91
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Supervisor table
7. SUPERVISOR
TABLE
μChiller provides a database of supervisor variables via Modbus RTU protocol over RS485 (BMS port on the μChiller controller).
The BMS port has the following default settings:
• baud rate 115,200;
• data bits 8;
• no
parity;
• stop bits 1.
See "Parameter table: BMS port" to set diff erent values.
"Index" is the address specifi ed in the Modbus® frame.
7.1
C
oil
S
tatus
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM Description
0
1
U001
BOOL
R/W
U001 - Reset user pump 1 hour counter
1
1
U004
BOOL
R/W
U004 - Reset user pump 2 hour counter
2
1
U010
BOOL
R/W
U010 - Enable set point compensation (0 = Disabled, 1 = Enabled)
3
1
U017
BOOL
R/W
U017 - Enable scheduler (0 = disabled, 1 = enabled)
4
1
U022
BOOL
R/W
U022 - Scheduler type (0 = Switch off , 1 = Change set point)
5
1
U034
BOOL
R/W
U034 - Type of cooling/heating changeover (0 = Keypad, 1 = DIn)
6
1
U036
BOOL
R/W
U036 - Control probe at start-up (0 = Return, 1 = Delivery)
7
1
U038
BOOL
R/W
U038 - Control probe when running (0 = Return, 1 = Delivery)
8
1
U057
BOOL
R/W
U057 - Remote alarm input logic (0 = NC, 1 = NO)
9
1
U058
BOOL
R/W
U058 - Cooling/heating input logic (0 = NO, 1 = NC)
10
1
U059
BOOL
R/W
U059 - Remote unit ON/OFF input logic (0 = NO, 1 = NC)
11
1
U060
BOOL
R/W
U060 - User pump fl ow input logic (0 = NC, 1 = NO)
12
1
U061
BOOL
R/W
U061 - User pump overload input logic (0 = NC, 1 = NO)
13
1
U062
BOOL
R/W
U062 - 2nd set point input logic (0 = NO, 1 = NC)
14
1
U063
BOOL
R/W
U063 - User pump output logic (0 = NC, 1 = NO)
15
1
U064
BOOL
R/W
U064 - Global alarm relay output logic (0 = NC, 1 = NO)
16
1
U065
BOOL
R/W
U065 - Free cooling valve output logic (0 = NO, 1 = NC)
17
1
U066
BOOL
R/W
U066 - Frost protection heater output logic (0 = NC, 1 = NO)
18
1
U067
BOOL
R/W
U067 - Alarm relay confi guration (0 = Contrlo alarms, 1 = All alarms)
19
1
U068
BOOL
R/W
U068 - Enable free cooling (0 = disabled, 1 = enabled)
20
1
E000
BOOL
R/W
E000 - ExV circ. 1 enable manual mode
21
1
E002
BOOL
R/W
E002 - ExV circ. 2 enable manual mode
22
1
Hd06
BOOL
R/W
Hd06 - Enable power supply request from BMS (0 = Disabled, 1 = Enabled)
23
1
C001
BOOL
R/W
C001 - Comp. 1 circ. 1 reset hour counter
24
1
C004
BOOL
R/W
C004 - Comp. 2 circ.1 reset hour counter
25
1
C007
BOOL
R/W
C007 - Comp. 1 circ. 2 reset hour counter
26
1
C010
BOOL
R/W
C010 - Comp. 2 circ. 2 reset hour counter
27
1
C034
BOOL
R/W
C034 - High pressure switch input logic (0 = NC, 1 = NO)
28
1
C035
BOOL
R/W
C035 - Comp. overload input logic (0 = NC, 1 = NO)
29
1
C036
BOOL
R/W
C036 - Comp. output logic (0 = NO, 1 = NC)
30
1
C044
BOOL
R/W
C044 - Enable circuit destabilisation (0 = Disabled, 1 = Enabled)
31
1
S001
BOOL
R/W
S001 - Source pump 1 reset hour counter
33
1
S009
BOOL
R/W
S009 - Source fan 1 circ. 1 reset hour counter
34
1
S013
BOOL
R/W
S013 - Source fan 1 circ. 2 reset hour counter
35
1
S020
BOOL
R/W
S020 - Enable low noise (0 = Disabled, 1 = Enabled)
37
1
S043
BOOL
R/W
S043 - Enable sliding defrost (0 = Disabled, 1 = Enabled)
38
1
S055
BOOL
R/W
S055 - Comp. behaviour after defrosting
(0 = Comp. OFF, 1 = Comp. ON)
39
1
S061
BOOL
R/W
S061 - Source fan output logic (0 = NC, 1 = NO)
40
1
S062
BOOL
R/W
S062 - Source pump output logic (0 = NC, 1 = NO)
41
1
S063
BOOL
R/W
S063 - Reversing valve output logic (0 = NC, 1 = NO)
42
1
S064
BOOL
R/W
S064 - Source fl ow type (0 = Independent, 1 = Common)
44
1
S065
BOOL
R/W
S065 - Source fan type (0 = Inverter, 1 = ON/OFF)
46
1
S068
BOOL
R/W
S068 - Source type (0 = Air, 1 = Water)
47
1
UoM
BOOL
R/W
UM - Unit of measure used for 2-row display and BMS, not Applica
(0 = ° C / bar, 1 = ° F / PSI)
48
1
Hc02
BOOL
R/W
Hc02 - Enable analogue channel 4 (0 = Disabled, 1 = Enabled)
49
1
Hc12
BOOL
R/W
Hc12 - Digital output 6 confi g. (0 = Frost protection, 1 = Source fan / Source pump)
50
1
Hc13
BOOL
R/W
Hc13 - Enable buzzer (0 = Disabled, 1 = Enabled)
52
1
Ha02
BOOL
R/W
Ha02 - Set controller internal clock (0 = No setting, 1 = Set)
53
1
Hd03
BOOL
R/W
Hd03 - Enable NFC (0 = disabled, 1 = enabled)
54
1
UnSt
BOOL
R/W
UnSt - Unit ON/OFF command from keypad (0=OFF 1=ON)
55
1
ModE
BOOL
R/W
ModE - Cool/Heat mode from keypad (0 = Cool, 1 = Heat)
56
1
RES
BOOL
R/W
RES - Reset active alarms from BMS net (0 = NO, 1 = Reset)
59
1
ClrH
BOOL
R/W
ClrH - Delete alarm log (0 = No, 1 = Yes)
63
1
Hd05
BOOL
R/W
Hd05 - Enable unit ON/OFF command from BMS net (0 = Disabled, 1 = Enabled)