background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 4 –

Where appliance instructions differ from this manual, follow the appliance instructions.

702G/O overview

The Model 702G/O combination gas/oil burner is a low-high-low (step 

modulating) burner that utilizes a damper motor to control air (and gas fuel 

rate). Fuel is selected using the Gas/oil changeover switch. The burner 

operates on either #2 fuel oil or gas (natural or propane).

See the next page for gas train component locations.

Gas mode operation

Ignition for main flame is accomplished by a proved gas pilot of approxi-

mately 280,000 Btuh. Pilot gas is introduced at the main burner flame 

retention ring, and is ignited by a Carlin 14,000-volt electronic ignitor 

wired to the two electrodes. After the pilot flame is proven, the two main 

gas safety valves open. The pilot gas valve closes after a time delay to 

allow main flame to establish. Flame is monitored both for pilot flame and 

main flame with a UV scanner mounted to the under side of the burner 

combustion head assembly. The burner main flame begins at low fire. 

If additional input is required, the damper motor opens the gas butterfly 

valve and air damper to their high fire positions.

Gas is introduced into the burner through a manifold around the air tube. 

The gas then circulates through a set of four orifice spuds into the air 

stream, ahead of the retention ring. The spin of the air flow at the retention 

ring thoroughly mixes the gas/air before it reaches the combustion zone.

Oil mode operation

Oil ignition is accomplished by the Carlin 14,000-volt electronic ignitor 

wired to the two electrodes. The oil flame begins at low fire, with 100 

psig

 

oil pressure at the nozzle. If additional input is needed, the damper mo-

tor opens the air to the high fire position. The damper motor end switch 

energizes the 2nd stage oil valve (fuel unit blocking valve) as the damper 

approaches its high fire position. This provides 300 

psig

 pressure to the 

oil nozzle for high fire. Flame is monitored by the UV scanner mounted 

to the under side of the combustion head assembly.

Firing rate adjustment

• 

Firing rate is determined by the oil nozzle. Air flow is matched to the oil 

flow for oil firing. Then gas flow is adjusted to match the air flow at low 

and high fire rates.

• 

See the “Starting and operating” section of this manual for the complete 

description of the adjustment process. The following is a brief summary 

only.

• 

High-fire air is set by adjusting the combustion head position (to control 

air flow through and around the retention ring).

• 

Low-fire air is then adjusted by fine-tuning the position of the low fire 

adjusting screw.

• 

Pilot gas flow is set for a smooth light-off. Then gas inputs are adjusted 

for good combustion at low and high-fire air settings.

1. The Carlin Model 702G/O combination gas/oil burner

702G/O oil nozzles

  Use the selections below when the heating equipment 

manufacturer’s specific nozzle selection data is not available, 

either in the equipment manual or the Carlin OEM Spec 

Guide. Follow all instructions provided with the appliance.

Nozzle specifications

• 

Preferred

 — 

Hago 45° SS

• 

Alternate

 — 

Hago 45° P or Monarch 45° PLP

Nozzle ratings

Full input (high fire) occurs at 300 psig nozzle pressure. Since nozzles 

are rated at 100 psig, the actual flow at 300 psig is approximately 73% 

higher than the rated nozzle capacity. See the table below for nozzle 

rating selections.

Table 1 

702G/O oil nozzles

 

Oil Nozzle Sizing

Equipment

Input rating

GPH

Recommended

nozzle rating

GPH

Low fire

input

(100 psig)

High fire

input

(300 psig)

6.00

3.50

3.50

6.00

6.50

3.75

3.75

6.50

6.90

4.00

4.00

6.90

7.80

4.50

4.50

7.80

8.70

5.00

5.00

8.70

9.50

5.50

5.50

9.50

10.40

6.00

6.00

10.40

11.20

6.50

6.50

11.20

1. For a packaged appliance application on which the burner has been tested, use the noz-

zle given in the appliance manufacturer's instructions or supplement for the best 
results.

Gas pressure requirements

The 702G/O burner requires 3.4" w.c. minimum pressure at the butterfly 

valve during high fire. Select a gas train that has a pressure drop no 

more than the available pressure at the gas train inlet minus the 3.4" 

needed at the butterfly valve. See page 13 for gas train pressure drop 

information. The burner is equipped with a 1" gas train unless a larger 

gas train is ordered.
Example: A boiler has an input rating of 1,300,000 Btuh. Gas pressure 

available at the gas train entrance is 6.0" w.c. Subtract 3.4” from the 

available 6.0" w.c. The gas train pressure drop must be 2.6” or less. A 1" 

gas train has a pressure drop of 3.3" w.c., and cannot be used. Select a 

1¼" RV-61 regulator gas train, which has a pressure drop of 0.87" w.c.

Содержание 702G/O

Страница 1: ...stantial property damage USER Refer only to User care and maintenance on back page for information regarding operation of this burner The burner Instruction Manual is intended only for your service te...

Страница 2: ...uidelinesbelowtoavoidpotentialsevere personal injury death or substantial property dam age Installer service technician Read all instructions before proceeding Perform all procedures and in the order...

Страница 3: ...n of Domestic Gas Conversion Burners ANSI Z21 8 National Fuel Gas Code ANSI Z223 1 NFPA 54 Standard for the Installation of Oil Burning Equipment NFPA 31 National Electrical Code ANSI NFPA 70 All addi...

Страница 4: ...firing Then gas flow is adjusted to match the air flow at low and high fire rates See the Starting and operating section of this manual for the complete description of the adjustment process The foll...

Страница 5: ...d assembly 22 Oil valve junction box 23 1st stage oil valve 24 Safety oil valve 25 2nd stage oil valve fuel unit blocking valve 29 Gas manifold 30 Gas spuds 4 required 31 Gas butterfly valve 32 Butter...

Страница 6: ...vent piping on the appliance flue outlet Clearances Check codes standards and the equipment manual Verify that the burner appliance will maintain all clearances to combustible walls or floor and all c...

Страница 7: ...ea area times 0 25 2 Metal louvers or grilles free area area times 0 60 3 Screens when used must be no smaller than inch mesh Motorized vent dampers Wire the vent damper end switch to prevent operatio...

Страница 8: ...Prepare appliance for burner mounting Positive overfire pressure applications When firing with positive overfire pressure do not exceed the pressure specified in the appliance manual Positive overfir...

Страница 9: ...target wall liner if flame length is close to the length of the chamber 3 Use a floor liner when possible The floor liner will improve firing in most applications Extend floor liner 3 to 4 inches up t...

Страница 10: ...tube flange assembly into the appliance opening Rotate the flange if needed to align with the mounting bolts Secure the flange to the appliance front plate 7 See the following instructions to install...

Страница 11: ...separate instructions if installing an optional knocked down gas train The gas train is available in either an angled standard or straight optional configuration 2 Connect the main and pilot gas trai...

Страница 12: ...s orifice nipple item 1 page 29 The label on the orifice nipple must agree with the gas used natural or propane gas If the nipple is not correct for the gas being used obtain the correct orifice nippl...

Страница 13: ...han 0 60 consult National Fuel Gas Code for correction factor PROPANE GAS Capacities in Btuh for Schedule 40 metal pipe Propane gas 1 5 specific gravity pressure drop 1 psi 1 839 1 264 1 015 869 770 3...

Страница 14: ...vacuum does not exceed the limit below during all firing conditions Oil flow schematic fuel unit connections Figure 10 shows oil flow and fuel unit port functions for Carlin 702G O burners Figure 11 a...

Страница 15: ...et 3 8 O D 1 2 O D 0 41 100 2 37 100 4 32 100 6 28 100 8 24 96 10 20 80 12 16 64 14 48 16 32 Figure 11 702G O burner with NYC DAR pressure regulation kit Obtain pressure regulator kitsforNewYorkCityDe...

Страница 16: ...applicable local codes standards 2 Connect the burner following Figures 13 and 14 and any special instructions or wiring diagrams provided with the appliance burner or other components 3 The burner re...

Страница 17: ...ns or wiring diagrams provided with the appliance burner or other components 3 The burner requires a 120 VAC 60 hz single phase control power supply with a 5 amp fuse The control circuit current draw...

Страница 18: ...cycle to low fire as demand decreases This keeps the burner on longer reducing cyclic losses 2 The appliance must be equipped with a high fire control This would be a make on fall control either temp...

Страница 19: ...high low cycles The firing cycle can be much longer using low high low firing because the burner can cycle to low fire as demand decreases This keeps the burner on longer reducing cyclic losses 2 The...

Страница 20: ...vent system Are voltages correct Burner appliance and motor correctly wired per burner and appliance manuals and wiring diagrams Gas manifold spud orifices on gas manifold item 29 page 5 sealed with p...

Страница 21: ...est instruments and make final burner adjustments Figure 17 Set initial low fire air damper setting Figure 16 Set initial combustion head position Low fire input High fire input Combustion head positi...

Страница 22: ...Failure to properly adjust the burner can result in severe personal injury death or substantial property damage Start the burner firing on oil Do not start the burner if the combustion chamber contai...

Страница 23: ...7 Restart the burner and check modulation again Continue with 1 through 6 above as needed until results are acceptable 8 Turn off the burner when Step 3 is completed before proceeding with setup for g...

Страница 24: ...o OFF The burner will shut down 5 Temporarily install two U tube manometer connections to check gas pres sures Install connections at the inlet pressure tap of the main manual gas valve and at the dow...

Страница 25: ...Tighten the swivel joint in place 10 Raise the damper motor linkage by pulling up on the damper linkage locknut and hold in this position The butterfly valve shaft slot must be horizontal If not use a...

Страница 26: ...xhausted from building If the building contains any exhaust fans or conditions that could affect vent performance check burner appliance vent operation with exhaust fans or other conditions operating...

Страница 27: ...tears can break away and plug the nozzle or fuel unit Perform the complete checkout procedures of pages 18 to 23 including system inspection and checks Inform the user of any problems found 8 Maintena...

Страница 28: ...h Oil nozzle size pattern Manifold gas pressure IWC High fire Low fire Inlet gas pressure IWC CO2 Oil Low Fire ______ Oil High Fire ______ Gas Low Fire ______ Gas High Fire ______ O2 Oil Low Fire Oil...

Страница 29: ...Model 702G O Advanced gas oil burners Instruction manual Carlin part number MN702GO Rev 06 23 14 29 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 30: ...appliance instructions differ from this manual follow the appliance instructions 9 Dimensions Figure 19 Dimensional data straight gas train configuration 1 Honeywell R7897C primary control standard 2...

Страница 31: ...liance instructions differ from this manual follow the appliance instructions Figure 20 Dimensional data angled gas train configuration 9 Dimensions continued 1 Honeywell R7897C primary control standa...

Страница 32: ...ed for high fire 23556S 6 Fuel line 75291 7 Airflow switch 98522 8 Honeywell M436 damper motor 35808 9 Gasket 40246 10 14 airtube with pressurized flange 1 main gas inlet 1 2 pilot inlet 99541 11 14 c...

Страница 33: ...art number MN702GO Rev 06 23 14 33 Where appliance instructions differ from this manual follow the appliance instructions 10 Repair parts continued For parts not shown or listed contact factory and or...

Страница 34: ...ruct the flow of combustion and ventilating air Most motors currently used on residential type burners use permanently lubricated bearings and do not require field lubri cation Read the label on the m...

Отзывы: