1. Heater defrost (d0 = 0, 2, 4): duty cycle
The duty cycle refers to the default values of parameters F2 and F3.
C
L
CMP
T
V2
E
S2
M
V_Pd
ir33+
S
F
Fig. 6.n
ON
OFF
ON
OFF
t
CMP
V_Pd
ON
OFF
FAN
ON
OFF
RES
REFRIG
PUMP
DOWN
DEF
DRIP
(dd)
POST DRIP
(Fd)
REFRIG
c8
Fig. 6.o
Key
CMP
Compressor
Refrig
Cooling
V_Pd Pump down valve
Pump down Pump down stage
FAN
Evaporator fan
Def
Defrost
RES
Heater
Drip
Dripping
E
Evaporator
Post drip
Post-dripping
C
Condenser
S2
Defrost probe
V2
Thermostatic expansion valve
L
Liquid receiver
F
Filter-drier
S
Liquid gauge
t
Time
Note:
•
in pump down mode, the behaviour of the fan is determined by F2;
•
in defrost, the behaviour of the fan is determined by F3.
2. Hot gas defrost (d0 = 1, 3): duty cycle
The duty cycle refers to the default values of parameters F2 and F3.
C
L
CMP
T
V2
E
S2
V_Pd
M
M
V_def
ir33+
S
F
Fig. 6.p
Note:
the defrost output (DEF) is used to control the hot gas valve
V_def.
ON
OFF
ON
OFF
t
CMP
V_Pd
ON
OFF
FAN
ON
OFF
V_def
(HOT GAS)
REFRIG
PUMP
DOWN
DEF
DRIP
POST
DRIP
REFRIG
c8
c8
Fig. 6.q
Key
CMP
Compressor
Refrig
Cooling
V_Pd
Pump down valve
Pump down Pump down stage
FAN
Evaporator fan
Def
Defrost
V_def Hot gas valve
Drip
Dripping
E
Evaporator
Post drip
Post-dripping
C
Condenser
S2
Defrost probe
V2
Thermostatic expansion valve
L
Liquid receiver
F
Filter-drier
S
Liquid gauge
t
Time
The defrost starts:
•
by setting the event and the start mode, with a maximum of 8 defrosts
each day (parameters td1 to td8). The real time clock (RTC) must be
available;
•
from the supervisor, which sends the defrost call to each controller via
the serial line;
•
from the keypad.
The defrost ends:
•
when the defrost probe measures a temperature greater than the end
defrost temperature dt1;
•
when no defrost probe is used, the defrost ends after a maximum time,
set by parameter dP1.
Maximum time between consecutive defrosts
Par. Description
Def
Min Max UOM
dI
Maximum time between consecutive defrosts
0 = defrost not performed
8
0
250
hr/
min
Tab. 6.k
Parameter dI is a safety parameter used to perform cyclical defrosts
every “dI” hours, even without the Real Time Clock (RTC). It is also useful
if the RS485 serial network is disconnected. At the start of each defrost,
irrespective of the duration, an interval starts being counted. If this
interval exceeds dI without a defrost being performed, one is started
automatically. The count is always active even if the controller is OFF.