103
APPENDIX A — LOCAL DISPLAY AND CCN TABLES (CONT)
MODE — SET POINTS
ITEM
EXPANSION
RANGE
UNITS
DEFAULT
CCN TABLE/
SUB---TABLE
CCN POINT
SETPOINT CONFIGURATION
SETPOINTS
SET_PNT
OCSP
Occupied Cool Setpoint
55 to 80F
dF
78
OCSP
UCSP
Unoccupied Cool Setpoint
75 to 95F
dF
85
UCSP
OHSP
Occupied Heat Setpoint
55 to 80F
dF
68
OHSP
UHSP
Unoccupied Heat Setpoint
40 to 80F
dF
60
UHSP
GAP
Heat--- Cool Setpoint Gap
2 to 10F
dF
5
HCSP_GAP
STO.R
SPT Offset Range (+/--- )
0 to 5F
^F
5
SPTO_RNG
RH.SP
Space RH Setpoint
30 to 95
%
50
SPRH_SP
RH.DB
Space RH Deadband
2 to 20
%
5
SPRH_DB
RH.HB
Reheat Heat SP Deadband
--- 5 to 5
^F
2
RH_HSPDB
CA.LO
Circuit A Lockout Temp
0 to 100F
dF
0
OATLCMPA
CB.LO
Circuit B Lockout Temp
0 to 100F
dF
0: no Humidi--- MiZer FIOP
Humidi--- MiZer FIOP:
40 (03--- 16)
0 (20--- 28)
OATLCMPB
CC.LO
Circuit C Lockout Temp
0 to 100F
dF
0
OATLCMPC
HT.LO
Heating Lockout Temp
40 to 125F
dF
75
OATLHEAT
EH.LO
Econo Cool Hi Temp Limit
40 to 100F
dF
65
OATLECLH
EL.LO
Econo Cool Lo Temp Limit
--- 30 to
50F
dF
0
OATLECLL
FC.LO
Free Cool Low Temp Limit
0 to 70F
dF
50
OATLUEFC
LCSP
Low Cool SAT Setpoint
55 to 75F
dF
55 (03--- 07)
65 (08--- 28)
LCSASP
HCSP
High Cool SAT Setpoint
50 to 70F
dF
55
HCSASP
MODE — INPUTS
ITEM
EXPANSION
RANGE
UNITS
CCN TABLE/
SUB---TABLE
CCN POINT
CCN
WRITE
STATUS
DISPLAY
WRITE
STATUS
STATUS DISPLAY
INPUTS
UINPUT
STAT
Thermostat Inputs
Y1
Thermostat Y1 Input
On/Off
Y1
forcible
Y2
Thermostat Y2 Input
On/Off
Y2
forcible
W1
Thermostat W1 Input
On/Off
W1
forcible
W2
Thermostat W2 Input
On/Off
W2
forcible
G
Thermostat G Input
On/Off
G
forcible
GEN.I
General Inputs
FIL.S
Filter Status Switch
Dirty/Clean
FILTSTAT
forcible
FAN.S
Fan Status Switch
On/Off
FAN_STAT
forcible
FDWN
Fire Shutdown Switch
On/Off
FIREDOWN
forcible
ENTH
Outdoor Enthalpy Switch
High/Low
ENTHALPY
forcible
RM.OC
Remote Occupancy Switch
On/Off
REM_OCC
forcible
HUM
Space Humidity Switch
High/Low
HUM_STAT
forcible
CS.IN
Current Sensor Inputs
CS.A1
Compressor A1 Feedback
On/Off
CS_A1
CS.A2
Compressor A2 Feedback
On/Off
CS_A2
CS.B1
Compressor B1 Feedback
On/Off
CS_B1
CS.C1
Compressor C1 Feedback
On/Off
CS_C1
AIR.Q
Air Quality Inputs
IAQ.S
IAQ Level (switch)
High/Low
IAQIN
forcible
forcible
IAQ
IAQ Level (sensor)
xxxx
ppm
IAQ
forcible
forcible
OAQ
OAQ Level (sensor)
xxxx
ppm
OAQ
forcible
forcible
SP.RH
Space Humidity Sensor
xxx.x
%
SPRH
forcible
forcible
48/
50P
G
and
P
M
Содержание 48/50PG Series
Страница 32: ...32 C07009 Fig 20 Air Baffle Dimensions 48 50PG03 16 48 50PG and PM...
Страница 33: ...33 C08077 Fig 21 Air Baffle Dimensions 48 50PG20 28 and 48 50PM16 28 48 50PG and PM...
Страница 58: ...58 C08549 Fig 28 48PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 59: ...59 C08550 Fig 29 50PG03 16 Control Wiring Schematic 48 50PG and PM...
Страница 60: ...60 C08551 Fig 30 Typical 48 50PG03 16 Power Wiring Schematic and Legend 48 50PG16 460 3 60 Shown 48 50PG and PM...
Страница 64: ...64 C08471 Fig 34 Typical 48PG and PM16 28 Control Schematic 48PM16 28 Shown 48 50PG and PM...
Страница 66: ...66 C08557 Fig 36 Typical 50PG and PM16 28 Control Schematic 50PG20 28 Shown 48 50PG and PM...
Страница 67: ...67 C08064 Fig 37 Typical 50PG and PM16 28 with Humidi MiZert Control Schematic 50PM16 28 Shown 48 50PG and PM...
Страница 68: ...68 C08558 Fig 38 Typical 48 50PG and PM16 28 Power Schematic 48 50PM16 28 Shown 48 50PG and PM...
Страница 72: ...72 C08565 Fig 42 Typical 48 50PG20 28 Component Arrangement 48 50PG20 24 Shown 48 50PG and PM...
Страница 73: ...73 C08067 Fig 43 48 50PM16 28 Component Arrangement 48 50PG and PM...
Страница 74: ...74 C08562 Fig 44 48 50PM16 28 with Humidi MiZert Component Arrangement 48 50PG and PM...
Страница 208: ...208 48 50PG and PM...