Carlin 702GAS Скачать руководство пользователя страница 8

MN702GE  060320

– 8 –

Prepare the appliance

 

Burner input: Install a burner sized for the normal input rating 

of the appliance. Do not install a burner with a higher firing rate 

than the appliance rating. Do not install a burner with a firing 

rate more than 10% lower than the appliance rating. The appli-

ance and vent system could be damaged due to condensation.

 

Clean the appliance: Clean the appliance thoroughly. Test all 

electrical components and verify the relief valve works (boilers 

only).

 

Seal the appliance: Seal all flue-gas containing joints.  Seal all 

connections to the vent piping or breeching.

 

Verify combustion chamber dimensions comply with the mini-

mum dimensions recommended on page 9. Install or replace 

chamber liner if required by the appliance manufacturer. The 

burner must not extend into the combustion chamber. The end 

of the burner air tube must be withi 1/4" of the inside face of 

the chamber. If the space around the burner air tube is more 

than 1/4", wrap the burner air tube with minimum 2300-°F-rated 

ceramic fiber blanket to seal off the gap. 

 

Repair or replace damaged appliance components. Inspect 

the appliance thoroughly. Follow appliance manufacturer’s 

guidelines for repair or replacement of any component found 

defective.

 

When cleaning the appliance or working with ceramic fiber 

refractories or fiberglass insulation, see WARNING on this 

page.

 

Failure to comply with the above could result in severe personal 

injury, death or substantial property damage.

Prepare appliance for burner mounting

 

Positive overfire pressure applications: When firing with positive 

overfire pressure, do not exceed the pressure specified in the 

appliance manual.

 

Positive overfire pressure reduces maximum burner capacity. 

See Page 3 for estimated reduction in burner capacity with 

pressurized firing and high altitude applications.

 

Failure to comply could result in severe personal injury, death 

or substantial property damage.

Ceramic fiber or 

Fiberglass insulation

 

Ceramic fiber materials, such as chamber liners, may 

contain carcinogenic particles (chrystobalites) after 

exposure to heat. Airborne particles from fiberglass 

or ceramic fiber components have been listed as po-

tentially carcinogenic by the State of California. Take 

the following precautions when removing, replacing 

and handling these items.

 

Avoid breathing dust and avoid contact with skin or 

eyes. Wear long-sleeved, loose-fitting clothing, gloves 

and eye protection. Use a NIOSH N95 certified respira-

tor. This respirator meets requirements for protection 

from chrystobalites. Actual job requirements or NIOSH 

regulations may require other or additional protec-

tion. For information, refer to the NIOSH website, 

http://www.cdc.gov/niosh/homepage.html.

 

Ceramic fiber removal: To prevent airborne dust, 

thoroughly wet ceramic fiber with water before han-

dling. Place ceramic fiber materials in a plastic bag 

and seal to dispose.

 

Avoid blowing, tearing, sawing or spraying fiber-

glass or ceramic fiber materials. If such operations are 

necessary, wear extra protection to prevent breathing 

dust.

 

Wash work clothes separately from other laundry

Rinse clothes washer thoroughly afterwards to prevent 

contamination of other clothing.

 

NIOSH First aid procedures:

 

Eye exposure — irrigate immediately

 

Breathing — fresh air.

2.  Pre-fire inspection  •  preparation 

(continued)

Содержание 702GAS

Страница 1: ...maintenance on back page for information regarding operation of this burner The burner Instruction Manual is intended only for your service technician The burner and heat exchanger must be inspected a...

Страница 2: ...heguidelinesbelowtoavoidpotentialsevere personal injury death or substantial property dam age Installer service technician Read all instructions before proceeding Perform all procedures and in the ord...

Страница 3: ...mply with the latest editions of Installation of Domestic Gas Conversion Burners ANSI Z21 8 National Fuel Gas Code ANSI Z223 1 NFPA 54 National Electrical Code ANSI NFPA 70 All additional applicable n...

Страница 4: ...into the burner through a manifold around the air tube The gas then circulates through a set of four orifice spuds into the air stream upstream of the retention ring The spin of the air flow at the re...

Страница 5: ...0 Btuh of all appliances in the space Do not install or operate the burner if any component is dam aged or if burner does not comply with other guidelines of this manual and the appliance manual Inspe...

Страница 6: ...u facturer s instructions Wire the switch into the appliance limit circuit to shut off the appliance burner if sustained downdraft should occur Refer to the appliance manufacturer s instruction manual...

Страница 7: ...2 Metal louvers or grilles free area area times 0 60 3 Screens when used must be no smaller than inch mesh Motorized vent dampers Wire the vent damper end switch to prevent operation of the burner un...

Страница 8: ...ications Whenfiringwithpositive overfire pressure do not exceed the pressure specified in the appliance manual Positive overfire pressure reduces maximum burner capacity See Page 3 for estimated reduc...

Страница 9: ...e a floor liner when possible The floor liner will improve firing in most applications Extend floor liner 3 to 4 inches up the side walls 4 Target wall liners Extend target wall liners at least 3 to 4...

Страница 10: ...ance opening so the end of the air tube is flush with or slightly short of the inside surface of the combustion chamber 4 Place gasket onto boiler front plate 5 Slide the end of the air tube into the...

Страница 11: ...enough ventilation to prevent overheating of the appliance burner and controls If there is risk of overheating you must install ventilation air openings sized large enough to provide air for cooling t...

Страница 12: ...e terminal strip inside the gas train J box b See the label in the burner junction box included Gas valve vent opening The V48 diaphragm gas valve is NOT fitted with a vent limiting orifice in the ven...

Страница 13: ...be more than the gas pressure at the burner gas train en trance minus 3 4 w c pressure required at entrance to butterfly valve See Figure 6 for gas train pressure drop information The standard gas tra...

Страница 14: ...990 810 690 620 2 2 750 1 900 1 520 1 300 1 150 2 4 350 3 000 2 400 2 050 1 850 Note 1 For natural gas with specific gravity other than 0 60 consult National Fuel Gas Code for correction factor PROPAN...

Страница 15: ...rmation for burner equipped with a primary control not covered in this manual see Figure 7A for a legend to callouts Turn off power to appliance when servicing burner Failure to comply could result in...

Страница 16: ...steam boiler activated Read the appliance manual for the location of the high fire control when used 3 See Figures 7 and 8 to connect the high fire control to the burner firing rate circuit 4 The burn...

Страница 17: ...nuals and wiring diagrams Gas manifold spud orifices sealed with pipe dope and tight Gas lines in good condition sized and designed correctly Gas line connections and fittings tight Burner appliance a...

Страница 18: ...et air damper linkage Table 5 Initial burner settings see the pages 18 through 22 for final adjustments using test instruments 6 Set burner initial head and damper positions continued 3 4 Determining...

Страница 19: ...e the maximum burner firing rate is reduced The firing rate is also reduced for altitudes higher than 2000 feet above sea level See page 3 for rating information 3 Adjust the burner fuel and air setti...

Страница 20: ...personal injury death or substantial property damage 3 Check the flame signal after the pilot has shut down to ensure the signal is still strong with main flame on 4 Move the burner fuel selector swi...

Страница 21: ...ly valve indicator until it is at 90 Disengage actuator motor Rotate linkage to high fire Tighten the two hex head screws while still holding the motor linkage arm in high fire Rotate linkage to low f...

Страница 22: ...ion with exhaust fans or other conditions operating 7 Adjust the burner using test instruments continued Combustion ventilation air Verify combustion ventilation air openings are not and will not be o...

Страница 23: ...s valves before disconnecting any portion of fuel lines and before cleaning or removing any parts from the burner or related equipment Burner and appliance components can be extremely hot Allow all pa...

Страница 24: ...season and to verify user is aware of proper operation and care of the burner appliance Review proper operation of the appliance burner unit with the user Turn off power to appliance Remove combustion...

Страница 25: ...Btuh Manifold gas pressure IWC High fire Low fire Inlet gas pressure IWC CO2 Gas Low Fire ______ Gas High Fire ______ Gas Low Fire ______ Gas High Fire ______ O2 Were limit controls tested Comments ab...

Страница 26: ...4 Combustion Head Assembly for 702GAS 7 4180002FS Gas Ignitor 8 35824S Motor Contactor 20 AMP R4242B1005 not shown ITEM PART NO DESCRIPTION 9 35311S C7027A1023 UV Scanner 97656S Q7800B1003 Sub Base 99...

Страница 27: ...appliance burner unit NEW PHOTO TO COME ITEM PART NO DESCRIPTION 16 35824S Motor Contactor 20 AMP R4242B1005 19 EMX51UVS EMX51UV KIT includes all of the below 35311S C7027A1023 UV Scanner 97656S Q780...

Страница 28: ...MN702GE 060320 28 10 Dimensions Figure 14 Dimensional data...

Страница 29: ...MN702GE 060320 29 10 Dimensions continued Figure 14A Dimensional data angled gas train...

Страница 30: ...and liquids Do not obstruct the flow of combustion and ventilating air Most motors currently used on residential type burners use permanently lubricated bearings and do not require field lubri cation...

Отзывы: