background image

Model 702G/O Advanced gas/oil burners — Instruction manual

Carlin part number MN702GO Rev. 06/23/14

– 23 –

Where appliance instructions differ from this manual, follow the appliance instructions.

8.  Adjust the burner using test instruments 

(continued)

3. 

See Figure 17, page 19. Adjust the low-fire damper screw until the low-fire 

CO

2

 is between 11% and 12%. Rotate the screw clockwise to increase 

airflow (reduced CO

2

). Rotate the screw counterclockwise to decrease 

airflow (increase CO

2

).

4. 

Smoke at low fire must be zero or a trace. Note that too much air can 

actually increase smoke.

Step 3 

(firing on oil)

 

Damper motor end switch position

1. 

Modulate the burner from low fire to high fire and back to low fire, pausing 

at each step for about one minute.

2. 

If the swing from low fire to high fire is rough (burner bangs or rumbles), 

or the fire is very smoky, the damper end switch may be in the wrong 

position. High-fire oil should pull in as the air damper, NOT THE DAMPER 

ARM, is about halfway through its swing.

3. 

For different appliance applications, it is sometimes necessary to have 

high-fire oil pressure pull in earlier or later than normal during the swing 

to achieve a smoother, cleaner transition.

4. 

If the swing is rough (flame goes out, bangs or rumbles), there could 

be air in the oil, or the nozzle may be defective. Check, and replace the 

nozzle if necessary. Then retry.

5. 

If the fire is too lean, the flame could lift off of the head, causing rumble or 

unsteady combustion. In this case, adjust the damper motor end switch 

to energize earlier.

6. 

If the flame is very smoky, then cleans up again, the damper motor end 

switch should be set to energize later. To adjust the damper motor end 

switch:

• 

Remove the damper motor cover.

• 

This will expose a white plastic gear with notches.

• 

With the burner OFF, use the end of a small-bladed screwdriver inserted 

into one of the notches of the white gear to rotate the gear as needed.

• 

Turn the gear one notch CLOCKWISE for a LATER PULL-IN.

• 

Turn the gear one notch COUNTERCLOCKWISE for an EARLIER 

PULL-IN.

7. 

Restart the burner and check modulation again. Continue with 1 through 

6 above as needed until results are acceptable.

8. 

Turn off the burner when Step 3 is completed before proceeding with 

setup for gas combustion, Step 4.

  The linkage between the damper motor arm and 

the air damper crank is set at the factory, and 

should ONLY need adjustment if the damper motor 

or the damper rod is replaced. With the burner in 

high-fire position, there should be minimal play in 

the connecting rod. DO NOT change this linkage  

setting. 

Step 1 

(firing on oil)

 

Set combustion head 

(Dimension “A”)

1. 

Allow the burner to operate approximately 15 minutes to ensure the ap-

pliance is heated and combustion is steady.

2. 

Set the overfire draft to -.02 inches w.c., or as specified in the appliance 

manual.

3. 

The combustion head adjusting screw is used to set the spacing between 

the retention ring and throttle ring, regulating how much air passes 

around the retention ring. (See Figure 16, page 19.) The larger the value 

of dimension A, the larger the clearance, so the larger the airflow. The 

smaller the value of dimension A, the smaller the airflow.

4. 

Measure the %CO

2

 in the appliance flue. The value should be approxi-

mately 12.5% for high fire oil. If the CO

2

 is higher than 12.5%, adjust the 

head adjusting screw (see Figure 16, page 19) to a larger dimension A 

to increase airflow. If the CO

2

 is less than 12.5%, adjust the screw to a 

smaller dimension A to decrease airflow.

5. 

Reset overfire draft to -.02 inches w.c., or as specified in the appliance 

manual, after any airflow adjustment. 

6. 

Check the smoke value in the appliance flue. It must be zero to a trace. 

If not, try increasing airflow (reducing the CO

2

)

. If increasing airflow 

increases smoke, the combustion is probably on the wrong side of the 

CO

2

 curve. To correct, increase the airflow until the smoke is eliminated.

7. 

When adjustments are completed, the CO

2

 must be between 12.0% 

and 12.5% at high fire oil, with smoke equal to zero or a trace. Overfire 

draft must be -.02 inches w.c., or as specified in the appliance manual.

Step 2 

(firing on oil)

 

Set low-fire damper

1. 

Flip the low-fire switch to low fire.

2. 

The burner fuel unit blocking valve will be deactivated, and the oil nozzle 

pressure will drop to 100 PSIG.

Содержание 702G/O

Страница 1: ...stantial property damage USER Refer only to User care and maintenance on back page for information regarding operation of this burner The burner Instruction Manual is intended only for your service te...

Страница 2: ...uidelinesbelowtoavoidpotentialsevere personal injury death or substantial property dam age Installer service technician Read all instructions before proceeding Perform all procedures and in the order...

Страница 3: ...n of Domestic Gas Conversion Burners ANSI Z21 8 National Fuel Gas Code ANSI Z223 1 NFPA 54 Standard for the Installation of Oil Burning Equipment NFPA 31 National Electrical Code ANSI NFPA 70 All addi...

Страница 4: ...firing Then gas flow is adjusted to match the air flow at low and high fire rates See the Starting and operating section of this manual for the complete description of the adjustment process The foll...

Страница 5: ...d assembly 22 Oil valve junction box 23 1st stage oil valve 24 Safety oil valve 25 2nd stage oil valve fuel unit blocking valve 29 Gas manifold 30 Gas spuds 4 required 31 Gas butterfly valve 32 Butter...

Страница 6: ...vent piping on the appliance flue outlet Clearances Check codes standards and the equipment manual Verify that the burner appliance will maintain all clearances to combustible walls or floor and all c...

Страница 7: ...ea area times 0 25 2 Metal louvers or grilles free area area times 0 60 3 Screens when used must be no smaller than inch mesh Motorized vent dampers Wire the vent damper end switch to prevent operatio...

Страница 8: ...Prepare appliance for burner mounting Positive overfire pressure applications When firing with positive overfire pressure do not exceed the pressure specified in the appliance manual Positive overfir...

Страница 9: ...target wall liner if flame length is close to the length of the chamber 3 Use a floor liner when possible The floor liner will improve firing in most applications Extend floor liner 3 to 4 inches up t...

Страница 10: ...tube flange assembly into the appliance opening Rotate the flange if needed to align with the mounting bolts Secure the flange to the appliance front plate 7 See the following instructions to install...

Страница 11: ...separate instructions if installing an optional knocked down gas train The gas train is available in either an angled standard or straight optional configuration 2 Connect the main and pilot gas trai...

Страница 12: ...s orifice nipple item 1 page 29 The label on the orifice nipple must agree with the gas used natural or propane gas If the nipple is not correct for the gas being used obtain the correct orifice nippl...

Страница 13: ...han 0 60 consult National Fuel Gas Code for correction factor PROPANE GAS Capacities in Btuh for Schedule 40 metal pipe Propane gas 1 5 specific gravity pressure drop 1 psi 1 839 1 264 1 015 869 770 3...

Страница 14: ...vacuum does not exceed the limit below during all firing conditions Oil flow schematic fuel unit connections Figure 10 shows oil flow and fuel unit port functions for Carlin 702G O burners Figure 11 a...

Страница 15: ...et 3 8 O D 1 2 O D 0 41 100 2 37 100 4 32 100 6 28 100 8 24 96 10 20 80 12 16 64 14 48 16 32 Figure 11 702G O burner with NYC DAR pressure regulation kit Obtain pressure regulator kitsforNewYorkCityDe...

Страница 16: ...applicable local codes standards 2 Connect the burner following Figures 13 and 14 and any special instructions or wiring diagrams provided with the appliance burner or other components 3 The burner re...

Страница 17: ...ns or wiring diagrams provided with the appliance burner or other components 3 The burner requires a 120 VAC 60 hz single phase control power supply with a 5 amp fuse The control circuit current draw...

Страница 18: ...cycle to low fire as demand decreases This keeps the burner on longer reducing cyclic losses 2 The appliance must be equipped with a high fire control This would be a make on fall control either temp...

Страница 19: ...high low cycles The firing cycle can be much longer using low high low firing because the burner can cycle to low fire as demand decreases This keeps the burner on longer reducing cyclic losses 2 The...

Страница 20: ...vent system Are voltages correct Burner appliance and motor correctly wired per burner and appliance manuals and wiring diagrams Gas manifold spud orifices on gas manifold item 29 page 5 sealed with p...

Страница 21: ...est instruments and make final burner adjustments Figure 17 Set initial low fire air damper setting Figure 16 Set initial combustion head position Low fire input High fire input Combustion head positi...

Страница 22: ...Failure to properly adjust the burner can result in severe personal injury death or substantial property damage Start the burner firing on oil Do not start the burner if the combustion chamber contai...

Страница 23: ...7 Restart the burner and check modulation again Continue with 1 through 6 above as needed until results are acceptable 8 Turn off the burner when Step 3 is completed before proceeding with setup for g...

Страница 24: ...o OFF The burner will shut down 5 Temporarily install two U tube manometer connections to check gas pres sures Install connections at the inlet pressure tap of the main manual gas valve and at the dow...

Страница 25: ...Tighten the swivel joint in place 10 Raise the damper motor linkage by pulling up on the damper linkage locknut and hold in this position The butterfly valve shaft slot must be horizontal If not use a...

Страница 26: ...xhausted from building If the building contains any exhaust fans or conditions that could affect vent performance check burner appliance vent operation with exhaust fans or other conditions operating...

Страница 27: ...tears can break away and plug the nozzle or fuel unit Perform the complete checkout procedures of pages 18 to 23 including system inspection and checks Inform the user of any problems found 8 Maintena...

Страница 28: ...h Oil nozzle size pattern Manifold gas pressure IWC High fire Low fire Inlet gas pressure IWC CO2 Oil Low Fire ______ Oil High Fire ______ Gas Low Fire ______ Gas High Fire ______ O2 Oil Low Fire Oil...

Страница 29: ...Model 702G O Advanced gas oil burners Instruction manual Carlin part number MN702GO Rev 06 23 14 29 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 30: ...appliance instructions differ from this manual follow the appliance instructions 9 Dimensions Figure 19 Dimensional data straight gas train configuration 1 Honeywell R7897C primary control standard 2...

Страница 31: ...liance instructions differ from this manual follow the appliance instructions Figure 20 Dimensional data angled gas train configuration 9 Dimensions continued 1 Honeywell R7897C primary control standa...

Страница 32: ...ed for high fire 23556S 6 Fuel line 75291 7 Airflow switch 98522 8 Honeywell M436 damper motor 35808 9 Gasket 40246 10 14 airtube with pressurized flange 1 main gas inlet 1 2 pilot inlet 99541 11 14 c...

Страница 33: ...art number MN702GO Rev 06 23 14 33 Where appliance instructions differ from this manual follow the appliance instructions 10 Repair parts continued For parts not shown or listed contact factory and or...

Страница 34: ...ruct the flow of combustion and ventilating air Most motors currently used on residential type burners use permanently lubricated bearings and do not require field lubri cation Read the label on the m...

Отзывы: