96
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Supervisor table
Index
S
ize
Ref.
Type
Min/Max
R/W
UoM
Description
265
1
S048
INT
0 to 999
R/W
s
S048 - Dripping duration
266
1
S049
INT
0 to 999
R/W
s
S049 - Post-dripping duration
267
1
S050
INT
0 to 999
R/W
min
S050 - Delay between defrosts
272
1
S053
INT
0..2
R/W
S053 - Defrost synchronisation type
(0 = Independent, 1 = Separate, 2 = Simultaneous)
274
2
S054
REAL
0..999.9
R/W
bar/psi
S054 - Pressure diff erential to reverse 4-way valve
278
1
S056
INT
20 to 999
R/W
s
S056 - Smart start function duration
279
2
S057
REAL
-999.9..999.9
R/W
°C/°F
S057 - Source frost protection alarm threshold
281
2
S058
REAL
0 to 999
R/W
K/R
S058 - Source frost protection alarm diff erential
283
1
S059
INT
0 to 999
R/W
s
S059 - Source frost protection alarm delay at 1K below the threshold
284
2
S060
REAL
-99.9..99.9
R/W
K/R
S060 - Source outside air temperature off set
286
1
Hc00
INT
0..3/4
R/W
Hc00 - Analogue input 3 confi guration (0 = not used, 1 = source temp., 2 = dis-
charge temp., 3 = suction temp., 4 = source delivery water temp.)
287
1
Hc01
INT
0..1
R/W
Hc01 - Analogue input 4 and 5 confi guration (0 = pressure, 1 = temp.)
288
1
Hc03
INT
0..2
R/W
Hc03 - Analogue input 6 confi guration (0 = not used, 1 = remote set point, 2 =
source temp.)
289
1
Hc04
INT
0..1
R/W
Hc04 - Analogue input 7 confi guration (0 = not used, 1 = suction temp.)
290
1
Hc05
INT
0..1
R/W
Hc05 - Analogue input 6 confi guration, circuit 2 board (0 = not used, 1 = remote
set point)
291
1
Hc06
INT
0..6
R/W
Hc06 - Digital input 4 confi guration (0 = Not used, 1 = Comp. 2 circ. 1 overload, 2
= Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote alarm, 6 = User
pump 1 overload)
292
1
Hc07
INT
0..6
R/W
Hc07 - Digital input 5 confi guration (0 = Not used, 1 = Comp. 2 circ. 1 overload, 2
= Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote alarm, 6 = User
pump 1 overload)
293
1
Hc08
INT
0..6
R/W
Hc08 - Digital input 6 confi guration (0 = Not used, 1 = Comp. 2 circ. 1 overload, 2
= Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote alarm, 6 = User
pump 1 overload)
294
1
Hc09
INT
0..5
R/W
Hc09 - Digital input 4 confi guration, circuit 2 board (0 = Not used, 1 = Comp. 2
circ. 2 overload, 2 = Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote
alarm, 6 = User pump 1 overload)
295
1
Hc10
INT
0..5
R/W
Hc10 - Digital input 5 confi guration, circuit 2 board (0 = Not used, 1 = Comp. 2
circ. 2 overload, 2 = Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote
alarm, 6 = User pump 1 overload)
296
1
Hc11
INT
0..5
R/W
Hc11 - Digital input 6 confi guration, circuit 2 board (0 = Not used, 1 = Comp. 2
circ. 2 overload, 2 = Remote ON/OFF, 3 = Cool/Heat, 4 = 2nd set point, 5 = Remote
alarm, 6 = User pump 1 overload)
297
1
Hc14
USINT
0..ID_CfgLim-
Max
R/W
Hc14 - Digital input 1 confi guration (0 = Not used, 1 = User fl ow switch, 2 = Comp.
1 circuit 1 overload, 3 = Comp. 2 circuit 1 overload, 4 = Remote ON/OFF, 5 = Cool/
Heat, 6 = 2nd set point, 7 = Remote alarm, 8 = User pump 1 overload, 9 = Low
pressure switch, 10 = User pump 2 overload, 11 = Remote control 1, 12 = Remote
control 2)
298
1
Hc15
USINT
0..ID_CfgLim-
Max
R/W
Hc15 - Digital input 2 confi guration (0 = Not used, 1 = User fl ow switch, 2 = Comp.
1 circuit 1 overload, 3 = Comp. 2 circuit 1 overload, 4 = Remote ON/OFF, 5 = Cool/
Heat, 6 = 2nd set point, 7 = Remote alarm, 8 = User pump 1 overload, 9 = Low
pressure switch, 10 = User pump 2 overload, 11 = Remote control 1, 12 = Remote
control 2)
299
1
Hc16
USINT
0..ID_CfgLim-
Max_Slv
R/W
Hc16 - Digital input 1 confi guration, circuit 2 board (0 = Not used, 1 = User fl ow
switch, 2 = Comp. 1 circuit 2 overload, 3 = Comp. 2 circuit 2 overload, 4 = Remote
ON/OFF, 5 = Cool/Heat, 6 = 2nd set point, 7 = Remote alarm, 8 = User pump 1
overload, 9 = Low pressure switch, 10 = User pump 2 overload, 11 = Remote
control 3, 12 = Remote control 4)
300
1
Hc17
USINT
0..ID_CfgLim-
Max_Slv
R/W
Hc17 - Digital input confi guration, circuit 2 board (0 = Not used, 1 = User fl ow
switch, 2 = Comp. 1 circuit 2 overload, 3 = Comp. 2 circuit 2 overload, 4 = Remote
ON/OFF, 5 = Cool/Heat, 6 = 2nd set point, 7 = Remote alarm, 8 = User pump 1
overload, 9 = Low pressure switch, 10 = User pump 2 overload, 11 = Remote
control 3, 12 = Remote control 4)
301
1
AI_Cf-
gLim-
Max_
Grp2
USINT
---
R/W
Maximum limit probe group 2
307
2
SEtC
REAL
U006..U007
R/W
°C/°F
SEtC - Cooling set point
309
2
SEtH
REAL
U008..U009
R/W
°C/°F
SEtH - Heating set point
324
2
C017
REAL
0..999.9
R/W
°C/°F
C017- Maximum high pressure threshold (HP)
326
2
C018
REAL
-99.9..99.9
R/W
bar/psi
C018 - Min low pressure threshold (LP)
328
1
E047
INT
0..2
R/W
E047 - Type of ExV driver (0 = Disabled, 1 = EVD embedded, 2 = EVD EVO)
335
2
P000
REAL
-999.9..999.9
R/W
°C/°F
P000 - Min evaporation temp. limit for custom envelope
337
2
P001
REAL
-999.9..999.9
R/W
°C/°F
P001 - Max condensing temp. limit for custom envelope
339
1
P002
INT
0 to 999
R/W
s
P002 - Min. prevent duration
340
1
P003
INT
0 to 999
R/W
s
P003 - Out of envelope alarm delay time
341
1
P004
INT
0 to 999
R/W
s
P004 - Low pressure diff erential alarm delay
342
2
P005
REAL
0..999.9
R/W
rps
P005 - Min BLDC speed threshold for circuit destabilisation
344
2
P006
REAL
0..100
R/W
%
P006 - Oil recovery min request for activation
346
2
P007
REAL
0..999.9
R/W
rps
P007 - Oil recovery min comp. speed for activation
348
1
P008
INT
0 to 999
R/W
min
P008 - Oil recovery time before activation in which the compressor can operate at
minimum speed
349
1
P009
INT
0 to 999
R/W
min
P009 - Oil recovery duration to override comp. speed
350
2
P010
REAL
0..999.9
R/W
rps
P010 - Oil recovery comp. override speed