3.4 Steam hoses
•
use
C
A
REL
hoses
(max
.
4
m
long
,
see
“Models
of
steam
hoses”
,
page
30)
.
Rigid
pipes
may
break
and
cause
steam
leaks;
•
avoid
the
formation
of
pockets
or
traps
(causes
of
condensate);
•
avoid
choking
the
hose
due
to
tight
bends
or
twisting
.
•
fasten
the
end
of
the
hose
to
the
connectors
on
the
humidi
fi
er
and
the
steam
distributor
using
metal
clamps
,
so
that
these
do
not
detach
due
to
the
high
temperature
.
•
avoid
solicitations
involving
stress
on
the
shank
out
of
steam
cylinder
.
3.5 Condensate drain hose
During
the
operation
of
the
humidi
fi
er
some
of
the
steam
may
condense
,
causing
a
decline
in
e
ffi
ciency
and
noise
(gurgling)
.
T
o
drain
the
condensate
,
connect
a
drain
hose
with
a
drain
trap
and
a
minimum
slope
of
5°
to
the
bottom
of
the
humidi
fi
er
(see
Fig
.
3
.
d)
.
C
A
REL
condensate
drain
hoses:
code
cod
.
1312590
A
XX
.
Important
:
he
drain
trap
in
the
condensate
drain
hose
must
be
fi
lled
with
water
before
starting
the
humidi
fi
er
.
Example
of
correct
and
incorrect
installation
of
the
steam
hose
and
condensate
drain
hose
.
Final
chec
k
s
Ƒ
the
steam
outlet
hoses
run
upwards
and
the
distributor
has
a
minimum
incline
of
2°
upwards
(see
Fig
.
3
.
c);
Ƒ
the
ends
of
the
hose
are
tightened
to
the
fi
ttings
with
metal
clamps;
Ƒ
the
curves
in
the
tubing
are
su
ffi
ciently
wide
(radius
>
300
mm
/
11
.
8”)
so
as
to
not
cause
bending
or
choking;
Ƒ
the
steam
hose
has
no
pockets
or
traps
for
condensate
to
form;
Ƒ
the
paths
of
the
steam
and
condensate
hoses
are
as
described
in
this
chapter
(see
Fig
.
3
.
d);
Ƒ
the
length
of
the
steam
hose
is
no
greater
than
4
metres
(13
.
1
feet);
Ƒ
the
incline
of
the
steam
hose
is
su
ffi
cient
to
allow
correct
draining
of
the
condensate
(>
20°
for
the
upward
sections
,
>
5°
for
the
downward
sections);
Ƒ
the
incline
of
the
condensate
hose
is
at
least
5°
at
every
point;
Ƒ
the
condensate
hose
always
follows
a
downwards
path
and
features
a
drain
trap
(
fi
lled
with
water
before
starting
operation)
to
avoid
steam
being
released
.
Y
E
S
>5°
D> 200mm
>5°
R> 300mm
H
≤
2m
Y
E
S
>20°
>5°
D>200mm
R>300mm
1
A
ll
UE
models
Models
UE25
to
UE65
(1)
extend
the
hose
inside
the
humidi
fi
er
to
the
bottom
tank
.
Y
E
S
>20°
>5°
D>200mm
R>300mm
1
NO
NO
Models
UE001
to
UE025
(1):
connection
with
fi
ll
tank
A
ll
UE
models
Fig.
3.d