68
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Functions
5.13.2
C
ontrol in chiller mode
Fan control may be modulating or ON-OFF and is based on the saturated temperature value, equivalent to the condensing
pressure, limited by Tc max.
User
C
ode
Description
Def
Min
Max
U
O
M
S
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C
S
S028
Source fan in cooling: set point
30.0
-999.9
999.9
°C
S
S034
Source fan: diff erential in cooling
15.0
0.0
99.9
K
S
S036
Modulating source fan: min speed value
20.0
0.0
100.0
%
S
S037
Modulating source fan: max speed value
80.0
0.0
100.0
%
The control diagram is shown below:
300053_063_R01
DT
5.0 K
1.5 K
Min speed
Max speed
100%
Inverter
SP
Tc max
Tc (°C)
Key
Max speed
Modulating source fan: max speed value
Min speed
Modulating source fan: min speed value
SP
Control set point
DT
Control diff erential
Tc max
Maximum condensing temperature
Tc
Condensing temperature
Fig. 5.r
In the graph, some off sets are expressed with a numerical value, indicating that they are not modifi able but rather are fi xed
parameters. The current calculated set point value is displayed on the dashboard.
Set point control
In chiller mode, a specifi c condensing temperature set point for starting the compressor can be set to a value that is higher than
the nominal set point, so that the compressor can reach steady operation more quickly. The transition to the nominal set point
is made gradually over a time equal to the delay at start-up.
User
C
ode
Description
Def
Min
Max
U
O
M
S
S031
Source fan in cooling: set point at start-up
45.0
0.0
999.9
°C
S
S032
Source fan: delay at start-up in cooling
240
0
999
s
300053_063_R01
300053_064_R01
D1
Cnd SP
Start SP
Nom SP
Comp ON
t (s)
Key
Cnd SP
Condensing temperature set point
Start SP
Set point at start-up
Nom SP
Nominal set point
Cmp ON
Compressor activation
D1
Delay at start-up
Fig. 5.s
5.13.3
C
ontrol in heat pump mode
Fan control may be modulating or ON-OFF and is based on the saturated temperature value, equivalent to the evaporation
pressure.
User
C
ode
Description
Def
Min
Max
U
O
M
S
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C
S
S029
Source fan in heating: set point
10.0
0.0
99.9
°C
S
S035
Source fan: diff erential in heating
5.0
0.0
99.9
K
S
S036
Modulating source fan: min speed value
20.0
0.0
100.0
%
S
S037
Modulating source fan: max speed value
80.0
0.0
100.0
%