACTION TAKEN BY
CONTROL
RESET
METHOD
PROBABLE CAUSE
T051
Compressor A1 Safety Trip
Add Strike for Circuit A
Automatic
High--- pressure switch open. Compressor internal protection
open. Wiring error
Service Test --- Compressor A1 Safety Trip
Compressor A1 Current Detected After Turnoff
Turn off all compressors
Automatic
Welded contactor
Service Test --- Compressor A1 Current Detected
After Turnoff
T052
Compressor A2 Safety Trip
Add Strike for Circuit A
Automatic
High--- pressure switch open. Compressor internal protection
open. Wiring error
Service Test --- Compressor A2 Safety Trip
Compressor A2 Current Detect After Turnoff
Turn off all compressors
Automatic
Welded contactor
Service Test --- Compressor A2 Current Detected
After Turnoff
T055
Compressor B1 Safety Trip
Add Strike for Circuit B
Automatic
High--- pressure switch open. Compressor internal protection
open. Wiring error
Service Test --- Compressor B1 Safety Trip
Compressor B1 Current Detect After Turnoff
Turn off all compressors
Automatic
Welded contactor
Service Test --- Compressor B1 Current Detected
After Turnoff
T059
Compressor C1 Safety Trip
Add Strike for Circuit C
Automatic
High--- pressure switch open. Compressor internal protection
open. Wiring error
Service Test --- Compressor C1 Safety Trip
Compressor C1 Current Detect After Turnoff
Turn off all compressors
Automatic
Welded contactor
Service Test --- Compressor C1 Current Detected
After Turnoff
T064
Circuit A Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor
fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T065
Circuit B Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor
fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T066
Circuit A Saturated Suction Temperature Thermis-
tor Failure
No Circuit A Cooling
Automatic
Circuit A Suction transducer internally forced inactive
T067
Circuit B Saturated Suction Temperature Thermis-
tor Failure
No Circuit B Cooling
Automatic
Circuit B Suction transducer internally forced inactive
T073
Outdoor Air Temperature Thermistor Failure
No cooling with economizer
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T074
Space Temperature Thermistor Failure
If U.CTL = 3, then no heat-
ing or cooling
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T075
Supply Air Temperature Thermistor Failure
No cooling with economizer
and No adaptive compressor
staging
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T076
Return Air Thermistor Failure
If RAT.S = Yes, then no re-
turn air display
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T077
Space Relative Humidity Sensor Failure
If RH.S = Yes, then no in-
door humidity control
Automatic
Faulty, shorted, or open sensor caused by wiring error or loose
connection.
T080
Circuit C Saturated Condensing Temp Thermistor
Failure
Use OAT to control Outdoor
fans
Automatic
Faulty, shorted, or open thermistor caused by wiring error or
loose connection.
T081
Circuit C Saturated Suction Temperature Thermis-
tor Failure
No Circuit C Cooling
Automatic
Circuit C Suction transducer internally forced inactive
T092
Circuit A Suction Pressure Transducer Failure
Shutdown Circuit A
Manual
Faulty transducer, faulty 5--- V power supply, or loose connec-
tion
T093
Circuit B Suction Pressure Transducer Failure
Shutdown Circuit B
Manual
Faulty transducer, faulty 5--- V power supply, or loose connec-
tion
T101
Circuit C Suction Pressure Transducer Failure
Shutdown Circuit C
Manual
Faulty transducer, faulty 5--- V power supply, or loose connec-
tion
T102
Compressor A1 Current Sensor Failure
If CS.A1 = Enable, then no
T051 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connec-
tion
Compressor A2 Current Sensor Failure
If CS.A2 = Enable, then no
T052 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connec-
tion
T103
Compressor B1 Current Sensor Failure
If CS.B1 = Enable, then no
T055 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connec-
tion
T104
Compressor C1 Current Sensor Failure
If CS.C1 = Enable, then no
T059 current alarm
Automatic
Faulty current sensor caused by wiring error or loose connec-
tion
T110
Circuit A Loss of Charge
Shutdown Circuit A
Manual
Low refrigerant or faulty suction pressure transducer
Service Test --- Circuit A Loss of Charge
T111
Circuit B Loss of Charge
Shutdown Circuit B
Manual
Low refrigerant or faulty suction pressure transducer
Service Test --- Circuit B Loss of Charge
T126
Circuit A High Discharge Pressure
Shutdown Circuit A
Automatic
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high--- pressure switch.
Service Test --- Circuit A High Discharge Pressure
T127
Circuit B High Discharge Pressure
Shutdown Circuit B
Automatic
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high--- pressure switch.
Service Test --- Circuit B High Discharge Pressure
T133
Circuit A Low Refrigerant Pressure
Add Strike for Circuit A
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open econom-
izer when the ambient temperature is low.
Service Test --- Circuit A Low Refrigerant Pressure
T134
Circuit B Low Refrigerant Pressure
Add Strike for Circuit B
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open econom-
izer when the ambient temperature is low.
Service Test --- Circuit B Low Refrigerant Pressure
T140
Circuit C Loss of Charge
Shutdown Circuit C
Manual
Low refrigerant or faulty suction pressure transducer
Service Test --- Circuit C Loss of Charge
T141
Circuit C Low Refrigerant Pressure
Add Strike for Circuit C
Automatic
Low refrigerant charge, dirty filters, evaporator fan turning
backwards, loose or broken fan belt, plugged filter drier, faulty
transducer, excessively cold return air, or stuck open econom-
izer when the ambient temperature is low.
Service Test --- Circuit C Low Refrigerant Pressure
T142
Circuit C High Discharge Pressure
Shutdown Circuit C
Automatic
An overcharged system, high outdoor ambient temperature
coupled with dirty outdoor coil, plugged filter drier, or a faulty
high--- pressure switch.
Service Test --- Circuit C High Discharge Pressure
T143
Circuit A Failure To Pressurize
Add Strike for Circuit A
Automatic
Wiring causing reverse rotation or faulty compressor
Service Test --- Circuit A Failure to Pressurize
T144
Circuit B Failure To Pressurize
Add Strike for Circuit B
Automatic
Wiring causing reverse rotation or faulty compressor
Service Test --- Circuit B Failure to Pressurize
T145
Circuit C Failure To Pressurize
Add Strike for Circuit C
Automatic
Wiring causing reverse rotation or faulty compressor
Service Test --- Circuit C Failure to Pressurize
T153
Real Timeclock Hardware Failure
No time and date schedule
operation
Automatic
No time/date configured, software failure, or MBB failure
* See Legend on next page
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...