33
ENG
μc0300053EN rel. 2.2 - 14.12.2021
Installation
Analogue inputs - Master circuit 1
Ref.
Description
Type
C
onfi guration parameters
S1
Return temperature from user
NTC
Hc31
S2
Delivery temperature to user
NTC
Hc32
S3
Discharge temperature
-
Hc00
S4
Condensing pressure
0-5V
Hc34; C040; 041; C042
S5
Evaporation pressure
0-5V
Hc35; C037; C038; C039
S6
Not present
-
Hc03; U025; U026; U027
S7
Suction temperature
NTC
Hc04
Tab. 2.bj
Notice:
the discharge temperature probe is automatically assigned type NTC-HT.
Analogue inputs - Slave circuit 2
Ref.
Description
Type
C
onfi guration parameters
S1
Not present
NTC
Hc41
S2
Not present
NTC
Hc42
S3
Discharge temperature
-
Hc00
S4
Condensing pressure
0-5V
Hc44; C040; 041; C042
S5
Evaporation pressure
0-5V
Hc45; C037; C038; C039
S6
Not present
-
Hc05; U025; U026; U027
S7
Suction temperature
NTC
Hc47
Tab. 2.bk
Digital inputs - Master circuit 1
Ref.
Description
C
onfi guration parameters
ID1
User pump fl ow switch
Hc14; U060
ID2
Compressor 1 overload
Hc15; C035
ID3
High pressure switch
C034
ID4
Not present
Hc06; C035; U059; U058; U062; U057; U061
ID5
Remote alarm
Hc07; C035; U059; U058; U062; U057; U061
ID6
2nd set point
HC08; C035; U059; U058; U062; U057; U061
Tab. 2.bl
Digital inputs - Slave circuit 2
Ref.
Description
C
onfi guration parameters
ID1
Pump 2 overload
Hc16; U061
ID2
Compressor 1 overload
Hc17; C035
ID3
High pressure switch
C034
ID4
Not present
Hc09; C035; U059; U058; U062; U057; U061
ID5
Not present
Hc10; C035; U059; U058; U062; U057; U061
ID6
Not present
Hc11
Tab. 2.bm
Digital outputs - Master circuit 1
Digital outputs - Slave circuit 2
Ref.
Description
C
onfi guration par-
am.s
Ref.
Description
C
onfi guration par-
am.s
C-NO1
Oil equalisation valve
(tandem compressors only)
Hc51; P017
C-NO1
Oil equalisation valve
(tandem compressors only)
Hc61; P017
C-NO2
Compressor 2
Hc52; C036
C-NO2
Compressor 2
Hc62; C036
C-NO3
User pump 1
Hc53; U063
C-NO3
User pump 2
Hc63; U063
C-NO4
Reversing valve (*)
Hc54; U066; S063; U065
C-NO4
Reversing valve (*)
Hc64; U066; S063; U065
C-NO5
Alarm
Hc55; U064
C-NO5
Alarm
Hc65
C-NO6
Frost protection heater
Hc56; Hc12
C-NO6
Frost protection heater
Hc66; Hc12
Tab. 2.bn
Tab. 2.bo
Notices:
• BLDC compressor driven by Power+ speed drive.
• (*) the confi guration of the output depends on the type of unit: heat pump (reverse- cycle) => reversing valve; Chiller with free
cooling (master only) => FC valve; otherwise => Frost protection heater.
Analogue outputs - Master circuit 1
Ref.
Description
Type
C
onfi guration parameters
N
otes
Y1
Modulating/On-Off fan
0-10V
Hc71
FCS1*0 /CONVONOFF
Y2
Not used
0-10V
Hc72
Tab. 2.bp
Analogue outputs - Slave circuit 2
Ref.
Description
Type
C
onfi guration parameters
N
otes
Y1
Modulating/On-Off fan
0-10V
Hc81
FCS1*0 /CONVONOFF
Y2
Not used
0-10V
Hc82
Tab. 2.bq
Содержание uChiller UCHBD00001230
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 105: ...105 ENG chiller 0300053EN rel 2 2 14 12 2021 Release notes Notes...
Страница 106: ...106 ENG chiller 0300053EN rel 2 2 14 12 2021 Notes...
Страница 107: ......