1. INTRODUCTION

The ir33+ platform for refrigeration applications comprises a series of 
microprocessor-based parametric electronic controllers, with LED display, 
designed to control stand-alone refrigeration units. Three ranges are 
available:

• 

ir33+;

• 

ir33+ wide and ir33+ small wide;

• 

easy wide and easy small wide.

which share the same software and diff er in terms of shape, user interface 
and the number of outputs. These controllers are especially suitable for 
applications requiring high load switching power, functions and control 
with direct access from the keypad, high IP ingress protection and 
compact dimensions. In terms of reliability, all the controllers are fi tted 
with an electronic device (watchdog) that prevents the microprocessor 
from losing control, even with high levels of electromagnetic disturbance. 
The ir33+ platform is made using the most advanced SMD technology, 
and electrical testing of all the components fi tted guarantees high quality 
standards.

In summary:

• 

up to 5 relay outputs on the more complete models: compressor, fan, 
defrost, AUX1, AUX2;

• 

panel installation (front panel as standard) or rear panel with separate 
fl exible keypad (can be customised);

• 

simple installation with two plastic fastening brackets (ir33+, ir33+ 
wide, ir33+ small wide) or with screws from the front (easy wide, easy 
small wide);

• 

buttons fl ush with the front panel, to ensure high ingress protection 
(IP65) and safety during operation and cleaning;

• 

bright 3 digit display, with decimal point and icons to denote operating 
status;

• 

immunity to brief power interruptions: if the controller detects that 
voltage drops below a certain threshold, the display is temporarily 
switched off  and the controller continues working normally;

• 

keypad with 4 (ir33+), 8 (ir33+ wide, ir33+small wide) or 9 buttons 
(easy wide, easy small wide);

• 

defrosts can be activated from the keypad, digital input, supervisor;

• 

management of various types of defrost, on one or two evaporators: 
natural (stopping the compressor), heater, hot gas;

• 

advanced defrost functions;

• 

automatic recognition of the network protocol: Carel or Modbus®;

• 

parameter selection simplifi ed by diff erent icons according to the 
category;

• 

temperature control with virtual control probe and set point variation 
at night;

• 

digital inputs to activate alarms, enable or activate defrosts, door / 
curtain switch, auxiliary output, on/off , etc.;

• 

control of 1 compressor with two steps, or two compressors, including 
rotation;

• 

keypad protection: the functions of the individual buttons can be 
disabled to prevent unwanted tampering;

• 

management of the light in the cabinet/cold room and the curtain on 
the cabinet;

• 

VPM program (Visual Parameter Manager), running on a personal 
computer, used to update the parameters and test the controller;

• 

alarm signal buzzer;

• 

HACCP functions: temperature monitoring and recording in the event 
of high temperature alarms during operation and after blackouts;

• 

RS485 serial network connection to remote supervisor and 
telemaintenance systems.

The models diff er in terms of:

• 

the type of power supply: alternating current (12 V~, 12 to 24 V~, 115 
V~, 115/230 V~, 230 V~, 50/60 Hz); direct current (12/18 Vdc, 12/30 
Vdc);

• 

the number of relay outputs;

• 

the type of probes that can be connected: NTC or NTC/PTC;

• 

the type of terminals: fi xed screw, plug-in or spade terminals.

Available accessories include:

• 

serial interface card (P/N IROPZ48500) for connection to the RS485 
network;

• 

programming key (P/N IROPZKEY**) for reading (upload) and writing 
(download) the control parameters;

• 

display interface (P/N IROPZDSP00) for remote display connection.

1.1 Main 

features

The ir33+ platform controllers are designed to off er maximum installation 
fl exibility. In addition to the control probe, a further three probes can be 
confi gured, as product probe (display only), condenser, frost protection 
and defrost probe. Using the advanced defrost functions, if the conditions 
are right, subsequent defrosts can be postponed or skipped. The digital 
outputs (relays) can control the solenoid valve or compressor, a second 
compressor, the evaporator or condenser fans, defrosts, lights and alarms. 
The digital inputs can be used for the door switch and light management, 
the curtain switch to change over to night-time operation, to enable 
and start defrosts, to switch the controller on/off  and to activate of the 
auxiliary output. Finally, the controller can also be used as simple ON/OFF 
thermostat, for heating applications.

Example: vertical display case and cold room.

Fig. 1.a

Fig. 1.b

Содержание easy small wide

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s ir33 platform ir33 ir33 wide ir33 small wide easy wide y easy small wide Electronic controller User manual...

Страница 2: ......

Страница 3: ...ot use corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those specified in the technical manual All of the above suggestions...

Страница 4: ...4 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 5: ...ter 31 6 8 Light and Aux outputs 32 6 9 Defrost 32 6 10 Evaporator fans 34 6 11 Condenser fans 35 6 12 Duty setting par c4 35 6 13 Running time defrost par d10 d11 35 7 PARAMETER TABLE 36 7 14 Variabl...

Страница 6: ...6 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 7: ...by different icons according to the category temperature control with virtual control probe and set point variation at night digital inputs to activate alarms enable or activate defrosts door curtain...

Страница 8: ...nstruction sheet 050003920 IREVXGD000 PST00VR100 Fig 1 g Fig 1 h RS485 serial interface P N IROPZ48500 and IROPZ485S0 Plugged directly into the programming key connector this provides connection to th...

Страница 9: ...Fig 2 e 2 2 Panel mounting To install the ir33 ir33 wide and ir33 small wide controllers use the 2 brackets shown in the figure 1 2 Fig 2 f 2 3 Rear panel mounting The models with separate membrane k...

Страница 10: ...o ir33 165 mm 21 mm 55 mm 26 1 mm Fig 2 j easy wide easy small wide STEP 1 Apply the two covered brackets to the controller Drill the holes with the spacing shown in the figure and make the opening fo...

Страница 11: ...xAxxxx 115 V 50 mA max SERIAL and KEY Fig 2 t 6 7 8 4 A 8A 2FLA 12LRA 1 2 3 4 5 8 9 10 11 12 PROBES DI DI L N 1 2 1 2 R1 R2 R1 R2 12 2 A 12A 5FLA 30LRA EN60730 1 UL 873 AUX 10T60 POWER SUPPLY 250 V Co...

Страница 12: ...on terminal 3 12 A Ixxxxx0xxxx 12 V 300 mA max 12 18 Vdc 300 mA dc max IxxxxxLxxxx 12 24 V 300 mA max 12 30 Vdc 300 mA dc max tLAN interface SERIAL and KEY IxxxF 0 7 0 L N C 0 2 xx Fig 2 ac 6 7 tLAN...

Страница 13: ...Corrente massima totale su terminale 3 12 A Maximum current on terminal 3 12 A L N 115 230 V 50 mA max tLAN interface SERIAL and KEY IxxxC 0 7 H N C 0 2 xx Fig 2 ad 6 7 8 4 A 8A 2FLA 12LRA 8 4 A 8A 2F...

Страница 14: ...o not use ethanol hydrocarbons petrol ammonia and by products Use neutral detergents and water 2 9 Programming key copy set up Programming key IROPZKEY00 A0 The programming key can load up to 7 differ...

Страница 15: ...g the settings of the dipswitches on the key 1 open the rear cover on the key and position the 2 dipswitches according to the desired operation 2 close the rear cover on the key and plug the key into...

Страница 16: ...s of the parameters The remote display IREVXGD000 PST00VR100 shows the temperature with resolution to the tenths between 9 9 C and19 9 C Note the standard display on the user terminal and the remote d...

Страница 17: ...he continuous cycle AUX DOWN SET DEF if pressed together for more than 1 second displays a submenu used to access the HACCP alarm parameters SET DEF If pressed for more than 1 s displays and or lets t...

Страница 18: ...the set point differential temperature monitoring interval interval between defrosts end defrost temperature dripping time alarm thresholds alarm bypass times etc See the parameter table Procedure 1 p...

Страница 19: ...P DOWN button for at least 5 seconds all the changes made to the parameters temporarily stored in the RAM can be cancelled by not pressing any button for 60 seconds thus returning to the standard disp...

Страница 20: ...st deactivation on ir33 On Off To switch the controller off from the keypad press On Off for 3 seconds The display shows the text Off flashing for 3 seconds and then on steady Finally the text Off alt...

Страница 21: ...inally press Prg for 5 seconds to save the value of the parameter HACCP menu The controller must be fitted with the RTC real time clock To enter the HACCP menu press the combination button shown the t...

Страница 22: ...ple in the case of bottle coolers typically used in supermarkets where the doors are opened frequently due to the greater thermal inertia of the liquids compared to the air and the fact that the probe...

Страница 23: ...ogramming key Procedure power down the controller power up while holding Prg mute the display will show the first set bn0 press UP DOWN to select set bn1 to bn6 For example select bn2 press Set to con...

Страница 24: ...reasing order with that configuration Par Description Def Min Max UOM A2 Probe 2 configuration S2 M models 0 0 4 A2 Probe 2 configuration S2 0 Absent 1 Product display only 2 Defrost 3 Condenser 4 Fro...

Страница 25: ...delayed external alarm is thus signal only 3 Probe shown on the display IR33M models On thermometer only models this setting selection is used to exploit the digital input in order to show on the disp...

Страница 26: ...close the door If after being closed for the first time the door remains closed for longer than time d8 or d8d the controller resumes normal operation compressor and evaporator fan switched on if nee...

Страница 27: ...r3 direct reverse operating mode When the contact is open the controller operates in direct mode cooling when the contact is closed in reverse mode heating A switch can therefore be connected to sele...

Страница 28: ...when the internal timer is set Relay output protectors parameters c7 c8 c9 Par Description Def Min Max UOM c0 Compressor fan and AUX start delay at power on 0 0 15 min c1 Minimum time between success...

Страница 29: ...r4 Automatic night time set point variation 3 0 20 20 C F 4 Virtual probe composition 0 control probe S1 100 probe S2 0 0 100 Tab 6 b Parameter 4 is used to determine the virtual probe Sv as the weigh...

Страница 30: ...wn whenever closing pump down valve following low pressure switch activation with no cooling demand c10 Pump down by time or pressure 0 1 pressure time 0 0 1 Tab 6 d Note c8 is a masked parameter and...

Страница 31: ...alarm signal can be ignored by suitably setting parameter c6 alarm bypass after continuous cycle Par Description Def Min Max UOM cc Continuous cycle duration 0 0 15 hour c6 Low temperature alarm bypa...

Страница 32: ...me 4 heater by time with temperature control The defrost can end by temperature in which case the defrost probe Sd must be installed or by time In the first case the defrost ends when the defrost prob...

Страница 33: ...valve Pump down Pump down stage FAN Evaporator fan Def Defrost V_def Hot gas valve Drip Dripping E Evaporator Post drip Post dripping C Condenser S2 Defrost probe V2 Thermostatic expansion valve L Li...

Страница 34: ...situation of this type it is preferable to enable defrost on start up above all if the defrost is controlled by temperature probe on the evaporator therefore avoiding unnecessary defrosts or at least...

Страница 35: ...20 C F Tab 6 o ON OFF FAN F4 F5 Sc F4 F4 0 2 First switch on t t Fig 6 t Key Sc Condenser probe Sv Virtual probe FAN Condenser fans t Time F4 Deactivation temperature F5 Differential Note if no conde...

Страница 36: ...irtual probe 5 Probe 4 2 Probe 1 6 Reserved 4 Probe 3 MSYFCH 0 0 6 I 19 119 R W C P Type of probe 0 NTC Standard Range 50T90 C 1 NTC Enhanced Range 40T150 C 2 PTC Standard Range 50T150 C MSYFCH 0 0 2...

Страница 37: ...shown 4 heater by time with temperature control Ed1 Ed2 not shown SYFCH 0 0 4 I 37 137 R W F dI Maximum time between consecutive defrosts 0 defrost not performed SYFCH 8 0 250 hr min I 38 138 R W F dt...

Страница 38: ...ed SYFCH 0 0 250 min I 54 154 R W C A8 Enable alarms Ed1 and Ed2 end defrost by timeout 0 alarms disabled SYFCH 0 0 1 D 49 49 R W C Ado Light management with door switch Ado Light when ope ning the do...

Страница 39: ...sweat heater function disabled F MSYFCH 0 50 200 C F A 37 37 R W C HrL Remote light relay status on Master 0 disabled MSYFCH 0 0 1 D 62 62 R W C HrA Remote AUX relay status on Master 0 disabled MSYFCH...

Страница 40: ...of parameter sets available I 137 237 R Digital input 1 status D 6 6 R Digital input 2 status D 7 7 R Virtual probe fault alarm D 9 9 R Probe alarm 1 D 10 10 R Probe alarm 2 D 11 11 R Probe alarm 3 D...

Страница 41: ...controller itself on the probes or in network communication An alarm can also be activated from an external contact immediate or delayed See paragraph 5 2 The display shows IA or dA and at the same t...

Страница 42: ...year month day hours minutes and duration in minutes of the selected alarm press Prg mute again to return to the previous list In addition the HACCP alarm menu allows the following operations delete t...

Страница 43: ...nal contact ON ON automatic duty setting A6 duty setting A6 OFF OFF OFF duty setting A6 dA Delayed alarm from external contact ON ON automatic duty setting A6 OFF if A7 0 OFF if A7 0 OFF if A7 0 duty...

Страница 44: ...old or the contact closes the alarm is not signalled and the count is reset When a new alarm condition occurs the count starts from 0 again Parameter A6 has a similar meaning to parameter c4 duty sett...

Страница 45: ...erature alarm threshold Acd Alarm delay cht High cond temperature pre alarm Sc Condenser probe CHT High condensing temperature alarm AE High condensing temperature alarm differential 8 8 Frost protect...

Страница 46: ...1 FLA 6 LRA C300 30000 IRxxxx E A N R C B A M L T xxx R1 R2 8 4 A N O 6 4 A N C 100000 8 A res 2 FLA 30000 IRxxxx 0 L H N R C B A M L T xxx R2 R3 R4 2 2 A N O N C 12 LRA C300 IRxxxx E A P Q S U V X Y...

Страница 47: ...ing cycles 250 V operating cycles PBEVxx E A P S V Y xxx 5A 5 1 A 100000 5A res 1FLA 6 LRA C300 30000 PBEVxx E A N C A L xxx PBEVxx O H N C A L xxx 8 A 8 4 A N O 6 4 A N C 2 2 A N O N C 100000 8 A res...

Страница 48: ...5A on model IRYS0EP 8 A Programming keypad key Special functions HACCP Real Time Clock Function can be enabled when Real Time Clock option available models IR C B L T S U Y Z and on IR33 power models...

Страница 49: ...twork interface Note standard Tab 9 e 9 6 easy wide part numbers Features PBEVS0EAAA PBEVY0EVD0 PBEVC0HND0 PBEVC0HNBA PBEVC0HCAA PBEVH0HNAA PBEVH0HNB0 PBEVH0HNBW PBEVS0SAFA PBEVC0SNFA PBEVC0SNFW Power...

Страница 50: ...PZKEYA0 connected to the computer via the converter IROPZPRG00 When opening the VPM program choose the device to be configured ir33 The Home page is displayed with the options to create a new project...

Страница 51: ...he right button choose Add set for each additional set Fig 10 i Set1 is displayed Fig 10 j Note onthecontroller Set0 Set1 Set6arenamedbn0tobn6respectively Set0 is the default set on the controller i e...

Страница 52: ...d starting from the eighth defrost Note if there are two evaporators the defrost duration used to determine the defrosts to be skipped is the longer nominal defrost duration Possible operating sequenc...

Страница 53: ...2 The following situations may occur if the outputs are not configured or there are probe alarms DEFROST BY TEMPERATURE Defrost probe evap output config Situation Effect Probe 2 defrost output 1 No pr...

Страница 54: ...of operation ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 1 t t t t Fig 11 d ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 2 t t t t Fig 11 e ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OF...

Страница 55: ......

Страница 56: ...EL INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency ir33plus 0300028EN rel 1 1 05 05 2...

Отзывы: