9.3 Cleaning and maintenance of the cylinder
Replacement
Important:
he
cylinder
must
be
only
be
replaced
by
quali
fi
ed
personnel
,
and
with
the
humidi
fi
er
unplugged
from
the
power
supply
.
In
normal
conditions
,
the
disposab
l
e
cy
l
inders
shou
l
d
be
rep
l
aced
after
one
year
(or
2500
hours
of
operation
,
if
cleaned
periodically)
,
while
the
openab
l
e
cy
l
inders
l
ast
5
years
(or
10
,
000
hours
of
operation
,
if
cleaned
periodically)
. T
hey
must
be
replaced
immediately
–
even
before
the
speci
fi
ed
intervals
–
if
any
anomalies
occur
.
For
example
,
when
the
lime
scale
inside
the
cylinder
prevents
the
correct
fl
ow
of
electric
current
.
T
he
cylinder
must
undergo
periodical
preventive
maintenance
by
Fortnightly
visual
and
be
replaced
either
when
depleted
(i
.
e
.,
full
of
lime
-
scale)
or
when
its
lifetime
has
expired
as
indicated
in
the
manual
or
when
any
anomalies
occur
. A
non
-
exhaustive
list
of
reasons
for
replacement
is:
•
T
here
is
too
much
lime
-
scale
inside
the
cylinder
with
electrodes
fully
covered
and
(almost)
touching
each
other:
this
can
be
seen
by
looking
into
the
cylinder
through
the
steam
outlet
or
by
opening
it
if
it
is
an
openable
cylinder
.
Comment:
it
is
normal
that
cylinders
fi
ll
with
lime
-
scale
because
this
is
naturally
contained
in
the
supply
water
.
Filling
with
lime
-
scale
is
not
an
anomaly
,
however
,
when
full
of
lime
-
scale
,
the
cylinder
must
be
replaced
•
T
he
lifetime
has
expired
as
indicated
in
the
manual
(2
,
500
hrs
for
disposable
cylinders
,
10
,
000
hrs
for
openable
cylinders)
•
A
nomaly
.
Dark
color
appearing
through
the
plastic
(black
,
dark
grey/brown)
because
this
would
likely
indicate
that
corrosion
of
the
electrodes
is
going
on;
in
such
a
case
,
additionally
,
check
that
the
supply
water
be
within
the
ranges
given
in
the
manual
,
always
remembering
that
softened
water
must
be
avoided
•
A
nomaly
.
Frequent
drains
along
with
E
A
/
A
F
warnings:
they
indicate
the
likely
presence
of
foam
or
mineral
deposits
in
the
inner
high
-
level
probe
that
generates
false
high
-
level/foam
drains
. T
ry
to
clean
the
cylinder
by
activating
the
pre
-fl
ushing
sequence
.
If
the
frequent
drains
persist
,
then
double
-
check
that
the
supply
water’s
quality
be
within
the
range
speci
fi
ed
in
the
manual
and
replace
the
cylinder
.
Comment:
foam
may
happen
,
but
if
it
happens
too
frequently
,
then
it
becomes
an
anomaly
•
A
nomaly
.
Cracks
on
the
plastic
•
A
nomaly
.
Water
leakage
from
the
connection
between
the
lower
and
upper
(lid)
parts
of
the
cylinder
.
If
the
cylinder
is
a
disposable
,
replace
it
asap;
if
it
is
an
openable
cylinder
,
try
to
properly
relocate
the
gasket
into
its
seat
,
eventually
replace
the
cylinder
if
the
leakage
persists
•
A
nomaly
.
Evident
signs
of
steam
leakage
on
to
the
cylinder’s
lid
around
the
electrodes
power
connections
•
A
nomaly
. A
ny
other
evident
or
suspicious
phenomenon
that
can
be
linked
to
problems
related
to
the
cylinder
C
A
REL
is
available
for
further
support
in
case
of
doubts
or
in
case
more
information
is
required
Replacement
procedure::
1
.
empty
all
the
water
(see
chap
.
6);
2
.
turn
o
ff
the
humidi
fi
er
(switch
“0”)
,
and
open
the
mains
disconnect
switch
on
the
power
supply
(safety
procedure);
3
.
wait
for
the
humidi
fi
er
and
the
cylinder
to
cool
down;
4
.
remove
the
front
cover;
5
.
disconnect
the
electrical
cables
from
the
cylinder;
6
.
release
the
cylinder
from
the
locking
device
and
lift
it
to
remove
it;
7
.
insert
the
new
cylinder
(make
sure
that
the
model
and
the
power
supply
of
the
new
cylinder
correspond
to
the
rated
data);
8
.
fasten
the
cylinder;
9
.
reconnect
the
electrical
cables
to
the
cylinder;
10
.
replace
the
front
cover;
11
.
switch
on
the
humidi
fi
er;
12
.
reset
cylinder
operating
hour
counter
(see
parameters
da
chap
.
7);
13
.
A
ctivate
the
wash
new
cylinder
procedure
,
pressing
EN
T
ER
+
DOWN
for
5
seconds
Periodical
checks
•
After
one
hour
of
operation:
check
for
any
signi
fi
cant
water
leaks
.
•
Every
1
5
days
or
no
more
than
300
operating
hours:
check
operation
,
the
absence
of
signi
fi
cant
water
leaks
,
the
general
conditions
of
the
casing
.
Check
that
during
operation
there
are
no
arcs
or
sparks
between
the
electrodes
.
•
Every
3
months
or
no
more
than
1000
operating
hours:
-
disposable
cylinders:
check
operation
,
the
absence
of
signi
fi
cant
water
leaks
and
if
necessary
replace
the
cylinder;
-
openable
cylinders:
if
there
are
signi
fi
cantly
blackened
areas
,
check
the
deposits
on
the
electrodes
and
clean
them
,
using
the
speci
fi
c
electrode
and
gasket
kit
.
•
Every
year
or
no
more
than
2500
operating
hours:
-
disposable
cylinders:
replace;
-
openable
cylinders:
if
there
are
signi
fi
cantly
blackened
areas
,
check
the
deposits
on
the
electrodes
and
clean
them
,
using
the
speci
fi
c
electrode
and
gasket
kit
.
•
After
5
years
or
no
more
than
10
,
000
operating
hours:
replace
the
openable
cylinder
.
A
fter
extended
operation
,
or
when
using
water
rich
in
salts
,
the
solid
deposits
that
naturally
form
on
the
electrodes
may
grow
until
attaching
to
the
inside
wall
of
the
cylinder
.
If
these
deposits
are
conductive
the
heat
generated
may
overheat
the
plastic
until
it
melts
,
with
the
risk
of
very
hot
water
being
released
.
Important
:
In
the
event
of
water
leaks
,
disconnect
the
power
supply
from
the
humidi
fi
er
as
the
water
may
conduct
electricity
.
9.4 Mechanically draining the water in the
cylinder
Drain
due
to
gravity
without
activating
the
humidi
fi
er
,
recommended
if:
•
humidi
fi
er
decommissioned;
•
to
empty
the
cylinder
without
switching
the
humidi
fi
er
on
.
Mechanical
drain:
•
make
sure
that
the
humidi
fi
er
is
not
powered;
•
remove
the
cover;
•
activate
the
mechanical
device
under
the
cylinder
(see
part
A,
Fig
.
9
.
e)
.
M
ode
l
s
UE00
1
to
UE0
1
8
M
ode
l
s
UE0
2
5
to
UE06
5
A
A
Fig.
9.e
9.5 Cylinder connection, three-phase models
UE025 to UE065
production
(
kg/h
)
conductivity
(
μS/cm
)
po
w
er
supp
l
y
(
V
)
23
0
400
25
75/350
μS/cm
A
B
350/1250
μS/cm
B
B
35
75/350
μS/cm
A
B
350/1250
μS/cm
A
B
45
75/350
μS/cm
A
A
350/1250
μS/cm
A
B
65
75/350
μS/cm
/
A
350/1250
μS/cm
/
B
T
ab.
9.f
T
he
cable
ends
must
be
tightened
with
the
top
nut
to
3
Newton
•
m
.
(units
with
BL*
T
5*
cylinder
only)