μc0300053EN rel. 2.2 - 14.12.2021
Parameter table
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
M
C013
Min compressor off time
60
30
999
s
R/W
HR163
M
C014
Min time between consecutive compressor starts
360
300
999
s
R/W
HR164
M
C017
Max high pressure threshold (HP)
65.0
0.0
999.9
°C/°F
R/W
HR324 (2R)
M
C018
Min low pressure threshold (LP)
0.2
-99.9
99.9
bar/psi
R/W
HR326 (2R)
M
C020
Maximum circuit destabilisation time
240
5
999
min
R/W
HR168
M
C021
Circuit capacity distribution
(0 = balanced, 1 = grouped)
0
0
1
-
R/W
HR169
S
C022
Circuit 1: discharge temp. off set
0.0
-99.9
99.9
K/R
R/W
HR170 (2R)
S
C023
Circuit 1: suction temp. off set
0.0
-99.9
99.9
K/R
R/W
HR172 (2R)
S
C024
Circuit 2: discharge temp. off set
0.0
-99.9
99.9
K/R
R/W
HR174 (2R)
S
C025
Circuit 2: suction temp. off set
0.0
-99.9
99.9
K/R
R/W
HR176 (2R)
S
C026
Circuit 1: condensation pressure off set
0.0
-99.9
99.9
bar/psi
R/W
HR178 (2R)
S
C027
Circuit 1: evaporation pressure off set
0.0
-99.9
99.9
bar/psi
R/W
HR180 (2R)
S
C028
Circuit 1: condensing temp. off set
0.0
-99.9
99.9
K/R
R/W
HR182 (2R)
S
C029
Circuit 1: evaporation temp. off set
0.0
-99.9
99.9
K/R
R/W
HR184 (2R)
S
C030
Circuit 2: condensation pressure off set
0.0
-99.9
99.9
bar/psi
R/W
HR186 (2R)
S
C031
Circuit 2: evaporation pressure off set
0.0
-99.9
99.9
bar/psi
R/W
HR188 (2R)
S
C032
Circuit 2: condensing temp. off set
0.0
-99.9
99.9
K/R
R/W
HR190 (2R)
S
C033
Circuit 2: evaporation temp. off set
0.0
-99.9
99.9
K/R
R/W
HR192 (2R)
M
C034
HP pressure switch: input logic - 0/1=NC/NO
0
0
1
-
R/W
CS027
M
C035
Compressor overload protector: input logic
0/1=NC/NO
0
0
1
-
R/W
CS028
M
C036
Compressor: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS029
M
C037
Evaporation pressure: probe type
0=0-5V - 1=4-20mA
0
0
1
-
R/W
HR194
M
C038
Evaporation pressure probe: min value
0.0
-1.0
99.9
bar/psi
R/W
HR195 (2R)
M
C039
Evaporation pressure probe: max value
17.3
0.0
99.9
bar/psi
R/W
HR197 (2R)
M
C040
Condensation pressure: probe type -
0=0-5V - 1=4-20mA
0
0
1
-
R/W
HR199
M
C041
Condensation pressure probe: min value
0.0
-1.0
99.9
bar/psi
R/W
HR200 (2R)
M
C042
Condensation pressure probe: max value
45.0
0.0
99.9
bar/psi
R/W
HR202 (2R)
M
C043
Discharge temperature
Probe type (0=NTC, 1=NTC-HT)
1
0
1
-
R/W
204
M
C044
Enable destabilisation - 0/1=No/Yes
1
0
1
-
R/W
CS030
S
C045
Refrigerant
3=R407C - 4=R410a - 6=R290 - 10=R744 - 22=R32
4
0
99
-
R
IR038
M
C046
No. of unit circuits
1
1
2
-
R/W
HR206
M
C047
Type of compressors used
0=1 On/Off - 1=2 On/Off - 2=1 BLDC -
3= 1 BLDC+On/Off
0
0
3
-
R/W
HR207
M
C049
LP pressure switch: alarm delay from compressor start
If C049 = 0 the alarm is triggered even if
the compressors are off .
If C049 > 0 the alarm is only triggered
when the compressors are on
90
0
999
-
R/W
HR269
M
C050
LP pressure switch: alarm delay in steady operation
15
0
999
-
R/W
HR269
M
C051
HP pressure switch: input logic 0=NC 1=NO
0
0
1
-
R/W
CS76
Tab. 6.b
6.3
B
LD
C
and Inverter
User
Display
C
ode
Description
Def.
Min
Max
U
O
M
R/W
Modbus
S
P000
Min evaporation temp.: custom limit
-25.0
-99.9
999.9
°C/°F
R/W
HR335 (2R)
S
P001
Max condensing temp.: custom limit
70.0
-99.9
999.9
°C/°F
R/W
HR337 (2R)
M
P003
Out of envelope alarm delay
120
0
999
s
R/W
HR340
M
P004
Low pressure diff erential alarm delay
60
0
999
s
R/W
HR341
M
P006
Oil recovery: min request for activation
35.0
0.0
100.0
%
R/W
HR344 (2R)
M
P007
Oil recovery: min speed for activation
35.0
0.0
999.9
rps
R/W
HR346 (2R)
M
P008
Oil recovery: comp. operating time at low speed
15
0
999
min
R/W
HR348
M
P009
Oil recovery: force comp. speed time
3
0
999
min
R/W
HR349
M
P010
Oil recovery: force comp. speed value
50.0
0.0
999.9
rps
R/W
HR350 (2R)
M
P011
Oil equalisation: solenoid valve opening time at start-up 30
0
999
s
R/W
HR352
M
P012
Oil equalisation: solenoid valve opening time
3
0
999
s
R/W
HR353
M
P013
Oil equalisation: min solenoid valve closed time
1
0
999
min
R/W
HR354
M
P014
Oil equalisation: max solenoid valve closed time
15
0
999
min
R/W
HR355
M
P015
Oil equalisation: solenoid valve closed time increment
20
0
999
min
R/W
HR356
S
P016
Oil equalisation valve: output logic - 0/1=NO/NC
0
0
1
-
R/W
CS66
M
P017
Enable oil equalisation valve - 0/1=No/Yes
0
0
1
-
R/W
CS67
M
P018
Enable oil recovery - 0/1=No/Yes
0
0
1
-
R/W
CS68
S
x
P019
BLDC compressor circ.1: operating mode
0=AUTO; 1=0%, …101=100%
0
0101-
R/W
HR357
S
x
P020
BLDC compressor circ.2: operating mode
0=AUTO; 1=0%, …101=100%
0
0
101
-
R/W
HR358